Translated English of Chinese Standard: GB4824-2013 www.chinesestandard.net Sales@ChineseStandard.net GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA ICS 33.100 L 06 GB 4824-2013 / IEC/CISPR 11:2010 Replacing GB 4824-2004 Industrial, scientific and medical (ISM) radio-frequency equipment - Disturbance characteristics -Limits and methods of measurement (IEC/CISPR 11:2000, IDT) 工业 科学和医疗 (ISM) 射频设备骚扰特性限值和测量方法 Issued on: December 31, 2013 Implemented on: January 13, 2015 Issued by: General Administration of Quality Supervision, Inspection and Quarantine; Standardization Administration Committee. www.chinesestandard.net Page 1 of 62
Table of Contents Foreword... 4 1 Scope... 7 2 Normative references... 7 3 Terms and definitions... 9 4 Frequencies designated for ISM use... 10 5 Classification of ISM equipment... 11 6 Limits of electromagnetic disturbances... 12 7 Measurement requirements... 27 8 Special provisions for test site measurements (9 khz to 1 GHz)... 38 9 Radiation measurements: 1 GHz to 18 GHz... 42 10 Measurement in situ... 43 11 Safety precautions... 43 12 Assessment of conformity of equipment... 43 13 Figures and flowcharts... 46 Annex A (Informative) Examples of equipment classification... 49 Annex B (Informative) Precautions to be taken in the use of a spectrum analyzer (see 7.3.1)... 52 Annex C (Normative) Measurement of electromagnetic radiation disturbance in the presence of signals from radio transmitters... 54 Annex D (Informative) Propagation of interference from industrial radiofrequency equipment at frequencies between 30 MHz and 300 MHz... 55 www.chinesestandard.net Page 2 of 62
Annex E (Informative) Recommendations of CISPR for protection of certain radio services in particular areas... 56 Annex F (Informative) Frequency bands allocated for safety-related radio services... 58 Annex G (Informative) Frequency bands allocated for sensitive radio services... 59 Bibliography... 61 www.chinesestandard.net Page 3 of 62
Foreword All technical content of this Standard is mandatory. This Standard was drafted in accordance with the rules given in GB/T 1.1-2009. This Standard replaces GB 4824-2004 Industrial, scientific and medical (ISM) radio-frequency equipment--electromagnetic disturbance characteristics-- Limits and methods of measurement. Compared with GB 4824-2004, the main changes are as follows: - specified the application scope of Clause 1; - modified Clause 2 Normative references ; - in Clause 3 Terms and definitions, added 4 definitions of industrial, scientific and medical (ISM) (RF energy) applications, equipment for resistance welding and allied processes, low voltage and small equipment; - in Clause 6 Limits of electromagnetic disturbances, the main changes were summarized as: category A high-power equipment limit changes (a group of power dividing line ~ 20kVA, 2 sets of power dividing line 75kVA); for category A equipment, the 3m limit was added, but only for small equipment; - in 7.5 Configuration of equipment under test, added For a separation distance of 3 m the assessment of the radiation from the cabling of the EUT shall be restricted to those fractions of interconnecting cables (see 7.5.2) and mains cables (see 7.5.3) which are within the test volume of 1.2 m diameter times 1.5 m height above ground. Peripheral equipment not fitting into the test volume shall be excluded from the measurements or decoupled from the test environment. ; - in 7.6 Load conditions of equipment under test, modified industrial equipment, microwave cooking appliances, single and multiple-zone induction cooking appliances, welding equipment ; - added 7.7 Recording of test-site measurement results ; - added 12.5 Measurement uncertainty ; - added Annex A Examples of equipment classification ; - added Annex E Recommendations of CISPR for protection of certain radio services in particular areas. www.chinesestandard.net Page 4 of 62
This Standard uses translation method and identically adopts International Electrotechnical Commission IEC/CISPR 11:2010 Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics - Limits and methods of measurement. It only made the following modifications: - modified Annex G Frequency bands allocated for sensitive radio services so as to make it suit the national conditions of China by referring to Provisions on Radio Frequency Division of the People's Republic of China (2010) (Decree No. 16 of the Ministry of Industry and Information Technology). The Chinese documents which have consistency with the international normative references in this Standard are as follows: - GB/T 4365-2003 Electrotechnical terminology - Electromagnetic compatibility [IEC 60050 (161), IDT] - GB/T 6113.101-2008 Specification for radio disturbance and immunity measuring apparatus and methods - Part 1-1: Radio disturbance and immunity measuring apparatus - Measuring apparatus (IEC/CISPR 16-1- 1:2006, IDT) - GB/T 6113.104-2008 Specification for radio disturbance and immunity measuring apparatus and methods - Part 1-4: Radio disturbance and immunity measuring apparatus-ancillary equipment - Radiated disturbance (IEC/CISPR 16-1-4:2005, IDT) - GB/T 6113.203-2008 Specification for radio disturbance and immunity measuring apparatus and methods - Part 2-3: Methods of measurement of disturbances and immunity - Radiated disturbance measurements (IEC/CISPR 16-2-3:2003, IDT) - YY 0505-2005 Medical electrical equipment - Part 1-2: General requirements for safety - Collateral standards: Electromagnetic compatibility - Requirements and tests (IEC 60601-1-2:2001, IDT) - GB 9706.4-2009 Medical electrical equipment - Part 2-2: Particular requirements for the safety of high frequency surgical equipment (IEC 60601-2-2:2006, IDT) This Standard was proposed by and shall be under the jurisdiction of National Technical Committee on Radio Interference of Standardization Administration of China (SAC/TC 79). Main drafting organization of this Standard: Shanghai Electric Apparatus Research Institute. www.chinesestandard.net Page 5 of 62
The drafting organizations of this Standard: Shanghai Sanki Electronic Industry Co., Ltd., Beijing Institute of Medical Instrumentation, Beijing General Electric Warren Medical Equipment Co., Ltd., Guangdong Galanz Group Co., Ltd., Shanghai Electric Automation Design & Research Institute Co., Ltd., Zunyi Product Quality Inspection Testing Institute. Main drafters of this Standard: Ye Qiongyu, Zhang Jun, Meng Zhiping, Ren Jie, Lu Yanhan, Qian Feng, Shou Jianxia, Huang Wenguang, Liu Yuan, Zheng Junqi, Lu Jianping, Zhang Zongqin. The previous versions replaced by this Standard are as follows: - GB 4824-1984, GB 4824-1996, GB 4824-2001, GB 4824-2004. www.chinesestandard.net Page 6 of 62
Industrial, scientific and medical (ISM) radio-frequency equipment - Disturbance characteristics - Limits and methods of measurement 1 Scope This Standard applies to industrial, scientific and medical electrical equipment operating in the frequency range 0 Hz to 400 GHz and to domestic and similar appliances designed to generate and/or use locally radio-frequency energy. This standard covers emission requirements related to radio-frequency (RF) disturbances in the frequency range of 9 khz to 400 GHz. Measurements need only be performed in frequency ranges where limits are specified in Clause 6. For ISM RF applications in the meaning of the definition found in the ITU Radio Regulations (see Definition 3.1), this standard covers emission requirements related to radio-frequency disturbances in the frequency range of 9 khz to 18 GHz. Requirements for ISM RF lighting apparatus and UV irradiators operating at frequencies within the ISM frequency bands defined by the ITU Radio Regulations are contained in this standard. Equipment covered by other CISPR product and product family emission standards are excluded from the scope of this standard. NOTE Induction cooking appliances are in the process of being transferred from GB 4824 to GB 4343.1. Until the removal of induction cooking appliances from the scope of GB 4824, users of the standards may choose either GB 4824 or GB 4343.1 for testing. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. GB/T 4365, Electrotechnical terminology - Electromagnetic compatibility [IEC 60050(161), IDT] www.chinesestandard.net Page 7 of 62
Bibliography [1] CISPR 16-4-4:2007, Specification for radio disturbance and immunity measuring apparatus and methods - Part 4-4: Uncertainties, statistics and limit modelling - Statistics of complaints and a model for the calculation of limits for the protection of radio services (only available in English) [2] GB 17743-2007, Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment [3] IEC 60050-601:1985, International Electrotechnical Vocabulary (IEV) - Chapter 601: Generation, transmission and distribution of electricity - General [4] IEC/TR 60083:2006, Plugs and socket-outlets for domestic and similar general use standardized in member countries of IEC [5] GB/T 16895.18-2010, Electrical installations of buildings - Part 5-51: Selection and erection of electrical equipment - Common rules (IEC 60364-5-51:2005, IDT) [6] GB/T 18800-2002, Household microwave oven - Methods for measuring performance (IEC 60705:1999, IDT) [7] GB/T 10066.9-2008, Test methods for electroheat installations - Part 9: The determination of power output for High-frequency dielectric heating installation (IEC 61308:2005, IDT) [8] YY/T 0750-2009, Ultrasonics - Physiotherapy systems - Field specifications and methods of measurement in the frequency range 0.5 MHz to 5 MHz (IEC 61689:2007, IDT) [9] GB/T 10066.31-2007, Test methods for electroheat installations - Part 31: High-frequency induction heating installation- Test methods for the determination of power output of the generator (IEC 61922:2002, IDT) [10] A.A. SMITH, Jr., Electric field propagation in the proximal region, IEEE Transactions on electromagnetic compatibility, Nov 1969, pp.151-163. [11] CCIR Report 239-7:1990, Propagation statistics required for broadcasting services using the frequency range 30 to 1 000 MHz [12] GB 4343.1, Electromagnetic compatibility - Requirements for household appliances electric tools and similar apparatus - Part 1: Emission (CISPR 14-1, IDT) www.chinesestandard.net Page 61 of 62