PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS

Similar documents
Catastrophic Relay Misoperations and Successful Relay Operation

Testing Numerical Transformer Differential Relays

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

DOUBLE-ENDED FAULT LOCATORS

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

Visualization and Animation of Protective Relay Operation

Pinhook 500kV Transformer Neutral CT Saturation

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

BUS2000 Busbar Differential Protection System

Forward to the Basics: Selected Topics in Distribution Protection

Verifying Transformer Differential Compensation Settings

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

Transformer Protection

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

889 Advanced Generator Protection Technical Note

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Improving Transformer Protection

Generator Protection Overcomes Current Transformer Limitations

Module 10. Initiation Code RELIABILITY ACCOUNTABILITY

Performance Analysis of Traditional and Improved Transformer Differential Protective Relays

Event Analysis Tutorial

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

ANALYSIS OF A DIFFERENTIAL AND OVERCURRENT OPERATION ON A 345KV HIGH VOLTAGE LINE REACTOR

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

1

Evaluating the Impact of Increasing System Fault Currents on Protection

How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate

Distance Relay Response to Transformer Energization: Problems and Solutions

Transformer Differential Protection Lab

Generator Protection GENERATOR CONTROL AND PROTECTION

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents

Malfunction of Differential Relays in Wind Farms

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN

Transformer Protection Principles

Overcurrent Elements

POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

Unit Auxiliary Transformer (UAT) Relay Loadability Report

II. DIFFERENTIAL PROTECTION

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

Transformer Protection

ATP modeling of internal transformer faults for relay performance testing

Protective Relaying of Power Systems Using Mathematical Morphology

Anti-IslandingStrategyforaPVPowerPlant

70 TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY COLLEGE STATION, TEXAS APRIL 3 APRIL 6, 2017

Commissioning Process and Acceptance Test of a Sub-harmonic Protection Relay

Power Plant and Transmission System Protection Coordination Fundamentals

Impact of Incipient Faults on Sensitive Protection

Improved power transformer protection using numerical relays

Power System Protection

2015 Relay School Bus Protection Mike Kockott March, 2015

CURRENT TRANSFORMER SELECTION TECHNIQUES FOR LOW-VOLTAGE MOTOR CONTROL CENTERS

Protecting Large Machines for Arcing Faults

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA

Protection of a 138/34.5 kv transformer using SEL relay

Solutions to Common Distribution Protection Challenges

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

Study of the Impact of Energization of 500 kv Autotransformer in Directional Overcurrent Relays of Adjacent Transmission Lines

Back to the Basics Event Analysis Using Symmetrical Components

Module 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY

Research on the Reason for Transformer Differential Protection Mal-operation Caused by Sympathetic Inrush

Power Plant and Transmission System Protection Coordination

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Bus Protection Fundamentals

Utility Interconnection and System Protection

Line Protection Roy Moxley Siemens USA

Power Quality Basics. Presented by. Scott Peele PE

Power Plant and Transmission System Protection Coordination

Analysis of Modern Digital Differential Protection for Power Transformer

Introduction to Harmonics and Power Quality

NVESTIGATIONS OF RECENT BLACK-

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

International Journal of Digital Application & Contemporary research Website: (Volume 2, Issue 10, May 2014)

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Fundamentals of Power Quality

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

A Model of A Differential Protection Relay

Substation Testing and Commissioning: Power Transformer Through Fault Test

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

COPYRIGHTED MATERIAL. Index

Using a Multiple Analog Input Distance Relay as a DFR

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

g GE POWER MANAGEMENT

Redundant Bus Protection Using High-Impedance Differential Relays

T-68 Protecting Your Equipment through Power Quality Solutions

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Performance of Relaying During Wide-area Stressed Conditions

Z. Kuran Institute of Power Engineering Mory 8, Warszawa (Poland)

Considerations for Power Plant and Transmission System Protection Coordination

Transcription:

PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS BY STEVE TURNER, Beckwith Electric Company, Inc. This paper provides detailed technical analysis of two relay misoperations and demonstrates how to prevent them from occurring. Case 1: An unwanted breaker failure operation tripped for a large offline generator during high load, resulting in an outage in the adjoining downtown area of a large city. Case 2: A transformer differential trip protecting the generator step-up transformer at a process plant occurred due to sympathetic inrush when a large nearby GSU was energized via the interconnecting high-voltage transmission line, resulting in an extended outage. Each individual analysis ends with a conclusion stating why the relay misoperated and providing a recommendation on the best practice for the particular application. CASE 1: UNWANTED BREAKER FAILURE OPERATION LARGE GENERATOR TRIPPED DURING HIGH-LOAD PERIOD During a period of high load, a breaker failure trip for a large offline generator located in the downtown area of a large city resulted in an outage. Figure 1 shows the system topology at the time of the trip. Note that the generator is connected to Figure 1: System Operating Conditions the transmission grid via a high-voltage breaker. The links connecting the generator to the GSU were open as well as the high-side breaker. The lowside winding of the GSU drew excitation current since it was energized via the auxiliary station service. Original Breaker Failure Scheme Logic Figure 2 shows the original logic used for this breaker failure protection scheme. Figure 2: Breaker Failure Logic NETAWORLD 43

Original Protection Settings Figure 3 shows the original relay settings for this breaker failure scheme. Fault Current Signals Figure 4 shows the oscillography captured by the relay at the time of the trip. Figure 5 shows the current phasors measured by the protective relay when the breaker failure occurred. Figure 3: Breaker Failure Settings Figure 4: Fault Event Oscillography Figure 5: Fault Current Phasors 44 WINTER 2016

Case 1 Conclusion The breaker failure trip occurred because I C was above the current detector pickup setting and input 4 (BFI) was asserted. Original Protection Settings Figure 8 shows the original settings for the transformer differential protection. The breaker failure function may be used for a unit breaker rather than a generator breaker. It is limited in that no fault detector is associated with the unit breaker. Output contact operation would occur if any of the initiate contacts close, and the 52b contact indicated a closed breaker after the set time delay. The corresponding logic is shown in Figure 6. Figure 8: 87T Settings Figure 6: Fault Current Phasors CASE 2: TRANSFORMER DIFFERENTIAL TRIP DUE TO SYMPATHETIC INRUSH The transformer differential relay protecting the step-up transformer at a processing plant tripped when a nearby large GSU at a power plant was energized from the high side. The trip was due to sympathetic inrush current flowing through the step-up transformer (Figure 7). Fault Current Signals Figure 9 shows the oscillography captured by the relay at the time of the trip. Note that current input IAW1 is almost completely offset, and there is some distortion in other current inputs as well. Figure 7: System Operating Conditions (Arrows Indicate Direction of Inrush Current) Figure 9: Fault Event Oscillography (Raw Waveforms) NETAWORLD 45

Harmonic Restraint Calculations Figure 10 shows the second harmonic content of the current inputs at the time of the trip. The second harmonic differential current present when the trip occurred was as follows: A-Phase = 17 percent B-Phase = 13 percent C-Phase = 13 percent If the ratio is greater than the restraint setting, then the transformer differential protection is blocked (Figure 12). Figure 12: Even Harmonic Restraint Logic The original second harmonic restraint setting was 20 percent for the electro-mechanical transformer differential relay. The customer used the same setting for the multi-function numerical relay that replaced the original electro-mechanical relay. Figure 10 showed that a setting of 20 percent was not sensitive enough to detect the sympathetic inrush current flowing through the step-up transformer. Figure 10: Fault Event Oscillography (Second Harmonic Content) The ratio of harmonic to fundamental differential current used to restrain the transformer differential protection is calculated as follows (Figure 11): Case 2 Conclusion For several decades, electro-mechanical relays had a fixed harmonic inhibit level of 20 percent. This worked well for a period of time until transformer manufacturers began making better transformers that used less material and were designed with smaller tolerances. Therefore, modern laminated-steel-core transformers will not reliably produce 20 percent second harmonic current during inrush. Based upon this particular event, an 11 percent setting for the second harmonic restraint would be the most reliable. Note that the multi-function numerical relay in this application actually uses the root mean square (RMS) of the second and fourth harmonic differential current, but that still was not enough to restrain the protection. Figure 11: Even Harmonic Restraint Equation 46 WINTER 2016

FINAL CONCLUSION The technical analysis of these two relay misoperations, along with examples of how to use the data recorded by a relay during these types of conditions, should help you understand why each misoperation occurred and how to implement best practices for each particular application. Knowing that the first misoperation was due to an incorrect relay setting, while the second was due to an incorrect application, should clarify the need for careful attention during the design and initial work stages. Steve Turner, an IEEE Senior Member, is a Senior Applications Engineer at Beckwith Electric Company. His previous experience includes work as an application engineer with GEC Alstom and as an application engineer in the international market for SEL, focusing on transmission line protection applications. Steve worked for Duke Energy (formerly Progress Energy), where he developed a patent for double-ended fault location on overhead transmission lines. He has a BSEE and MSEE from Virginia Tech. Steve has presented at numerous conferences, including Georgia Tech Protective Relay Conference, Western Protective Relay Conference, Energy Council of the Northeast, and Doble User Groups, as well as various international conferences.