HTS PARTIAL CORE TRANSFORMER- FAULT CURRENT LIMITER

Similar documents
A Glance into the Future of Transformers and Beyond

PARTIAL CORE TRANSFORMERS FOR HV TESTING AND POWER SUPPLIES

Superconducting Transformer Design and Construction

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

Walchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer

4. Superconducting sector magnets for the SRC 4.1 Introduction

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS

Design considerations in MgB2-based superconducting coils for use in saturated-core fault current limiters

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Electrical Design Process

SPECIFICATIONS FOR A 4.7 TESLA/310MM BORE ACTIVELY SHIELDED MAGNET SYSTEM

INNOVATIVE PERSPECTIVES FOR ELECTRICITY TRANSPORT

2.3 PF System. WU Weiyue PF5 PF PF1

Liquid-Filled Transformers

NUMERICAL MODEL OF THE 10 KVA TRANSFORMER WITH COPPER WINDINGS

TECHNICAL SPECIFICATIONS. FOR AN MRBR 7.0 TESLA / 160mm ACTIVELY SHIELDED ROOM TEMPERATURE BORE MAGNET SYSTEM

COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ACADEMIC YEAR / EVEN SEMESTER QUESTION BANK

Development and performance analysis of a saturated core high temperature superconducting fault current limiter

The Results of the KSTAR Superconducting Coil Test

Comparison of Leakage Impedances of Two Single-phase Transformers

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Basic Principles and Operation of Transformer

HOW TO SAFE GUARD THE TRANSFORMER..???

Recent Development of SFCL in the USA

High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems

SPECIFICATIONS FOR AN MRBR 7.0 TESLA / 210MM ACTIVELY SHIELDED MAGNET SYSTEM

Power Transformers Basics

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

SPECIFICATION FOR A 7.0 TESLA/400MM ROOM TEMPERATURE BORE MAGNET SYSTEM

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

(2) New Standard IEEE P (3) Core : (4) Windings :

Outcomes from this session

Title ZnO device and resistor in parallel IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2006), 16(2): 65.

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

Resistive and Inductive Fault Current Limiters: Kinetics of Quenching and Recovery

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Final Publishable Summary

Frequency Tuning and RF Systems for the ATLAS Energy Upgrade. Gary P. Zinkann

PRELIMINARY SPECIFICATIONS MRBR 7.0 TESLA / 210MM ACTIVELY SHIELDED CRYO-COOLED MAGNET SYSTEM

GOVERNMENT COLLEGE OF ENGINEERING, BARGUR

EQUIVALENT CIRCUIT OF A SINGLE-PHASE TRANSFORMER

The design of Ruthroff broadband voltage transformers M. Ehrenfried G8JNJ

Lecture 16 Transformer Design

Part 10: Transducers

Introduction. Inductors in AC Circuits.

AC Excitation. AC Excitation 1. Introduction

Power Transformers. Energy Systems Research Laboratory, FIU

CHAPTER 6 FABRICATION OF PROTOTYPE: PERFORMANCE RESULTS AND DISCUSSIONS

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

Generation of Sub-nanosecond Pulses

Back to the Basics Current Transformer (CT) Testing

Study of Design of Superconducting Magnetic Energy Storage Coil for Power System Applications

Engineering Science OUTCOME 4 - TUTORIAL 3 CONTENTS. 1. Transformers

Transformers. gpmacademics.weebly.com

Laminate Transformer Testing

FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

RF power tests of LEP2 main couplers on a single cell superconducting cavity

Transformers. Department of Physics & Astronomy Texas Christian University, Fort Worth, TX. April 23, 2013

Line Frequency Transformer

An improved design of an inductive fault current limiter based on a superconducting cylinder

Physical Design of Superconducting Magnet for ADS Injection I

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Tech Byte 16: The Truths About Transformers Part 2

Transformer Factory Testing

Use of inductive heating for superconducting magnet protection*

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

Superconducting Fault Current Limiter Modules for Power Transmission / Distribution

Unit WorkBook 1 Level 4 ENG U31: Electrical Systems and Fault Finding 2018 UniCourse Ltd. All Rights Reserved. Sample

Single-Phase Transformation Review

Testing of the Toroidal Field Model Coil (TFMC)

Transformer Waveforms

Chapter 3. Experimental set up. 3.1 General

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Chapter 2-1 Transformers

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Induction heating of internal

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

TRANSFORMERS INTRODUCTION

Packaging of Cryogenic Components

Electrical Theory 2 Lessons for Fall Semester:

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Design of Integrated LC Filter Using Multilayer Flexible Ferrite Sheets S. Coulibaly 1, G. Loum 1, K.A. Diby 2

Sub-cooled SFCL Device and Modules for Power Transmission / Distribution

Electromagnetic Force Modification in Fault Current Limiters under Short-Circuit Condition Using Distributed Winding Configuration

7. INSPECTION AND TEST PROCEDURES

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

Unit FE-5 Foundation Electricity: Electrical Machines

Practical Tricks with Transformers. Larry Weinstein K0NA

Department of Electrical and Computer Engineering Lab 6: Transformers

DESIGN AND CONSTRUCTION OF 1500VA VARIABLE OUTPUT STEP DOWN TRANSFORMER

Design Comparison for Rectangular and Round Winding Distribution Transformer (1000kVA)

Target Temperature Effect on Eddy-Current Displacement Sensing

Hands-On Transformer Testing and Maintenance

UNIVERSITY OF BRITISH COLUMBIA

Units. In the following formulae all lengths are expressed in centimeters. The inductance calculated will be in micro-henries = 10-6 henry.

Transcription:

EEA CONFERENCE & EXHIBITION 2013, 19-21 JUNE, AUCKLAND HTS PARTIAL CORE TRANSFORMER- FAULT CURRENT LIMITER JIT KUMAR SHAM*, UNIVERSITY OF CANTERBURY, CHRISTCHURCH, NEW ZEALAND PROF. PAT BODGER, UNIVERSITY OF CANTERBURY, CHRISTCHURCH, NEW ZEALAND PRESENTER*

1. Introduction In 1908, a Dutch physicist Kamerlingh Onnes, was the first person to liquefy helium at 4.2 K. Subsequently in 1911, he was able to discover that mercury, when cooled by liquid helium, has no electrical resistance. He named this phenomenon Superconductivity. Although superconductors were discovered in 1911, high temperature superconductors (HTS) were only discovered in 1987. This enabled material to become superconducting at liquid nitrogen temperature[1]. As a result, the operating cost of using superconductors came down. This opened the way to use superconductors in power system applications[2]. The basic premise behind using superconductors is that they tend to quench once the magnetic field density, temperature and conductor current are breached beyond their combined critical limit. Once this limit is breached, they tend to change from a superconducting state to a resistive state. It is this behaviour of superconductors that has carved the path towards using superconductors as fault current limiters. This paper presents a HTS partial core transformer-fault current limiter that was designed and built at the University of Canterbury. The transformer was tested under no load, short circuit and full load conditions, followed by a test with a short circuit fault to determine its capability as a fault current limiter. 2. Device description and design method The device has a structure which is both a partial core transformer and a fault current limiter. A partial core transformer is a transformer with its yokes and limbs removed [3]. This makes the transformer light weight, and construction and transportation is much easier. The tradeoff of this design is that it increases the magnetizing current of the transformer due to the higher reluctance of the magnetic circuit. The higher magnetizing current results in higher copper losses and therefore a larger cross-sectional area is required for the windings. Hence, a conductor which has very low losses and a small cross-sectional area is required. This brings the HTS into the picture which has all the above required characteristics. In addition, HTS has the advantage of quenching which makes it useful for current limiting. The reverse design method is used to design this device [3]. The method takes into account the physical characteristics such as material resistivities, permeabilites and the dimensions of the windings and the core as the specifications. By altering these specifications, the performance of the device is optimized and a suitable design is obtained. An Excel program has been developed for simulation purposes and this serves as a gauge to test the proposed design before actually fabricating it. The key parameters considered while designing the transformer are listed in Table 1. Modifications are made to allow for the new combined device of a transformer-fault current limiter. A Steinmetz model, shown in Fig. 1, is used to depict the equivalent circuit parameters of the combined device [3].

Fig 1. Steinmetz model of a transformer-fault current limiter In the above circuit diagram the inside winding resistance and reactance are R 1 and X 1 respectively, while the outside winding resistance and reactance, referred to the inside winding, are R 2 and X 2 respectively. R h, R ec and X m represent the core hysteresis losses, eddy current losses and magnetising current respectively. 2.1 Core The core was constructed from high permeability, grain oriented silicon steel. It was designed as a circular core with stacked laminations arranged in parallel. The dimensions of the core are listed in Table 1. Parameter Dimension Core length 384mm Diameter of core 80mm Stacking factor 0.86 Lamination thickness 0.23mm Operating temperature -50 0 C Former thickness 19.5 mm Material density 7700kg/m 3 2.2 Windings Table 1. Design data of the partial core The HTS windings were wound on a former made of G10 composite, as shown in Figure 2. The composite was fabricated by an outside vendor. The emphasis on choosing G10 composite was its ability to withstand liquid nitrogen and an operating temperature of 77K. In order to prevent inter-turn short circuits, the HTS windings are insulated with Nomex tape. Spacers were used between each layer to accommodate cooling of the windings. This allowed liquid nitrogen to freely flow between the windings on each layer. Figure 3 shows the top view of the windings in AutoCAD. In this figure, the white spacers are shown to wrap around the former. This allows for the 2mm spacing in between each winding. The primary/inside winding consisted of 6 layers while the secondary/outside winding consisted of 6.5 layers. The specifications for the windings are given in Table 2. This model design was achieved using the reverse design method over several iterations. Appropriate efficiency, regulation and the fault current level were taken into account while performing these iterations. The 6.5 layers in the secondary were wound in a circular pattern with the last half layer wound on the centre. This ensured symmetrical flux distribution along the device. Figure 4 displays the fabricated device with the windings wound on the former.

Parameter Inside Winding Outside Winding Winding height 384mm 384mm Number of layers 6 6.5 Turns per layer 73 73 Conductor length 189m 267m Wire width 4.1mm 4.1mm Wire thickness 0.3mm 0.3mm Wire insulation thickness 5.5mm 5.5mm Insulation layer space 2 mm 2 mm Operating temperature 77K 77K Table 2. Winding data of the transformer-fault current limiter Fig 2. Axial representation of the partial core transformer- FCL Fig 3. AutoCAD representation of the windings from Top view Bodger 24/4/13 10:44 AM Comment [1]: Put the photos as Figure 4 and say what they are. Refer to them from the text.

Fig 4. HTS windings wound around the former with spacers in between 2.3 Cryogenic equipment for cooling To maintain the transformer under cryogenic conditions, a vacuum Dewar, shown in Fig. 5 was filled with liquid nitrogen (LN2). The vacuum Dewar consists of an inner vessel for storing the LN2 and an outer vessel exposed to room temperature with a vacuum between them. The vacuum is present to limit convection losses to the LN2 from the outside. To limit radiation losses, several layers of aluminized non-stretch polyester were wrapped around the inner vessel. Care was taken not to create shorted turns by insulating the aluminized nonstretch polyester with vacuum rated tissue paper. The bottom of the inner vessel was dome shaped so that the joint between the dome and the tube of the inner vessel, when exposed to LN2, expanded and contracted evenly. A pressure relief port is present on the outside of the Dewar in case a failure of the inner vessel results in nitrogen gas venting into the vacuum chamber. The core vessel is similar to the vacuum Dewar in that a vacuum is formed between the core and the LN2. A similar arrangement of aluminized polyester and tissue was used in the core vessel. The HTS winding former is fitted over the core vessel and held in place with a clamping ring. A float is attached to the core vessel to indicate the minimum and maximum LN2 levels. A filling tube for the LN2 is also fitted to the outside of the core vessel. A pressure relief port is present on the top of the core vessel in case a failure vents nitrogen gas into the vacuum chamber. Fig 5. Cryogenic equipment for HTS transformer- fault current limiter

3. Testing Electrical tests were performed on the combined unit of the transformer-fault current limiter to determine its operational characteristics. The HTS transformer-fault current limiter was operated under no-load, short circuit, full load and fault conditions, and then subjected to an endurance run. 3.1 Experimental Setup 3.1.1 Preview of the lab The tests are performed in the High Voltage Lab of the University of Canterbury. The facility is equipped with a single phase power supply that can deliver 600A at 400V. Its large size helps to accommodate the test equipment and the device with adequate spacing between them. 3.1.2 Test Gear The test gear used in this experimental setup consisted of two calibrated Fluke 41B meters for measuring voltage, current and power of the primary and secondary windings. The meters were connected to a computer through an IEEE-488 interface which ran a Matlab program to collect the data recorded from the tests. For measuring the resistance of the windings under dc conditions, a MPK254 digital micro-ohmmeter was used. The insulation tests were performed with a Megger meter with model specs S1-5005. For energising the transformer-fault current limiter, two transformer variacs were used. They were connected in series. The first variac was the laboratory s 600 A supply, while the second variac was the 70 A supply. The 70 A variac is portable and allows for adjusting the voltage in steps while recording and monitoring the measurements. The experimental setup is shown in Fig.6 Fig 6. Experimental setup of the HTS transformer-fault current limiter 3.2 Open circuit test With an open circuit or no load test, very little current is required to energise the core. Since the secondary is open circuited, all the current flows through the primary winding and the losses are attributed as the core losses. The open circuit test also determines the voltage ratio of the primary and the secondary windings.

To perform the test, the voltage in the second variac is increased in small increments to the rated voltage and the measurements are recorded. The measured results are given in Table 3. They are compared to the calculated results determined from the design program. There is generally good agreement between the measured and calculated results. Parameter Measured Calculated Inside winding voltage (V) 230.6 230 Outside winding voltage (V) 235 237 Voltage ratio 1.02 1.03 Excitation current (A) 13.6 15.4 Excitation current s phase -87-86 Volt-amperes (kva) 3.14 3.54 Real power (W) 167 165 Power factor 0.05 0.05 Table 3: Open circuit test results 3.3 Short circuit test In a short circuit test, the secondary is shorted. The test determines the series impedance and full load losses in the combined unit. All the losses are related to the windings. The results from the short circuit test are given in Table 4. Again there is good agreement between the measured and calculated results. Parameter Measured Calculated Inside winding voltage (V) 42.1 42.3 Inside winging current (A) 30.1 31.3 Outside winding current (A) 26 28 Volt-amperes (kva) 12.6 13.0 Real Power (W) 47 50 Power factor 0.03 0.04 Inside winding current s phase in deg -88-87 Table 4: Short circuit test results 3.4 Load test The load test on the HTS transformer-fault current limiter determines the performance of the device while delivering power. The device was connected to a resistive load bank as illustrated in Fig 7. The supply voltage was varied on the primary side till it reached the rated voltage and the load resistance varied till it reached the rated value. The results from this test are given in Table 5. Again there is good correlation between the measured and calculated values.

Fig 7. Load bank to perform the load test Parameter Measured Calculated Inside winding voltage (V) 230 230 Inside winding current (A) 33 31.3 Outside winding voltage (V) 234.5 234.5 Outside winding current (A) 30.7 24.2 Outside winding current s phase (deg) -34-32 Volt-amperes (VA) 7.2 7.2 Real power (kw) 6.8 5.7 Power factor 0.84 0.80 Efficiency (%) 99.97 99.96 Voltage Regulation (%) 5.7 5.8 3.5 Fault current test Table 5: Load test results The transformer and fault current limiter was tested under a fault condition. The test was performed by shorting the secondary windings with a manual switch while the primary winding was energised with the rated voltage and the rated load was connected to the secondary side of the transformer. Fig 8 depicts the arrangement of the rated load and the manual switch used in this test to short the secondary windings. The voltage and current for the primary and secondary windings were monitored using an oscilloscope. The images obtained are shown in Fig 9. In the channel traces, the green waveform indicates the primary current while the yellow waveform indicates the secondary current. Each square block in the oscilloscope chart has amplitude of 100A for the current. The measured fault current after quenching was 200A as compared to the calculated prospective current of 173A determined using the reverse design model. The circuit being inductive means that the voltage leads the current as show in the second image of Fig 9.

Fig 8. Fault current test Fig 9. Oscilloscope images of the primary voltage, (V) and current, (A) during a fault condition. Under normal conditions, the HTS acts as a conductor with almost zero resistance, however, once the critical current, I c of the HTS material (BSCCO) has been breached, it quenches and turns resistive. The fault limiting capabilities of the HTS material was modelled by taking into account the resistive properties of silver. 4. Conclusion This paper begins with a brief about superconductors and how they were applied in power system applications. It highlights the advantages of a partial core design as a transformer and its application in the combined device of transformer-fault current limiter. The fabricated design is then displayed followed by the results of tests done to investigate its feasibility as a current limiter. The measured values from the test and the reverse design model are found to have close correlation which confirms that the model can be used to design current limiters and transformers. 5. References 1. At the Frontiers of Science: Superconductivity and its Power Applications. NREL, July 1998.

2. Keisuke Fushiki, Tanzo Nitta, Jumpei Baba et al., Design and Basic Test of SFCL of Transformer Type by Use of Ag Sheathed BSCCO wire, Applied Superconductivity, vol17, no2, June 2007. 3. Liew, M.C. and Bodger, P.S., "Applying a reverse design modelling technique to partial core transformers", AUPEC2001, Perth, Australia, 23-26 September, 2001, paper 020, pp. 310-315.