Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

Similar documents
Harmonics Elimination Using Shunt Active Filter

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

POWER QUALITY IMPROVEMENT USING SHUNT ACTIVE FILTER

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Active Harmonics Filtering of Distributed AC System

Harmonics Reduction using 4-Leg Shunt Active Power Filters

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

Modeling of Shunt Active Filter Using P-Q Theory

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

ISSN Vol.03,Issue.42 November-2014, Pages:

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

ABSTRACT I. INTRODUCTION

Implementation and Comparison of Different Switching Techniques for Shunt Active Power Filters

ISSN: (Online) Volume 2, Issue 2, February 2014 International Journal of Advance Research in Computer Science and Management Studies


Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

2020 P a g e. Figure.2: Line diagram of series active power filter.

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Power Quality Improvement in Fourteen Bus System using UPQC

Power Quality Improvement using Shunt Passive Filter

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Power Control Scheme of D-Statcom

Shunt Active Power Filter for Compensation of System Harmonics

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

THE P-Q THEORY FOR ACTIVE FILTER CONTROL: SOME PROBLEMS AND SOLUTIONS

INSTANTANEOUS POWER THEORY AND APPLICATIONS TO POWER CONDITIONING

Universal power quality conditioner

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Three-Level Shunt Active Filter Compensating Harmonics and Reactive Power

ISSN Vol.03,Issue.07, August-2015, Pages:

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Power Control and Quality Management in DG Grid Interfaced Systems

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

P.CHAITHANYAKUMAR, T.VARAPRASAD/

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Review on Shunt Active Power Filter for Three Phase Four Wire System

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Effective Algorithm for Reducing DC Link Neutral Point Voltage and Total Harmonic Distortion for Five Level Inverter

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Literature Review for Shunt Active Power Filters

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Comparison of Control Algorithms for Shunt Active Filter for Harmonic Mitigation

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

IMPROVING THE OUTPUT OF CASCADED FIVE LEVEL MULTILEVEL INVERTER USING LOW PASS BROADNBAND FILTER

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Simulation and Experimental Results of 7-Level Inverter System

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Control Strategy for a cross phase connected and a conventional UPQC

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

CONTROL TECHNIQUES FOR ACTIVE POWER FILTER FOR HARMONIC ELIMINATION & POWER QUALITY IMPROVEMENT

Transcription:

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 07, 2016 ISSN (online): 2321-0613 Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter Megha Ramteke 1 S.P.Phulambrikar 2 Prateek Jain 3 1 Assistant Professor 2 Professor 3 P.G. Scholar 1,2,3 Department of Electrical Engineering 1,2,3 Samrat Ashok Technological Institute Vidisha, Madhya Pradesh Abstract With the rapid use of power electronics devices such as rectifier, inverter etc. in power system causes serious problem with power quality. One among them is generation of current and voltage harmonics causing distortion of load waveforms, fluctuation in voltages, voltage dip, heating etc. Also presence of non-linear loads such as UPS, SMPS, drives etc. are the reason of current harmonics in power system. They draw reactive power components of current from mains causing disturbance in supply current waveform. Thus to avoid the consequences of harmonics we have to compensate the harmonics in power system. Among various methods used, one of the favourable way to compensate harmonics in power system is the effective use of Shunt Active Power Filter (SAPF). This research work gives detail performance analysis of SAPF with the help or control strategy of instantaneous active and reactive power theory i.e. p-q theory. Here we took 3 phase diode rectifier and simulation analysis is done to justify the method better over other. In this method a reference current is generated, which compensate harmonic current component in power system and THD of the source current is reduced. And system performance enhanced. Key words: THD, P-Q Theory I. INTRODUCTION Harmonic pollution is more common in low voltage side due to wide use of nonlinear loads (UPS, SMPS, Rectifier etc.), which is not desirable as it causes serious voltage fluctuation and voltage dip in power system. So it is required to eliminate these undesirable current and voltage harmonics and to compensate the reactive power, to improve the performance of the power system network. The use of traditional passive filter in removing harmonics is not that much effective because their static action and no real time action or dynamic action is taken for the removal of harmonics. But the shunt active power filter on the other hand gives promising results when compared with conventional active and passive filters. This project basically shows the current control strategy i.e instantaneous active-reactive power method which is helpful to reduce the current harmonics when used with SAPF through MATLAB simulation and modeling. II. THE P-Q THEORY In 1983, Akagi have proposed the "The Generalized Theory of the Instantaneous Reactive Power in 3-Phase Circuits, which is also known as instantaneous power theory, or p-q theory. This theory is based on the instantaneous values in 3- phase power systems with or without neutral wire, and this is applicable for steady-state operation of the system or transitory operations as well as for generic voltage and current waveforms. The p-q theory consists of an algebraic transformation which is known as Clarke transformation of the three-phase voltages and currents in the a-b-c coordinates to the α-β-0 coordinates and followed by the calculation of the p-q theory instantaneous power components: The power components which are p(active power) and q(reactive power) are related to the same α-β voltages and currents, and the power component can be written as: These power quantities are illustrated for an electrical system represented in a-b-c coordinates and have the following meaning: P0 = it is the mean value of the instantaneous zerosequence power which is related to the energy per time unity. From the power supply this energy is transferred to the load through the zero-sequence components of V(voltage)and I(current). ~p0 = it is the alternated value of the instantaneous zero-sequence power. Physical meaning of this term is the energy/time unity that is transferred between the power supply and the load through the zero-sequence components. The zero-sequence power only exists in 3-phase systems with neutral wire. Furthermore, the systems must have unbalanced V(voltages) and I (currents) and/or third order harmonics in both voltage and current of at least one phase. p = mean value of the instantaneous real power. Which corresponds to the energy/time unity. This energy is transferred from the supply to the load, in a balanced manner(it is the desired power component). ~p = it is the alternated value of the instantaneous real power. It is the energy/time unity. This energy is exchanged between the power supply and the load via the abc coordinates. q =it is the instantaneous imaginary power corresponds to the power that is transferred between the phases of the load. This component doesn t imply any transference or exchange of energy between the power supply and the load, but this is responsible for the existence of undesirable currents which circulate between the system phases. In the case of a balanced voltage supply and a balanced load, with or without harmonics, q (it is the mean value of the instantaneous imaginary power) is equal to the conventional reactive power ( q = 3 V I1 sin φ1 ). All rights reserved by www.ijsrd.com 211

To determine the reference compensation currents in the α-β coordinates, the expression (5) is inverted, and the powers to be compensated ( ~p p0 and q ) are used: Fig. 1: Power components of the p-q theory in a-b-c coordinates. A. The P-Q Theory Applied To Shunt Active Filters: The p-q theory is one of the various methods that can be used in the control active filters. It has some interesting features, namely: It is inherently a 3-phase system theory, It can be applied to any 3-phase system (balanced or unbalanced with or without the harmonics in voltages and currents), It is based on instantaneous values, allowing tremendous dynamic response, Its calculations are relatively easy (it is only includes algebraic expressions which can be implemented using by std. processors), It allows two control strategies:- one is constant instantaneous supply power and other is sinusoidal supply current. As seen before, p is the only desirable p-q theory power component. The other various quantities can be compensated using a shunt active filter. P0 can be compensated without the any power supply need in the shunt active filter. This quantity is transferred from the power supply to the load via the active filter (see Fig.2.2 ). This means that the energy previously transferred from the source to the load via the zero-sequence components of voltage and current, is now transferred in a balanced way through the source phases. It is also possible to conclude from Fig. that the active filter capacitor is only needs to compensate ~p and ~p0, since these quantities need to be stored in this component at one moment to be later transferred to the load and The instantaneous imaginary power [ q]which also includes the conventional reactive power is compensated without the needs of the capacitor. This means that the capacitor size does not depend on the amount of reactive power to be compensated. Since the zero-sequence current must be compensated, the reference compensation current in the 0 coordinate is i0 itself: ic0* = i0 In order to calculate the reference compensation currents in the a-b-c coordinates the inverse of the transformation given in expression (1) is applied. The calculation given so far are synthesized in Fig.2.3 and similar to a shunt active filter control strategy for constant instantaneous power supply. This approach when applied to a 3-phase system with balanced sinusoidal voltages, produces following results (Fig.): The phase supply currents become in phase with the voltages, sinusoidal, balanced (in other words the supply sees the load as a purely resistive symmetrical load), The neutral current is become equal to zero (even third order current harmonics are compensated); The total instantaneous power supplied is made constant. In the case of a non-sinusoidal or unbalanced supply voltage, the only difference is that the supply current will also includes harmonics (Fig2.3), but in practical cases the distortion is negligible. Fig 2: Compensation of power componenets in a,b,c coordinates. Fig. 3: Calculation for the constant instantaneous power supply control strategy. The sinusoidal supply current control technique must be used when the voltages are distorted or sinusoidal and unbalanced currents are desired. The block diagram of Fig.2.3 presents the calculations required in this case. When this strategy is used the results, illustrated in Fig.2.4, are: The Phase Supply Currents Will Become Sinusoidal, Balanced, And Become In Phase With The Fundamental Voltages, And The Neutral Current Is Made Nearly Equal To Zero (Even Third Order Current Harmonics Are Compensated); All rights reserved by www.ijsrd.com 212

The Total Instantaneous Power Supplied (P3s) Isn t Made Constant, But It Gives Only A Small Ripple (Much Smaller Than Before Compensation). Fig. 4: Calculations for the sinusoidal supply current control strategy. III. SIMULINK MODEL IV. CONTROL CIRCUIT Fig. 5: All rights reserved by www.ijsrd.com 213

V. SIMULATION RESULT A. 3 Phase Source Voltage And Current Waveform without SAPF: Fig. 6: C. Αβ0 Reference Current: D. Αβ0 Reference Power: Fig. 9: αβ0 reference current. Fig. 7: 3 phase source current with harmonics. B. Αβ0 Reference Voltage: Fig. 10: (a) Zero sequence power (b) Active Power (c)reactive Power Fig. 8: αβ0 reference voltage All rights reserved by www.ijsrd.com 214

E. Compensating Current In Αβ0 Coordinates: I. Source Current Waveform With and Without Harmonics. Fig. 11: (a) Zero sequence compensating current. (b)α sequence compensating current. (c) β sequence compensating current. F. Compensating Current in Abc Coordinates from Αβ0 Coordinates: Fig. 15: Source current waveform with and without harmonics. VI. RESULT Three phase diode bridge rectifier is simulated in matlab/simulink. Various parameters used for simulation is given in table 6.1. the model was run for 0.5 seconds. In the wavforms it is clearly shown that the harmonics before 0.15 seconds and after 0.15 seconds when filter injects the compensation current, harmonics are eliminated from source current. FFT analysis is done for both the conditions and results are compared. %THD Before SAPF 19.61% Fig. 12: compensating current in abc coordinate. G. Current Fed in System: Fig. 13: Compensating Current fed in system. H. Filtered Source Current: Fig. 14: Current Comparision after & before the SAPF. After SAPF 1.03% Table 1: From above table it is clear that the harmonics are reduced/compensated to a great extend using this theory i.e. the p-q theory and THD is reduced from 19.61% to 1.04%. VII. CONCLUSION AND FUTURE SCOPE From MATLAB/SIMULINK simulation of hysteresis current controller based active power filter of 3 phase diode rectifier, it is found that THD of source current is reduced to 1.04 % from 19.61 % after use of filter. Reactive power required by nonlinear load is completely compensated by active power filter (APF) and power factor at source end becomes almost unity. Active filters are an up-to-date solution to power quality problems. Shunt active filters allow the compensation of current harmonics and unbalance, together with power factor correction, and can be a much better solution than the conventional approach (capacitors for power factor correction and passive filters to compensate for current harmonics). This paper presents the p-q theory as a suitable tool to the analysis of non-linear three-phase systems and for the control of active filters. The implementation of active filters based on the p- q theory are cost-effective solutions, allowing the use of a large number of low-power active filters in the same facility, close to each problematic load (or group of loads), avoiding the circulation of current harmonics, reactive currents and neutral currents through the facility power lines. All rights reserved by www.ijsrd.com 215

REFERENCES [1] Joao Afonso, Carlos Couto, Julio Martins, Active filters with control based on the p-q Theory, IEEE Industrial Electronics Society Newsletter vol.47,sept. 2000, ISSN:0746-1240, PP. 5-10 [2] Hirofumi Akagi, Edson H. Watanabe, Mauricio Aredes, INSTANTANEOUS POWER THEORY AND APPLICATIONS TO POWER CONDITIONING, New jersey: IEEE Press/ Wiley-Interscience, 2007, ISBN: 978-0-470-10761-4. [3] Joao L. Afonso, M.J. Sepulveda Freitas, Julio S. Martins, p-q Theory Power Components Calculations, ISIE 2003- IEEE, ISBN: 0-7803-7912-8. [4] R.A. Kapgate, N.T. Sahu (YCCE,Nagpur), Basic Of P-Q Theory for Shunt and Series Compansation, IJAIS-ISSN: 2249-0868. [5] Fukao, T., Iida and Miyairi, S. (1972) ''Improvements of the Power Factor of Distorted Waveforms by Thyristor Based Switching Filter,'' Transactions of the IEE-Japan, Part B, vol. 92, no.6, pp. 342-349 (in Japanese). [6] Gyugyi, L. and Pelly, B. R. (1976) ''Static Power Frequency Changers: Theory, Performance and Application'', John Wiley & Sons, New York. [7] Harashima, F., Inaba, H. and Tsuboi, K. (1976) ''A Closed-loop Control System for the Reduction of Reactive Power Required by Electronic Converters,'' IEEE Trans. IECI, vol. 23, no. 2, May, pp. 162-166. [8] Watanabe, E. H., Stephan, R. M. and Aredes, M. (1993) "New Concepts of Instantaneous Active and Reactive Powers in Electrical Systems with Generic Loads," IEEE Trans. Power Delivery, vol. 8, no. 2, Apr., pp. 697-703. [9] Gyugyi, L. and Strycula, E. C. (1976) "Active ac Power Filters," in Proc. IEEE Ind. Appl. Ann. Meeting, vol. 19- C, pp. 529-535. [10] Takahashi, I. and Nabae, A. (1980) "Universal Reactive Power Compensator," IEEE Industry Application Society Annual Meeting Conference Record, pp. 858-863. [11] Takahashi, I. Fujiwara, Y. and Nabae, A. (1981) "Distorted Current Compensation System Using Thyristor Based Line Commutated Converters," Transactions of the IEE-Japan, Part B, vol. 101, no.3, pp. 121-128 (in Japanese). All rights reserved by www.ijsrd.com 216