Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Similar documents
Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

The Fault Level Reduction in Distribution System Using an Active Type SFCL

REDUCING THE FAULT CURRENT AND OVERVOLTAGE IN A DISTRIBUTION SYSTEM WITH DISTRIBUTION GENERATION UNITS WITH SFCL

Superconducting Fault Current Limiter for Energy Storage Protection in a Micro Grid

Design and Simulation of superconducting fault current limiter

Performance of Superconducting Fault Current Limiter and Fault Current Limiter in Power System

INCREASING THE POWER SYSTEM SWITCH GEAR CAPACITY BY USING SUPERCONDUCTING FAULT CURRENT LIMITER

ANALYSIS OF OPTIMAL LOCATION OF SUPERCONDUCTING FAULT CURRENT LIMITER FOR THE SMART GRID

ISSN Vol.07,Issue.08, July-2015, Pages:

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD

FAULT CURRENT LIMITER IN SINGLE PHASE AND THREE PHASE LINES FOR COMPENSATING VOLTAGE SAG

PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS

A Novel High Step up And High efficiency DC-DC converter for Grid Connected or Standalone PV applications

SIMULATION OF MULTI CONVERTER BASED UNIFIED POWER-QUALITY (MC-UPQC) CONDITIONING SYSTEM ON VOLTAGE STABILITY OF RADIAL DISTRIBUTION SYSTEMS

Analysis of Superconducting Fault Current Limiter in DC System with Renewable Energy Sources

Electromagnetic transient analysis of saturated iron-core superconducting fault current limiter and DVR

The Impact of Superconducting Fault Current Limiter Locations on Voltage Sag in Power Distribution System

ISLANDING DETECTION USING DEMODULATION BASED FFT

International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN

SERIES ACTIVE power filters have proved to be an interesting

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

Multilevel inverter with cuk converter for grid connected solar PV system

Superconducting Fault Current Limiter For Energy Storage Protection Under Grounded Faults In A Micro Grid

Current limiting characteristic of saturated iron core SFCLs

Power Transmission of AC-DC Supply in a Single Composite Conductor

GRID CONNECTED HYBRID SYSTEM WITH SEPIC CONVERTER AND INVERTER FOR POWER QUALITY COMPENSATION

ISSN Vol.07,Issue.06, July-2015, Pages:

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

A Dual Half-bridge Resonant DC-DC Converter for Bi-directional Power Conversion

SUPERCONDUCTING MAGNETIC ENERGY

Thyristor Based Fault Current Limiter to Control Magnitudes of Fault Currents

EMERGING distributed generation technologies make it

FULL-BRIDGE THREE-PORT CONVERTERS WITH WIDE INPUT VOLTAGE RANGE FOR RENEWABLE POWER SYSTEMS

TRANSIENT AND DESIGN OPERATION ASSESSMENT OF RFCL IN BULK POWER SYSTEMS

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

FUZZY CONTROL OF SHOOT THROUGH TIME OF SINGLE STAGE BOOST INVERTER WITH COUPLED INDUCTOR FED BY A FUEL CELL

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

MMC based D-STATCOM for Different Loading Conditions

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

ANALYSIS OF ACTIVE POWER FILTER FOR HARMONIC VOLTAGE RESONANCE SUPPRESSION IN DISTRIBUTION SYSTEM

Cascaded Two Level Electrical Converter-Based Multilevel STATCOM for High Power Utilization

Fault Current Limiter Selection Considerations for Utility Engineers

Downloaded from

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

LOAD BALANCING IN PRIMARY DISTRIBUTION FEEDERS BY COMBINATION OF RENEWABLE ENERGY SOURCE AND VOLTAGE SOURCE INVERTER

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

ACTIVE POWER ELECTRONIC TRANSFORMER A STANDARD BUILDING BLOCK FOR SMART GRID

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Simulation of HTS saturable core-type FCLs for MV distribution systems

Multilevel Inverter Based Statcom For Power System Load Balancing System

Islanding Detection Method Based On Impedance Measurement

Power System Transient Stability Enhancement by Coordinated Control of SMES, SFCL & UPFC

Proposed structure of fault current limiter with power quality improvement

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Matlab Simulation of a High Step-Up DC-DC Converter for a Micro grid Application

Design and Implementation of Closed Loop LCL-T Resonant DC-to- DC Converter Using Low Cost Embedded Controller

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

Kalman Filter Based Unified Power Quality Conditioner for Output Regulation

Compensation for Voltage and Current in Multifeeder System Using MC-UPQC

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

STUDY OF CIRCULATING CURRENT PHENOMENA IN MULTIPLE PARALLEL INVERTERS OPERATING IN MICROGRID

,, N.Loganayaki 3. Index Terms: PV multilevel inverter, grid connected inverter, coupled Inductors, self-excited Induction Generator.

Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

DC-DC CONVERTER WITH VOLTAGE MULTIPLIER CIRCUIT FOR PHOTOVOLTAIC APPLICATION

Power Quality Analysis in Power System with Non Linear Load

A Fuel Cell Fed Single Stage Boost Inverter with Unique Impedance Network

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

THE increasing tension on the global energy supply has resulted

RECENTLY, the harmonics current in a power grid can

LeMeniz Infotech. 36, 100 Feet Road, Natesan Nagar, Near Indira Gandhi Statue, Pondicherry Call: , ,

A NOVEL High Step-Up Converter with a Voltage Multiplier Module for a Photo Voltaic System

Mitigation of Fault Current using Parallel- Resonance Type FCL

Accurate Current Measurement Transducer for Relaying Purpose

ISSN Vol.07,Issue.11, August-2015, Pages:

TYPICALLY, a two-stage microinverter includes (a) the

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Sliding Mode MPPT Based Control For a Solar Photovoltaic system

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

A Pv Fed Buck Boost Converter Combining Ky And Buck Converter With Feedback

Phase Shift Modulation of a Single Dc Source Cascaded H-Bridge Multilevel Inverter for Capacitor Voltage Regulation with Equal Power Distribution

Quasi Z-Source DC-DC Converter With Switched Capacitor

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Voltage Support and Reactive Power Control in Micro-grid using DG

Power Quality Improvement by DVR

Smart Time-Division-Multiplexing Control Strategy for Voltage Multiplier Rectifier

Transcription:

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute of Technology & sciences, A.P., India, ranadheer_p@pace.ac.in Mobile no: 9440868865 Abstract The Active Superconducting Current Controller (ASCC) is a new type of Fault Current Limiters which can limit the fault current in different modes and also has the particular abilities of compensating active and reactive power for AC main circuit in the normal state. The use of the ASCC disturbs the operation of Over Current Relays (OCR) used in the distribution system. In consideration that applying superconducting fault current limiter (SFCL) may be a feasible solution, in this paper, the effects of a voltage compensation type active SFCL on them are studied through theoretical derivation and simulation. The active SFCL is composed of an air-core superconducting transformer and a PWM converter. The magnetic field in the air-core can be controlled by adjusting the converters output current, and then the active SFCLs equivalent impedance can be regulated for current limitation and possible overvoltage suppression. Due to the difficulty in power network reinforcement and the interconnection of more distributed generations, fault current level has become a serious problem in transmission and distribution system operations [10]. The utilization of fault current limiters (FCLs) in power system provides an effective way to suppress fault currents and result in considerable saving in the investment of high capacity circuit breakers. In this work a resistive superconducting fault current limiter designed. Index Terms Distributed generation (DG), distribution system, overvoltage, short-circuit current, voltage compensation type active superconducting fault current limiter (SFCL) 1. INTRODUCTION In recent years, with the great development of interconnected power grid, the power network structure becomes increasingly complicated, and the system short circuit capacity and short circuit current have reached a new level which could exceed the allowable currents of the circuit breakers. The increase of the fault current has imposed a severe burden on the related machinery in the grid, and the stability of the power system is also damaged. The fault current limiters (FCL) are regarded as the suitable solution to solve excessive fault current problems. [1] Active superconducting fault current limiter (ASFCL) voltage compensation type is a novel topology of FCL. This type SFCL not only preserves the merits of bridge type SFCL such as the automatic switch to the current limiting mode and without the quench of the superconductor, but also has the particular abilities of controlling the steady fault current and compensating active and reactive power for AC main circuit in the normal state. Fig. 1 shows the circuit structure of the three phase active SFCL, which is consisting of three air-core superconducting transformers and a three-phase voltage source converter. As a result, faults in power networks incur large short-circuit currents flowing in the network and in some cases may exceed the ratings of existing circuit breakers (CB) and damage system equipment The problems of inadequate CB short-circuit ratings have become more serious than before since in many locations, the highest rating of the CB available in the market has been used. To deal with the problem, fault current limiters (FCLs) are often used in the situations where insufficient fault current interrupting capability exists [1]. Less expensive solutions such as current limiting reactors may have unwanted side effects, Such as increasing system losses, voltage regulation problems or possibly could compromise system stability. Smart grid is a modern electricity system. It uses sensors, monitoring, communications, automation and computers to improve the edibility, security, reliability, efficiency, and safety of the electricity system. Renewable energy technologies such as photovoltaic, solar thermal electricity, and wind turbine power are environmentally beneficial sources of electric power generation [3]. The integration of renewable energy sources into electric power distribution systems can provide additional economic benefits because of a reduction in the losses associated with transmission and distribution lines. In this work a SFCL model is designed. SFCL is an innovative fault current limiter. It works on the principle of Superconducting Property. It is inactive e under normal condition. It is in active under fault condition; it inserts some resistance into the line to limit the fault current. It suppresses the fault current within first half cycle only. It operates better than Circuit breakers, Relays, because the Circuit breakers take minimum 2-3 cycles before they getting activated. The effect of SFCL on micro grid fault current observed. The optimal place to SFCL is determined [10]. 828 www.ijergs.org

We have proposed voltage compensation type active SFCL in previous work [7], and analyzed the active SFCL s control strategy and its influence on relay protection [8, 9]. In addition, an 800 V/30 a laboratory prototype was made, and its working performances were confirmed well [10]. In this paper, taking the active SFCL as an evaluation object, its effects on the fault current and overvoltage in a distribution network with multiple DG units are studied. 2. THEORETICAL ANALYSIS 2.1. Structure and Principle of the Active SFCL As shown in Fig. 1(a), it denotes the circuit structure of the single-phase voltage compensation type active SFCL, which is composed of an air-core superconducting transformer and a voltage-type PWM converter.ls1, Ls2 are the self-inductance of two superconducting windings, and Ms is the mutual inductance.z1is the circuit impedance andz2is the load impedance. Ld and Cd are used for filtering high order harmonics caused by the converter. Since the voltage-type converter s capability of controlling power exchange is implemented by regulating the voltage of AC side, the converter can be thought as a controlled voltage source Up. By neglecting the losses of the transformer, the active SFCL s equivalent circuit is shown in Fig. 1(b). Fig. 1. Single-phase voltage compensation type active SFCL. (a) Circuit structure and (b) equivalent circuit. In normal (no fault) state, the injected current (I2) in the secondary winding of the transformer will be controlled to keep a certain value, where the magnetic field in the air-core can be compensated to zero, so the active SFCL will have no influence on the main circuit. When the fault is detected, the injected current will be timely adjusted in amplitude or phase angle, so as to control the superconducting transformer s primary voltage which is in series with the main circuit, and further the fault current can be suppressed to some extent. Below, the suggested SFCL s specific regulating mode is explained. In normal state, the two equations can be achieved. Controlling I2 to make jωl s1 1 jωms 2=0 and the primary voltage U 1 will be regulated to zero. Thereby, the equivalent limiting impedance ZSFCL is zero (ZSFCL=U1/I1), and I2 can be set as 2 = 2 /(Z1+Z2)k, where k is the coupling coefficient and it can be shown as k=ms/.under fault condition (Z2is shorted), the main current will rise from I1to I1f, and the primary voltage will increase to U 1f. (1) (2) (3) 829 www.ijergs.org (4)

The current-limiting impedance ZSFCL can be controlled in: (5) Fig. 2. Application of the active SFCL in a distribution system with DG units. According to the difference in the regulating objectives of I2, there are three operation modes: 1) MakingI2 remain the original state, and the limiting impedancezsfcl 1=Z2 (jωls1)/(z1+z2+jωls1). 2) ControllingI2to zero, andzsfcl 2=jωLs1. 3) Regulating the phase angle of I2 to make the angle difference between Us and jωms I2 be 180.Bysetting jωms I2= c Us, and ZSFCL 3=cZ1/(1 c)+jωls1/(1 c). The air-core superconducting transformer has many merits, such as absence of iron losses and magnetic saturation, and it has more possibility of reduction in size, weight and harmonic than the conventional iron-core superconducting transformer [9], [8]. Compared to the iron-core, the air-core can be more suitable for functioning as a shunt reactor because of the large magnetizing current [5], and it can also be applied in an inductive pulsed power supply to decrease energy loss for larger pulsed current and higher energy transfer efficiency [6], [7]. There is no existence of transformer saturation in the air-core, and using it can ensure the linearity of ZSFCL well. 2.2. Applying the SFCL into a Distribution Network with DG As shown in Fig. 2, it indicates the application of the active SFCL in a distribution network with multiple DG units, and the buses B-E are the DG units probable installation locations. When a single-phase grounded fault occurs in the feeder line 1 (phase A, k1 point), the SFCL s mode 1 can be automatically triggered, and the fault current s rising rate can be timely controlled. Along with the mode switching, its amplitude can be limited further. In consideration of the SFCL s effects on the induced overvoltage, the qualitative analysis is presented. In order to calculate the over voltages induced in the other two phases (phase B and phase C), the symmetrical component method and complex sequence networks can be used, and the coefficient of grounding G under this condition can be expressed as G= 1.5m/(2 +m)±j 3/2, where m=x0/x1, and X0 is the distribution network s zero-sequencereactance,x1is the positive-sequence reactance [6]. Further, the amplitudes of the B-phase and C-phase over voltages can be described as: Where UAN is the phase-to-ground voltage s root mean square (RMS) under normal condition. 3. SUPERCONDUCTING FAULT CURRENT LIMITER Superconducting Fault Current Limiter (SFCL) is innovative electric equipment which has the capability to reduce the fault current level within the first cycle of fault current [1]. The first-cycle suppression of fault current by a SFCL results in an increased transient stability of the power system carrying higher power with greater stability. The concept of using the superconductors to carry electric power and to limit peak currents has been around since the discovery of superconductors and the realization that they possess highly non-linear properties. More specifically, the current limiting behavior depends on their nonlinear response to temperature, current and magnetic field variations. Increasing any of these three parameters can cause a transition between the superconducting and the normal conducting regime. The current increase can cause a section of superconductor to become so resistive that the heat generated cannot be removed locally. This excess heat is transferred along the conductor, causing the temperature of adjacent sections to increase. The combined current and temperature can cause these regions to become normal and also generate heat. The term quench is commonly used to describe the propagation of the normal zone through a superconductor. Once initiated, the quench process is often rapid and (6) 830 www.ijergs.org

uncontrolled. Though once initiated the quench process is uncontrolled, the extent of the normal region and the temperature rise in the materials can be predicted. 4. MATLAB/SIMULINK RESULTS For purpose of quantitatively evaluating the current-limiting and overvoltage-suppressing characteristics of the active SFCL, the distribution system with DG units and the SFCL for the other DG, it can be installed in an arbitrary position among the Buses C E (named as DG2). To reduce the converter s design capacity, making the SFCL switch to the mode 2 after the fault is detected, and the detection method is based on measuring the main current s different components by Fast Fourier Transform (FFT) and harmonic analysis. Case: 1 Without SFCL and with the active SFCL Fig. 3. Matlab/Simulink model of three pahse the short-circuit occurs a k3 point. Without SFCL and with the active SFCL Figure3 Shows Matlab/Simulink Model of Three Pahse the Short-Circuit Occurs A K3 Point. Without SFCL and With the Active SFCL 831 www.ijergs.org

Fig. 4. Voltage waveforms when the three-phase short-circuit occurs a k3 point. Without SFCL and with the active SFCL Figure4 shows the Voltage waveforms when the three-phase short-circuit occurs a k3 point. Without SFCL and with the active SFCL Fig. 5. Line current waveforms when the three-phase short-circuit occurs a k3 point. Figure5 shows the Line current waveforms when the three-phase short-circuit occurs a k3 point Case: 2 Without SFCL and with the active SFCL with pv 832 www.ijergs.org

Fig. 6. Matlab/Simulink model of three pahse the short-circuit occurs a k3 point. Without SFCL and with the active SFCL with PV. Figure6 Shows Matlab/Simulink Model of Three Pahse the Short-Circuit Occurs A K3 Point. Without SFCL and With the Active SFCL with PV Fig. 7. Voltage waveforms when the three-phase short-circuit occurs a k3 point. Without SFCL and with the active SFCL with PV. Figure7 shows the Voltage waveforms when the three-phase short-circuit occurs a k3 point. Without SFCL and with the active SFCL with PV. 833 www.ijergs.org

Fig. 8. Photovoltaic voltage Figure8 shows Without SFCL and with the active SFCL with photovoltaic voltage. Fig. 9. Line current waveforms when the three-phase short-circuit occurs a k3 point with PV Figure9 shows the Line current waveforms when the three-phase short-circuit occurs a k3 point with PV 5. CONCLUSION In this paper, the application of the active SFCL into in a power distribution network with DG units is investigated. For the power frequency overvoltage caused by a single-phase grounded fault, the active SFCL can help to reduce the overvoltage s amplitude and 834 www.ijergs.org

avoid damaging the relevant distribution equipment. The active SFCL can as well suppress the short-circuit current induced by a three-phase grounded fault effectively, and the power system s safety and reliability can be improved. The study of a coordinated control method for the renewable energy sources and the SFCL becomes very meaningful, and it will be performed in future. REFERENCES: [1] S. Conti, Analysis of distribution network protection issues in presence of dispersed generation, Elect. Power Syst. Res., vol. 79, no. 1, pp. 49 56, Jan. 2009. [2] A. S. Emhemed, R. M. Tumilty, N. K. Singh, G. M. Burt, and J. R. McDonald, Analysis of transient stability enhancement of LV connected induction micro generators by using resistive-type fault current limiters, IEEE Trans. Power Syst., vol. 25, no. 2, pp. 885 893, May 2010. [3] S.-Y. Kim and J.-O. Kim, Reliability evaluation of distribution network with DG considering the reliability of protective devices affected by SFCL, IEEE Trans. Appl. Supercond., vol. 21, no. 5, pp. 3561 3569, Oct. 2011. [4] S. A. A. Shahriari, A. Yazdian, and M. R. Haghifam, Fault current limiter allocation and sizing in distribution system in presence of distributed generation, in Proc. IEEE Power Energy Soc. Gen. Meet., Calgary, AB, Canada, Jul. 2009, pp. 1 6. [5] S. Hemmati and J. Sadeh, Applying superconductive fault current limiter to minimize the impacts of distributed generation on the distribution protection systems, in Proc. Int. Conf. Environ. Electr. Eng., Venice, Italy, May 2012, pp. 808 813. [6] S.-H. Lim, J.-S. Kim, M.-H. Kim and J.-C. Kim, Improvement of protection coordination of protective devices through application of a SFCL in a power distribution system with a dispersed generation, IEEE Trans. Appl. Supercond., vol. 22, no. 3, p. 5601004, Jun. 2012. [7] L. Chen, Y. Tang, J. Shi, and Z. Sun, Simulations and experimental analyses of the active superconducting fault current limiter, Phys. C, vol. 459, no. 1/2, pp. 27 32, Aug. 2007. [8] L. Chen, Y. Tang, J. Shi, Z. Li, L. Ren, and S. Cheng, Control strategy for three-phase four-wire PWM converter of integrated voltage compensation type active SFCL, Phys. C, vol. 470, no. 3, pp. 231 235, Feb. 2010. [9] L. Chen, Y. J. Tang, J. Shi, L. Ren, M. Song, S. J. Cheng, Y. Hu, and X. S. Chen, Effects of a voltage compensation type active superconducting fault current limiter on distance relay protection, Phys. C, vol. 470, no. 20, pp. 1662 1665, Nov. 2010. [10] J. Wang, L. Zhou, J. Shi, and Y. Tang, Experimental investigation of an active superconducting current controller, IEEE Trans. Appl. Supercond., vol. 21, no. 3, pp. 1258 1262, Jun. 2011 835 www.ijergs.org