www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Similar documents
www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

PD300. Transformer, generator and motor protection Data sheet

g GE POWER MANAGEMENT

EASUN REYROLLE LIMITED

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Unit Protection Differential Relays

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Stabilized Differential Relay SPAD 346. Product Guide

Detecting and Managing Geomagnetically Induced Currents With Relays

Transformer Protection

Differential Protection with REF 542plus Feeder Terminal

Transformer protection IED RET 670

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Bus Protection Fundamentals

Transformer Protection Principles

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Power System Protection Manual

Transformer Fault Categories

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay

Protective Relays Digitrip 3000

Catastrophic Relay Misoperations and Successful Relay Operation

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection M 3420

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

SPAD 346 C Stabilized differential relay

Transformer Protection

POWER SYSTEM II LAB MANUAL

These drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations and retrofit

Multimeter 500CVD21 RTU500 series

BUS2000 Busbar Differential Protection System

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

Verifying Transformer Differential Compensation Settings

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

Centralized busbar differential and breaker failure protection function

Earth Fault Relay EFSPL-1A/5A

Transformer differential protection

Improving Transformer Protection

XD1-T - Transformer differential protection relay

System Protection and Control Subcommittee

Power systems Protection course

UV3 _ Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High)

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

COPYRIGHTED MATERIAL. Index

Pinhook 500kV Transformer Neutral CT Saturation

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

Relaying 101. by: Tom Ernst GE Grid Solutions

3 Pole high impedance differential relay 7VH83

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Overcurrent Elements

PROTECTION of electricity distribution networks

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

function block description to the differential protection and restricted earth-fault protection functions for autotransformers

Generator Protection M 3425

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

7SG14 Duobias-M Transformer Protection

2015 Relay School Bus Protection Mike Kockott March, 2015

High speed bus transfer function block description Operation Manual

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

IRI1-ER - Stabilized Earth Fault Current Relay

INSTRUCTION MANUAL. AQ F3x0 Feeder protection IED

Integra 1560 and 1580 Digital Transducer Systems

MotStart Three-phase Start-Up Supervision for Motors

FMR. Ultra Line FEEDER MANAGER RELAY

DIGITAL EARTH FAULT RELAY

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

Instruction Book. M-3425A Generator Protection

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Introduction. Principle of differential relay operation

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

889 Advanced Generator Protection Technical Note

7PG2113/4/5/6 Solkor Feeder Protection Answers for energy

AQ P215 Power Monitoring IED

Instruction Book. M 3425A Generator Protection

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

Two variable ac current, variable phase-angle sources Variable dc voltage/current source and latch timer Variable harmonic current source

AQ F201 Overcurrent and Earthfault

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Inrush3 Three-Phase Transformer Inrush and Motor Start-Up Current Detector

Restricted earth-fault protection function block description

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

Performance Analysis of Traditional and Improved Transformer Differential Protective Relays

ASHIDA Numerical 3OC + 1EF Protection Relay

N. TEST TEST DESCRIPTION

Transcription:

Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions: High and low set differential elements for each phase with multi-slope bias characteristics. The MD3T is suitable for protecting any two winding transformer or a three winding transformer with unit-directional current flow. Low set differential element response time of less than cycles, high set response time under cycle. Programmable nd and 5th harmonic restraint elements which may be reduced automatically during transformer energization or at any time by an external trigger. Restricted ground fault element. Automatic CT ratio compensation for all transformer winding and CT connection configurations through programmable vector groups. 6 cycle oscillographic records of trip events. An oscillographic record may also be triggered externally. The MD3T also shares the following features common to all Edison relays: Simple five button man machine interface (MMI) allows access to all functions, settings, and stored data without the need for a computer. Bright electroluminescent display easily visible even in brightly lit environments. Draw-out design permits relay testing without disturbing connections to case. August 997 New Issue Printed in USA Modbus communication protocol and RS485 terminal on rear. Modular design allows the draw-out module to be fitted to a variety of space saving cabinet styles. Three programmable Form C (SPDT) output contacts and one Form A/B contact. Pick-up (start-time) elements. Programmable reset characteristics. Dedicated power supply/relay fail output contacts. Applications The MD3T is ideally suited for the protection of any two winding transformer against two or three phase internal faults, inter-turn faults, and ground faults in transformers with low-impedance or solidly grounded neutrals. Electrical Apparatus MD3T Transformer Differential Relay 50-30 Figure. Front View of the MD3T Transformer Differential Relay The MD3T may also be used to protect multi-winding transformers where one winding always acts as the source winding, and the CTs of the other load windings are connected in an appropriate manner to represent the sum of the load currents. For autotransformer-started motors, some differential protection schemes include the autotransformer in the zone of protection. In this case a rotating machine differential relay, such as the MD3G, is not suitable as the nd and 5th harmonic restraint functions common to transformer differential relays is required. For this application, the MD3T should be used.

MD3T Transformer Differential Relay Figure. Dual Slope Bias Characteristic of the MD3T Differential Relay Multi-slope Biased Differential Element Each phase is provided with its own differential element with a characteristic as shown in Figure. The relay internally calculates the RMS value of the differential current compensated for any CT ratio and phase angle mismatch. The minimum differential current required for operation is adjustable between 0. and 0.5 pu of the rated current. This setting is fixed up to 0.5 pu of the transformers rated current. Above 0.5 pu compensation of the set point is required for CT saturation, which may occur at higher current levels, and for voltage ratio fluctuations caused by on-load tap changers. From 0.5 to.5 pu of rated current, the slope of the differential element is adjustable between 0 and 50%. Between.5 pu and 8 pu of rated current, the bias slope is fixed at 00%. Is/In 8 Id/In 0 I R 0.5.5 3 3 Is= Effective relay s operation differential current Id= Relay s setting differential current I R I d Id I d { Is/In =[d>] for F87 =[d>>] for F87 Low Set Differential Element 4 In addition to the multi-slope bias characteristic, the low set differential element is further equipped with programmable nd and 5th harmonic restraint logic. During transformer energization, significant nd harmonic current is present, which may result in false trips. This requires the relay to suppress its response to the nd harmonic component of current. The MD3T allows for adjustment of the nd harmonic restraint element over the range of 0. to 0.3 pu of the transformer s rated current. Similarly, over-excitation of the transformer may result in significant levels of 5th harmonic current, requiring similar restraint characteristics. The MD3T allows for an adjustment range of 0. - 0.4 pu of rated current. Either or both the nd and 5th harmonic restraint elements may be disabled if desired. To avoid problems associated with the harmonic restraint elements from being too sensitive on actual I d R% = (I 00 -I ) = 00 I R (I -I )/ 3 Is I = 4 In In Is I = d R% In In + ( I R In -- 0.5) 00 Is = In I d Is 4 8 In R% I + + ( R.5) In 00 In - faults and blocking the relay, the MD3T allows the harmonic restraint settings to be lowered to as little as one-half the normal settings during a programmable time period following transformer energization. Transformer energization is sensed via a digital input connected to an auxiliary contact on the transformer s breaker. High Set Differential An instantaneous (high set) differential element is provided to quickly remove the transformer from service in the event of severe internal faults. To effectively eliminate the effects of dc offsets and harmonics, the relay trips on the sensing of sequential positive and negative peak currents whose magnitude exceeds the high set trip level. The high set trip level may be either set to be a fixed value, or may be biased in the same fashion as the low set element. Due to the operational nature of the element, no harmonic programmable harmonic restraint elements are provided. This element will operate in less than cycle (5 msec).

Ground Fault Protection To provide greater coverage for ground faults, the MD3T monitors the fundamental frequency component of current fed into the ground element inputs. Depending upon the connection, this element can perform: Restricted ground fault protection for one Y connected winding (87N). Residual current (3Io) protection of one winding (5G). Neutral current protection of one winding (5N). This ground fault element consists of a definite time high set element and a fixed 30 ms response time instantaneous element. This element may be blocked during transformer energization. Targets Eight bright LED targets are provided as follows: One red LED for each of the three phase differential elements. One red LED for the restricted ground fault element. Two red LEDs to signal when the nd or 5th harmonic currents respectively exceed the restraint level. For all of the above, the LEDs flash when the element is picked up, and constantly illuminate upon trip. In addition, one yellow LED is provided which illuminates when the blocking input is active. A second yellow LED flashes when the relay is in programming mode, and illuminates constantly upon relay or power supply failure. Blocking Input An opto-isolated programmable blocking input is provided. This input may be programmed so that when activated, any combination of the low set differential, high set differential, or ground fault elements may be blocked. While the blocking input is active, the pickup of any element associated with the blocking input is prevented. Sensing of the input quantities and the countdown of any timers begins only when the blocking is removed. Reset Characteristic The programmable output relays may be programmed to reset in one of two manners. Instantaneously upon the input or calculated quantities dropping below the pickup value. Manual reset (by front panel or computer command) only. Measurements and Inrush Values The following quantities are continuously monitored and are available for display at the relay and are accessible by software: RMS values of each phase s differential current Fundamental frequency component of the neutral current in per unit of the rated phase current. RMS values of the three high side currents. RMS values of the three low side currents. nd and 5th harmonic current components of each of the phase s differential currents. In addition, the maximum values of each of these quantities during the first 00 msec after transformer energization is also recorded. This makes it convenient to quickly review the inrush currents associated with the most recent energization. Last Trip Record The following parameters are stored in non-volatile memory, providing details of the last five trip events: Which element was the cause of the last trip. The values of all measured currents at the time of trip. In addition the relays keep a cumulative total of the cause of all breaker trips. 50-30 Oscillography The MD3T stores two oscillographic records which are made available for downloading to a PC for graphing. All six input phase currents are recorded. Each oscillographic record consists of 8 pre-trigger and 8-post trigger cycles, for a total of 6 cycles. The waveform is sampled at samples per cycle. Storage of an oscillographic record may be programmed to occur automatically every time a protective element trips, or to occur only upon an external trigger. Output Elements The following functions may be programmed to one or more of the output relays. The only limitation is that pick-up and time delay functions may not be assigned to operate the same output relay(s). Low set differential element. High set differential element. Instantaneous ground fault element. Time delayed ground fault element. Diagnostics Complete memory and circuit diagnostics are run upon powering the relay. The revision level of the firmware is displayed at this time. The relay runs a comprehensive set of diagnostics every 5 minutes that includes memory checksum, test of the A/D converters by injection of an internally generated reference voltage, and a check of the ALU. The relay provides two manual test routines which may be run at any time. The first routine performs the same 5 minute test and in addition checks the target LEDs and the control circuitry to the output relays without operating the output relays. The second test is identical but also operates the output relays. 3

Figure 3. Wiring Diagram for the MD3T Transformer Differential Relay used for the 87T Protection Only Figure 4. Wiring Diagram for the MD3T Transformer Differential Relay used for 87T and 5G Protection 4

50-30 Figure 5. Wiring Diagram for the MD3T transformer Differential Relay used for 87T and 5N (Restricted Ground (Earth) Fault) Protection Figure 6. Wiring Diagram for the MD3T Transformer Differential Relay used for 87T and 87N (Restricted Ground (Earth) Fault) Protection 5

MD3T Transformer Differential Relay TABLE Functional Specifications 6 Nominal system frequency setting range...50 or 60 Hz Programmable rated primary input current of phase CTs... - 9999A in A steps(high and low side CT programmable separately) Programmable rated phase-to-phase voltage of transformer...0.0 to 380.00 kv in 0.0 kv steps...(high and low side voltages programmable separately) Transformer connection and vector group...yy0 to Yz0 Differential Element Minimum pick-up level of low set differential element...0.0 to 0.50 pu of rated CT current in 0.0 pu step Minimum pick-up level of high set differential element...0 to 8.0 pu of rated CT current in 0. pu steps Bias percentage slope from 0.5 pu to.5 pu rated CT current...0-50% in % steps nd Harmonic restraint level...0.0 to 0.30 pu of the differential current in 0.0 pu steps 5th Harmonic restraint level...0.0 to 0.40 pu of the differential current in 0.0 pu steps Harmonic restraint multiplier (reduction)...0.50 to.00 pu of original setting in 0.0 pu steps during energization...(nd and 5th harmonic restraint multipliers programmable separately) Harmonic restraint reduction timer (starting at transformer energization) 0.05 to 99.00 seconds in 0.0 sec. steps Ground Fault Element Minimum pick-up level for ground fault element...0.0 to.00 pu of rated CT current in 0.0 pu steps Time delay of ground fault element...0.0 to 9.99 seconds in 0.0 second steps as described in IEC 76 Dimensional and Electrical Specifications See Catalog Section 50-05 for electrical specifications and dimensional information on all Edison Relays. Ordering Information Construct catalog number from Table. Example: MD3TL5JS is an MD3T with low range power supply, 5A CT inputs, in a single relay case. If ordering two or more relays to be fit in a common case, the first relay ordered should indicate the case style desired. This relay will be located in the leftmost bay of the case. Subsequent relays should use the C, C3, or C4 suffixes to denote their position in the case using the leftmost bay as a C reference. TABLE Catalog Numbers 997 Cooper Power Systems, Inc. Edison is a registered trademark of Cooper Industries, Inc. Description Catalog Number Base Relay MD3T To the above add one each of the following applicable suffixes Power Supply 4-0V AC/DC L 90-0V AC/DC H Rated CT Input A 5A 5 Modbus Protocol J Case Style Draw out relay only, no cabinet supplied D Single relay case S Double relay case T 9" Rack mount cabinet N Mounting Position Denotes mounting position in either a double C case or 9" Rack along with other relays C3 ordered at the same time. C4 The power supplies are user replaceable and interchangeable. See Catalog section 50-99. The relay itself may be drawn out of any of the listed cases and plugged into any of the other case styles. The catalog number specified during ordering denotes the type of cabinet in which the relay will be shipped. Printed on Recycled Paper P.O. Box 640, Waukesha, WI 5387 http://www.cooperpower.com/