Corrigo E. Lon-interface variable list Covers all versions of Corrigo E.-LON from revision Revision: 8 Date:

Similar documents
BACNET LISTE - CORRIGO VERSJON 3.7

Corrigo E Ventilation

Sensor Plug-In Description / Documentation

TEC226x-3 and TEC220x-3 Series LONWORKS Network Staged Thermostats

IntesisBox ME-AC-LON-1 v

Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT

LonWorks Integration Instructions

PolyGard Digital Transmitter DGC DT-02

OP5U. Pre-programmed, configurable controller for simple applications

Functional Profile. SOMFY animeo LON Sensor Interface WM Ref

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

LON I/O Module DR-N MCU4-AC Art. no.: MTN881811

Introduction to BAS Technology

NEUROLOGIC RESEARCH CORPORATION

Technical manual GS 4x.00 knx application description air quality sensor

Fan-coil intelligent unitary controller

ECL-VAV Series Preloaded Applications. User Guide

Relay (R1) 003. Balancing Valve. Slab Pump (P1) Max. 4 pipe diameters apart. Injection Pump (P2) 150 No 24V only. Power. Off.

CONTENTS Project name WMHpc Revision 1.3

Software Description STCN_55_1_01 for STC 04 FTT and STC 65 FTT

Metasys Zoning Package Commissioning

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Modbus VAV Controller Configuration Properties

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Software description LON bus

TAC5 Regulation + SAT KNX Module

6$3+,5 8QLYHUVDO/21,QWHUIDFH9$&;,93URGXNW/%$SSOLFDWLRQY[ (QJLQHHULQJ*XLGH 6LHPHQV%XLOGLQJ7HFKQRORJLHV +9$&3URGXFWV. CE2Y3226en/IVP

Control equipment. Regula 1.4. lindab we simplify construction

MicroTech II Applied Rooftop Unit Controller Protocol Information

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

Application Sheet Supply and extract VAV with analog VAV controller, heating and cooling coil and hot water radiator on triac output

Variable Air Volume Modular Assembly (VMA) 1200 Series Controllers

Cetetherm IQ Heat Midi/Maxi

Control panel touch screen MOD. 80

Application Sheet Active chilled beam with variable fan, cooling coil and hot water radiator on triac output

CAN-I/O 45 CAN-I/O Module 45 Software Version 1.13 Programming Functions Manual Version 1.13

REH FC-BMS3 Modbus Manual

IS-3000 SERIES INFRARED SCANNER

OJ Air Pressure VENTILATION CONTROLLERS AND PRESSURE TRANSMITTERS. full-range pressure and ventilation control HVAC CONTROLS & POWER

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block

B 520 ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS. RTB C2 Eng. COSTER BUS. B RTB C2 Eng MC REV 01

Tracer LonTalk Communication Interface for ReliaTel Controls for light and large commercial units with a ReliaTel control platform

Brief description. Type overview

Fan Coil Actuator FCA 2

Application Sheet Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Relay Driver Overview and Applications

CONTROL UNITS. VEHICLE EXHAUST GASES Pure advantages VEHICLE EXHAUST GASES

Universal Controller

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE

Application sheet for Green 300 series controllers. Title. Purpose. Application Controller Loop Configuration: Wiring: Explanation :

ELECTRONIC THERMOSTAT: T920

CONTROL MANUAL. Dry-Pic 09PE - 09VE

Zone controller TAC Xenta 102

Think About Control Fundamentals Training. Terminology Control. Eko Harsono Control Fundamental - Con't

CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

Functional description "BIU-2ILT"

Brief description. VAV-Compact LON en-gb Changes reserved 1. Application. Pressure measurement

LONMARK Functional Profile: Air Velocity Sensor

DESCRIPTION NOTE MODEL 2200VM

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

Self-powered RadioTechnology for Building Automation Systems

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Electro Controls. Input-Output Modules WattsIndustries.co.uk

Stryker CVAHU WEBs-N4 Configuration Wizard Guide

FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications. Features and Benefits

NRT 105: Electronic fan-coil controller, equiflex

NX Series Inverters. HVAC Pocket Programming Guide

Electronic Controls For general purpose and multi stages controls. Features and Benefits

TAC 2112 Manual (GB),

Optidrive Applications Support Library

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665

STC-KNX (32-channel AP)

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user)

R7L-YV2. DC VOLTAGE OUTPUT MODULE, 2 points MODEL BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL R7L-YV2

E V1. System Manager Installation Manual

KNX ENO 634 (32-channel AP)

Installation and User Guide

Differential pressure sensors

Microprocessor Based Multistage Temperature Controller & Two Channel 365 Day Time Switch. Made in Australia 100% Australian Owned Company

User Instructions For TopTronic RS-10

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682

Analogue temperature controllers

control & display PROGRAMMABLE SENSOR CONTROLLER COMPLETE VERSATILITY OF UNDERGROUND SENSOR MANAGEMENT & DATA COMMUNICATIONS

User manual. KNX MultiController DALI. Article number: 5410x / 5411x. function Technology AS

DDC volume flow controller

Unidirectional Gateway EnOcean - KNX/BUS

NEW MEXICO STATE UNIVERSITY NMDA

Introduction To Temperature Controllers

User Manual. KNX MultiLight Dali. Article number: function Technology AS. Picture: KNX MultiLight products

Product Specifications

APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

SKS B2 120 GDD 69/11 - A11 MA PB

Transcription:

Corrigo E Lon-interface variable list Covers all versions of Corrigo E.-LON from revision 1.2-1-0 Revision: 8 Date: 11-08-19 Copyright AB REGIN, Sweden, 2011

About the manual This document covers all versions of the LON-profiles. Certain variables are only available for later versions of the Corrigo software. These variables are marked with a number. Explanations are provided after each section. All variables are backward-compatible. New in this version: the profile for ventilation has been updated to version 3.1. See page 5. Corrigo E Ventilation Application files, CorrigoEVentilation.apb and CorrigoEVentilation.xif The files CorrigoEVentilation.APB and CorrigoEVentilation.XIF are included in the E tool distribution. E tool can be downloaded free of charge from Regin's website: www.regin.se. After downloading and installing E tool, the files can be found in the folder: Exo\Slib\Corrigo\VentilationProgram\Lon. Use the file CorrigoEVentilationX_Y that corresponds to the revision in the Corrigo. The files CorrigoEVentilationX_Y-S should be used when the unit is marked S. Table of Network Variables, Outputs (NVO) Name SNVT type Description nvooutdoortemp SNVT_temp_p Outdoor temperature nvosuppairtemp SNVT_temp_p Supply air temperature nvoexstairtemp SNVT_temp_p Extract air temperature nvoroomtemp SNVT_temp_p Room temperature nvoextrasensor SNVT_temp_p Temperature, extra sensor nvosafpressure SNVT_press_p Pressure, Supply air fan nvoeafpressure SNVT_press_p Pressure, Extract air fan nvosafairflow SNVT_flow Flow, Supply air fan (l/s) nvoeafairflow SNVT_flow Flow, Extract air fan (l/s) nvodeicingtemp SNVT_temp_p Temp. De-icing sensor heat exchanger nvofrostprottemp SNVT_temp_p Temp. Frost protection sensor nvoco2 SNVT_ppm CO 2 nvoroomhumidity SNVT_lev_precent Room humidity nvorunindication SNVT_state Bit0 Run indication, Supply air fan Bit1 Run indication, Extract air fan Bit2 Run indication, Pump, heating Bit3 De-icing heat exchanger active nvoao1 SNVT_volt_f Output signal Ao1 nvoao2 SNVT_volt_f Output signal Ao2 nvoao3 SNVT_volt_f Output signal Ao3 nvoao4 SNVT_volt_f Output signal Ao4 nvoao5 SNVT_volt_f Output signal Ao5 nvoao1exp1 SNVT_volt_f Output signal Ao1 Expansion unit 1 (6) nvoao2exp1 SNVT_volt_f Output signal Ao2 Expansion unit 1 (6) nvoao3exp1 SNVT_volt_f Output signal Ao3 Expansion unit 1 (6) nvoao4exp1 SNVT_volt_f Output signal Ao4 Expansion unit 1 (6) nvoao5exp1 SNVT_volt_f Output signal Ao5 Expansion unit 1 (6) nvodo SNVT_state Bit0 Output signal Do1 2 Corrigo E - Lon-interface variable list

Name SNVT type Description Bit1 Output signal Do2 Bit2 Output signal Do3 Bit3 Output signal Do4 Bit4 Output signal Do5 Bit5 Output signal Do6 Bit6 Output signal Do7 Bit7 Output signal Do1 Expansion unit 1 (6) Bit8 Output signal Do2 Expansion unit 1 (6) Bit9 Output signal Do3 Expansion unit 1 (6) Bit10 Output signal Do4 Expansion unit 1 (6) Bit11 Output signal Do5 Expansion unit 1 (6) Bit12 Output signal Do6 Expansion unit 1 (6) Bit13 Output signal Do7 Expansion unit 1 (6) nvovvxexcheffi SNVT_lev_percent Heat exchanger efficiency monitoring nvosetpoint SNVT_temp_p Setpoint, Supply air nvocascadesetp SNVT_temp_p Setpoint cascade control. Depending on configuration (Room temp if room control is configured, Extract air temp if extract air control is configured) nvomaxlimit SNVT_temp_p Max limit Supply temperature nvominlimit SNVT_temp_p Min limit Supply temperature nvoalarm SNVT_state_64 Bit0 Run error Supply air fan Bit1 Run error Extract air fan Bit2 Run error P1-Heating Bit3 Run error P1-Cooling Bit4 Run error P1-Exchanger Bit5 Filter guard Bit6 Flow guard Bit7 External frost guard Bit8 De-icing heat exchanger Bit9 Fire alarm Bit10 External stop Bit11 External alarm Bit12 Control error Supply air controller Bit13 Not used Bit14 High supply air temperature Bit15 Low supply air temperature Bit16 Supply air max limit active Bit17 Supply air min limit active Bit18 Too high room temperature Bit19 Too low room temperature Bit20 Too high extract air temperature Bit21 Too low extract air temperature Bit22 Overheating protection active Bit23 Frost risk Bit24 Frost protection active Bit25 Low efficiency heat exchanger Bit26 Sensor error Bit26 Sensor error outdoor temperature (4) Bit27 Analogue de-icing of heat exchanger active Bit28 Rotation guard heat exchanger Bit29 Fire damper is out of operation Bit30 Control error Supply air fan Bit31 Control error Extract air fan Bit32 External operation Supply air fan Bit33 External operation Extract air fan Bit34 Manual running mode Bit35 Manual operation Supply air controller Corrigo E - Lon-interface variable list 3

Name SNVT type Description Bit36 Manual operation Supply air fan Bit37 Manual operation SAF Frequency converter Bit38 Manual operation Extract air fan Bit39 Manual operation EAF Frequency converter Bit40 Manual output Heating Bit41 Manual output Exchanger Bit42 Manual output Cooling Bit43 Manual operation P1-Heating Bit44 Manual operation P1-Cooling Bit45 Manual operation P1-Exchanger Bit46 Manual operation Fire damper Bit47 Internal Battery error Bit48 Sensor error Supply air temp (4) Bit49 Sensor error Extract air temp (4) Bit50 Sensor error Room temp 1 (4) Bit51 Sensor error Room temp 2 (4) Bit52 Sensor error Exhaust air temp (4) Bit53 Sensor error Extra sensor (4) Bit54 Sensor error SAF pressure (4) Bit55 Sensor error EAF pressure (4) Bit56 Sensor error De-icing temp (4) nvoalarm SNVT_state_64 Bit57 Sensor error Frost protection temp (4) Bit58 Sensor error CO2 (4) Bit59 Sensor error Humidity room (4) Bit60 Sensor error Humidity duct (4) nvorunmode SNVT_state Binary 0 = Stop 1 = Starting up 2 = Starting half speed 3 = Starting full speed 4 = Alarm delay 5 = Normal operation 6 = Support control Heating 7 = Support control Cooling 8 = CO 2 control 9 = Free cooling 10 = Full speed stop 11 = Fan stop 12 = Fire run (5) 13 = Recirculation run (5) 14 = De-icing (5) Table of Network Variables, Inputs (NVI) Name SNVT type Description nvioutdoortemp SNVT_temp_p Outdoor temperature. Overrides signal from local sensor nviroomtemp SNVT_temp_p Room temperature. Overrides signal from local sensor nvifullspeedext SNVT_switch Force to full speed (1) nviexternalstop SNVT_switch External stop (1) nvifirealarm SNVT_switch Fire alarm (1) nvisetpoint SNVT_temp_p Setpoint Supply air nvicascadsetp SNVT_temp_p Setpoint cascade control. Depending on configuration (Room temp if room control is configured, 4 Corrigo E - Lon-interface variable list

Extract air temp if extract air control is configured) nvimaxlimit SNVT_temp_p Max limit Supply air nviminlimit SNVT_temp_p Min limit Supply air nviocccmd SNVT_occupancy 0 = The unit is forced to run at 1/1-speed (3) 1 = Shut down. Support control and free cooling not active. Frost protection active if configured 2 = Runs according to the built-in timer. Support control and free cooling active if configured 3 = Unit stopped. Support control and free cooling active if configured. Frost protection active if configured nvisndhrtb SNVT_time_sec Heart Beat (0 = disable) nvitemphyst SNVT_temp_p Hysteresis for variables of the type _temp_p (2) nvico2hyst SNVT_ppm Hysteresis for variables of the type _ppm (CO 2 ) (2) nvipercenthyst SNVT_lev_percent Hysteresis for variables of the type _lev_percent (2) nvipreshyst SNVT_press_p Hysteresis for variables of the type _press_p (Pressure) (2) nviairflowhyst SNVT_flow_p Hysteresis for variables of the type _flow_p (Air flow)(2) nvivolthyst SNVT_volt_f Hysteresis for variables of the type _volt_f (Ao) (2) nvisfpressetpnor SNVT_press_p Setpoint pressure supply air fan normal operation (5) nviefpressetpnor SNVT_press_p Setpoint pressure extract air fan normal operation (5) nvisfpressetptred SNVT_press_p Setpoint pressure supply air fan reduced operation (5) nviefpressetptred SNVT_press_p Setpoint pressure extract air fan reduced operation (5) nvisfairflowsetpnor SNVT_flow Setpoint flow supply air fan normal operation (5) nviefairflowsetpnor SNVT_flow Setpoint flow extract air fan normal operation (5) nvisfairflowsetptred SNVT_flow Setpoint flow supply air fan reduced operation (5) nviefairflowsetptred SNVT_flow Setpoint flow extract air fan reduced operation (5) nviparatransfer SNVT_temp_p Parallel displacement of the supply air setpoint at outdoor compensated supply air temperature control (6) (1) For these parameters it is possible to use both a local hard-wired digital input and the Lon parameter. Activation of either alternative will trigger the function. However, if a function has been set using the Lon network it must also be reset using the Lon network since the nvi input value cannot be reset locally. (2) The hysteresis variables have nothing to do with the control software in the controller. They are internal to the LON interface and are used for minimising the amount of communication in the LON network. (3) Only Corrigo E version 1.8 or later. CorrigoEVentilation1_8.APB and CorrigoEVentilation1_8.xif are also required. (4) Only Corrigo E version 2.1 or later. CorrigoEVentilation2_1.APB and CorrigoEVentilation2_1.xif are also required. (5) Only Corrigo E version 3.0 or later. CorrigoEVentilation3_0.APB and CorrigoEVentilation3_0.xif are also required. The flow variables are given in l/s, i.e. you divide the value by 3.6 to convert it to m 3 /h. (6) Only Corrigo E version 3.1 or later. CorrigoEVentilation3_1.APB and CorrigoEVentilation3_1.xif are also required. Corrigo E - Lon-interface variable list 5

Corrigo E Heating Application files, CorrigoEHeating.apb and CorrigoEHeating.xif The files CorrigoEHeating.APB and CorrigoEHeating.XIF are included in the E tool distribution. E tool can be downloaded free of charge from Regin's website: www.regin.se. After downloading and installing E tool, the files can be found in the folder: Exo\Slib\Corrigo\HeatingProgram\Lon. Use the file CorrigoEHeatingX_Y that corresponds to the revision in the Corrigo. The files CorrigoEHeatingX_Y-S should be used when the unit is marked S. The first time a Corrigo E Heating controller is used in a LON network, the application file CorrigoEHeating.apb must be loaded to the Corrigo E. Use Echelon LonMaker (or any other LON network program that can download application software to a LON device). Table of Network Variables, Outputs (NVO) Name SNVT type Description nvohs1supplytemp SNVT_temp_p Actual value, Supply temperature HS1 nvohs2supplytemp SNVT_temp_p Actual value, Supply temperature HS2 nvohs3supplytemp SNVT_temp_p Actual value, Supply temperature HS3 nvohs1supplysetp SNVT_temp_p Setpoint, Supply temperature HS1 nvohs2supplysetp SNVT_temp_p Setpoint, Supply temperature HS2 nvohs3supplysetp SNVT_temp_p Setpoint, Supply temperature HS3 nvooutdoortemp SNVT_temp_p Outdoor temperature nvohs1roomtemp SNVT_temp_p Room temperature HS1 nvohs2roomtemp SNVT_temp_p Room temperature HS2 nvohs3roomtemp SNVT_temp_p Room temperature HS3 nvohw1supplytemp SNVT_temp_p Actual value, Supply temperature HW1 nvohw2supplytemp SNVT_temp_p Actual value, Supply temperature HW2 nvohw1supplysetp SNVT_temp_p Setpoint, Supply temperature HW1 nvohw2supplysetp SNVT_temp_p Setpoint, Supply temperature HW2 nvohp1supplytemp SNVT_temp_p Storage tank, Supply temperature nvohp1starttemp SNVT_temp_p Storage tank, Start temperature nvohp1stoptemp SNVT_temp_p Storage tank, Stop temperature nvoboilertemp SNVT_temp_p Boiler temperature, Actual value nvoboilstarttmp1 SNVT_temp_p Boiler, Start temperature 1 nvoboilstarttmp2 SNVT_temp_p Boiler, Start temperature 2 nvoboilerstoptmp SNVT_temp_p Boiler, Stop temperature nvowindspeed SNVT_speed Wind speed nvodp SNVT_press_f Differential pressure nvodpsetp SNVT_press_f Setpoint, Differential pressure nvovolume SNVT_vol_kilo Volume, Hot water nvocw1volume SNVT_vol_kilo Volume, Cold water 1 nvocw2volume SNVT_vol_kilo Volume, Cold water 2 nvoao1 SNVT_volt_f Output signal Ao1 nvoao2 SNVT_volt_f Output signal Ao2 nvoao3 SNVT_volt_f Output signal Ao3 nvoao4 SNVT_volt_f Output signal Ao4 nvoao5 SNVT_volt_f Output signal Ao5 6 Corrigo E - Lon-interface variable list

Name SNVT type Description nvorunind SNVT_state Bit0 HS1-P1A Run indication Bit1 HS1-P1B Run indication Bit2 HS2-P1A Run indication Bit3 HS2-P1B Run indication Bit4 HS3-P1A Run indication Bit5 HS3-P1B Run indication Bit6 HW1-P1 Run indication Bit7 HWB-P1 Run indication Bit8 Frequency converter Run indication Bits9 15 not used nvodovalue SNVT_state Bit0 Output signal Do1 Bit1 Output signal Do2 Bit2 Output signal Do3 Bit3 Output signal Do4 Bit4 Output signal Do5 Bit5 Output signal Do6 Bit6 Output signal Do7 Bits7 15 not used nvoalarm SNVT_state_64 Bit0 Run error P1A-HS1 Bit1 Run error P1B-HS1 Bit2 Run error P1A-HS2 Bit3 Run error P1B-HS2 Bit4 Run error P1A-HS3 Bit5 Run error P1B-HS3 Bit6 Run error P1-Hot water 1 Bit7 Run error P1-Storage tank Bit8 Run error frequency converter Bit9 Expansion vessel alarm Bit10 External alarm Bit11 Alarm, Boiler Bit12 HS1 control error Bit13 HS2 control error Bit14 HS3 control error Bit15 HW1 control error Bit16 HW2 control error Bit17 Sensor error Bit17 Sensor error outdoor temperature (4) Bit18 High supply temp. HW1 Bit19 High supply temp. Boiler Bit21 Low supply temp. Boiler Bit22 Pulse error, volume pulse Bit23 Pulse error, energy pulse Bit24 High 24 hour usage Cold water Bit25 High energy consumption Bit24 High hour usage Cold water Bit27 Leakage Bit28 Run error P1A&B-HS1 Bit29 Run error P1A&B-HS2 Bit30 Run error P1A&B-HS3 Bit31 Pulse error CW1 Bit32 Pulse error CW2 Bit33 Max. limit supply temp. HS1 Bit34 Max. limit supply temp. HS2 Bit35 Max. limit supply temp. HS3 Bit36 Min. limit supply temp. HS1 Bit37 Min. limit supply temp. HS2 Bit38 Min. limit supply temp. HS3 Bit39 Max. limit return temp. HS1 Bit40 Max. limit return temp. HS2 Corrigo E - Lon-interface variable list 7

Name SNVT type Description nvoalarm SNVT_state_64 Bit41 Max. limit return temp. HS3 Bit42 Min. limit return temp. HS1 Bit43 Min. limit return temp. HS2 Bit44 Min. limit return temp. HS3 Bit45 Frost protection HS1 Bit46 Frost protection HS2 Bit47 Frost protection HS3 Bit48 Internal battery error Bit49 Low return temp Boiler (4) Bit50 Sensor error HS1 Supply (4) Bit51 Sensor error HS2 Supply (4) Bit52 Sensor error HS3 Supply (4) Bit53 Sensor error HW1 Supply (4) Bit54 Sensor error HW2 Supply (4) Bit55 Sensor error HP1 Supply (4) Bit56 Sensor error HS1 Room (4) Bit57 Sensor error HS2 Room (4) Bit58 Sensor error HS3 Room (4) Bit59 Sensor error HS1 Return (4) Bit60 Sensor error HS2 Return (4) Bit61 Sensor error HS3 Return (4) Bit62 Sensor error HP1 Return (4) Bit63 Sensor error Wind (4) Table of Network Variables, Inputs (NVI) Name SNVT type Description nvioutdoortemp SNVT_temp_p Outdoor temperature. Overrides signal from local sensor nvihs1roomtemp SNVT_temp_p Room temp HS1. Overrides signal from local sensor nvihs2roomtemp SNVT_temp_p Room temp HS2. Overrides signal from local sensor nvihs3roomtemp SNVT_temp_p Room temp HS3. Overrides signal from local sensor nvihw1setp SNVT_temp_p Setpoint, Supply HW1 nvihw2setp SNVT_temp_p Setpoint, Supply HW2 nvidpsetp SNVT_press_f Setpoint Differential pressure nvisndhrtb SNVT_time_sec Heart Beat (0 = disable) nvitemphyst SNVT_temp_p Hysteresis for the variable type _temp_p (2) nvipreshyst SNVT_press_f Hysteresis for the variable type _press_f (2) nvispeedhyst SNVT_speed Hysteresis for the variable type _speed (2) nvivolthyst SNVT_volt_f Hysteresis for the variable type _volt_f (Ao) (2) (2) The hysteresis variables have nothing to do with the control software in the controller. They are internal to the LON interface and are used for minimising the amount of communication in the LON network. (4) Only Corrigo E version 2.1 or later. CorrigoEHeating2_1.APB and CorrigoEHeating2_1.xif are also required. 8 Corrigo E - Lon-interface variable list