Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Similar documents
A DUMMIES GUIDE TO GROUND FAULT PROTECTION

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Busbars and lines are important elements

Upgrading Your Electrical Distribution System To Resistance Grounding

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Protection of Electrical Networks. Christophe Prévé

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

COPYRIGHTED MATERIAL. Index

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

System Protection and Control Subcommittee

ARC FLASH HAZARD ANALYSIS AND MITIGATION

Electrical Protection System Design and Operation

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Transmission Protection Overview

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Bus Protection Fundamentals

COPYRIGHTED MATERIAL. Introduction to protective relaying. 1.1 What is relaying?

Webinar: An Effective Arc Flash Safety Program

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Notes 1: Introduction to Distribution Systems

Distribution Feeder Principles

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

Power systems Protection course

Grounding for Power Quality

Protection Introduction

Back to the Basics Current Transformer (CT) Testing

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

Using a Multiple Analog Input Distance Relay as a DFR

A short introduction to Protection and Automation Philosophy

TABLE OF CONTENT

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson

TECHNICAL BULLETIN 004a Ferroresonance

How to maximize reliability using an alternative distribution system for critical loads

Power System Protection Manual

NERC Protection Coordination Webinar Series July 15, Jon Gardell

PIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

Utility Interconnection and System Protection

Tab 2 Voltage Stresses Switching Transients

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Protective Relays Digitrip 3000

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Transformer Protection

FERRORESONANCE SIMULATION STUDIES USING EMTP

Safety through proper system Grounding and Ground Fault Protection

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Time-current Coordination

Comparison of recloser and breaker standards

EH2741 Communication and Control in Electric Power Systems Lecture 2

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Connection Impact Assessment Application

Protective Relaying for DER

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

2. Current interruption transients

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Power System Fundamentals

Power Quality Basics. Presented by. Scott Peele PE

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

BED INTERCONNECTION TECHNICAL REQUIREMENTS

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

1% Switchgear and Substations

Embedded Generation Connection Application Form

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Optimizing HV Capacitor-Bank Design Protection & Testing

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Power Plant and Transmission System Protection Coordination Fundamentals

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Generator Protection GENERATOR CONTROL AND PROTECTION

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

Embedded Generation Connection Application Form

Impact Assessment Generator Form

2 Grounding of power supply system neutral

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

EE 741 Spring Electric Power Distribution Systems An Overview

Transmission System Phase Backup Protection

Embedded Generation Connection Application Form

Transcription:

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1

Protection Fundamentals By John Levine 2

Introductions Tools Outline Enervista Launchpad On Line Store Demo Relays at Levine ANSI number Training CD s Protection Fundamentals 3

Objective We are here to help make your job easier. This is very informal and designed around Applications. Please ask question. We are not here to preach to you. The knowledge base in the room varies greatly. If you have a question, there is a good chance there are 3 or 4 other people that have the same question. Please ask it. 4

Tools 5

6

Demo Relays at L-3 7

Relays at L-3 8

9

GE Training CD s 10

ANSI Symbols 11

Conversion of Electro-Mechanical to Electronic sheet 12

PowerPoint presentations at: http://l-3.com/private/ieee/ 13

Protection Fundamentals 14

Desirable Protection Attributes Reliability: System operate properly Security: Don t trip when you shouldn t Dependability: Trip when you should Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition Speed: Usually the faster the better in terms of minimizing equipment damage and maintaining system integrity Simplicity: KISS Economics: Don t break the bank 15

Art & Science of Protection Selection of protective relays requires compromises: Maximum and Reliable protection at minimum equipment cost High Sensitivity to faults and insensitivity to maximum load currents High-speed fault clearance with correct selectivity Selectivity in isolating small faulty area Ability to operate correctly under all predictable power system conditions 16

Art & Science of Protection Cost of protective relays should be balanced against risks involved if protection is not sufficient and not enough redundancy. Primary objectives is to have faulted zone s primary protection operate first, but if there are protective relays failures, some form of backup protection is provided. Backup protection is local (if local primary protection fails to clear fault) and remote (if remote protection fails to operate to clear fault) 17

Primary Equipment & Components Transformers - to step up or step down voltage level Breakers - to energize equipment and interrupt fault current to isolate faulted equipment Insulators - to insulate equipment from ground and other phases Isolators (switches) - to create a visible and permanent isolation of primary equipment for maintenance purposes and route power flow over certain buses. Bus - to allow multiple connections (feeders) to the same source of power (transformer). 18

Primary Equipment & Components Grounding - to operate and maintain equipment safely Arrester - to protect primary equipment of sudden overvoltage (lightning strike). Switchgear integrated components to switch, protect, meter and control power flow Reactors - to limit fault current (series) or compensate for charge current (shunt) VT and CT - to measure primary current and voltage and supply scaled down values to P&C, metering, SCADA, etc. Regulators - voltage, current, VAR, phase angle, etc. 19

Types of Protection Overcurrent Uses current to determine magnitude of fault Simple May employ definite time or inverse time curves May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive May use various polarizing voltages or ground current for directionality Communication aided schemes make more selective 20

Instantaneous Overcurrent Protection (IOC) & Definite Time Overcurrent t CTI Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI (Clearing Time Interval) I 50 +2 50 +2 CTI Distribution Substation 21

(TOC) Coordination t Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI I CTI Distribution Substation 22

Time Overcurrent Protection (TOC) Selection of the curves uses what is termed as a time multiplier or time dial to effectively shift the curve up or down on the time axis Operate region lies above selected curve, while no-operate region lies below it Inverse curves can approximate fuse curve shapes 23

Time Overcurrent Protection (51, 51N, 51G) Multiples of pick-up 24

Differential Types of Protection current in = current out Simple Very fast Very defined clearing area Expensive Practical distance limitations Line differential systems overcome this using digital communications 26

Current, pu 1 pu Differential I P CT-X CT-Y I P I S +1 I R-X Relay I R-Y I S 1 + (-1) = 0 Note CT polarity dots This is a through-current representation 0-1 Perfect waveforms, no saturation DIFF CURRENT 27

Current, pu I P 2 pu 2 pu Fault CT-X CT-Y I P Differential X I S +2 0-2 I R-X Relay DIFF CURRENT I R-Y I S 2 + (+2) = 4 Note CT polarity dots This is an internal fault representation Perfect waveforms, no saturation 28

Types of Protection Voltage Uses voltage to infer fault or abnormal condition May employ definite time or inverse time curves May also be used for undervoltage load shedding Simple May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive 29

Types of Protection Frequency Uses frequency of voltage to detect power balance condition May employ definite time or inverse time curves Used for load shedding & machinery under/overspeed protection Simple May be slow Selectivity at the cost of speed can be expensive 30

Types of Protection Power Uses voltage and current to determine power flow magnitude and direction Typically definite time Complex May be slow Accuracy important for many applications Can be expensive 31

Types of Protection Distance (Impedance) Uses voltage and current to determine impedance of fault Set on impedance [R-X] plane Uses definite time Impedance related to distance from relay Complicated Fast Somewhat defined clearing area with reasonable accuracy Expensive Communication aided schemes make more selective 32

X Z L Impedance Relay in Zone 1 operates first Time between Zones is called CTI R T 2 Z B T 1 Z A 21 21 A B Source 33

Generation-typically at 4-20kV Transmission-typically at 230-765kV Typical Bulk Power System Receives power from transmission system and transforms into subtransmission level Subtransmission-typically at 69-161kV Receives power from subtransmission system and transforms into primary feeder voltage Distribution network-typically 2.4-69kV Low voltage (service)-typically 120-600V 36

Protection Zones 1. Generator or Generator-Transformer Units 2. Transformers 3. Buses 4. Lines (transmission and distribution) 5. Utilization equipment (motors, static loads, etc.) 6. Capacitor or reactor (when separately protected) Unit Generator-Tx zone Transformer zone Bus zone Line zone Bus zone Transformer zone Bus zone Motor zone ~ Generator XFMR Bus Line Bus XFMR Bus Motor 37

Zone Overlap 1. Overlap is accomplished by the locations of CTs, the key source for protective relays. 2. In some cases a fault might involve a CT or a circuit breaker itself, which means it can not be cleared until adjacent breakers (local or remote) are opened. Relay Zone A Relay Zone A Zone A Relay Zone B Zone B Zone A Relay Zone B Zone B CTs are located at both sides of CBfault between CTs is cleared from both remote sides CTs are located at one side of CBfault between CTs is sensed by both relays, remote right side operate only. 38

What Info is Required to Apply Protection 1. One-line diagram of the system or area involved 2. Impedances and connections of power equipment, system frequency, voltage level and phase sequence 3. Existing schemes 4. Operating procedures and practices affecting protection 5. Importance of protection required and maximum allowed clearance times 6. System fault studies 7. Maximum load and system swing limits 8. CTs and VTs locations, connections and ratios 9. Future expansion expectance 10. Any special considerations for application. 43

C37.2: Device Numbers Partial listing 44

One Line Diagram Non-dimensioned diagram showing how pieces of electrical equipment are connected Simplification of actual system Equipment is shown as boxes, circles and other simple graphic symbols Symbols should follow ANSI or IEC conventions 45

1-Line Symbols [1] 46

1-Line Symbols [2] 47

1-Line Symbols [3] 48

1-Line Symbols [4] 49

1-Line [1] 50

1-Line [2]

3-Line 52

CB Trip Circuit (Simplified) 55

Lock Out Relay PR 86b 86 TC 86a 86b Shown in RESET position 58

CB Coil Circuit Monitoring: T with CB Closed; C with CB Opened + Trip/Close Contact Coil Monitor Input 52/a or 52/b T/C Coil - Relay Breaker 52/a for trip circuit 52/b for close circuit 59

CB Coil Circuit Monitoring: Both T&C Regardless of CB state Relay Relay Breaker Breaker 60

Current Transformers Current transformers are used to step primary system currents to values usable by relays, meters, SCADA, transducers, etc. CT ratios are expressed as primary to secondary; 2000:5, 1200:5, 600:5, 300:5 A 2000:5 CT has a CTR of 400 61

Standard IEEE CT Relay Accuracy IEEE relay class is defined in terms of the voltage a CT can deliver at 20 times the nominal current rating without exceeding a 10% composite ratio error. For example, a relay class of C100 on a 1200:5 CT means that the CT can develop 100 volts at 24,000 primary amps (1200*20) without exceeding a 10% ratio error. Maximum burden = 1 ohm. 100 V = 20 * 5 * (1ohm) 200 V = 20 * 5 * (2 ohms) 400 V = 20 * 5 * (4 ohms) 800 V = 20 * 5 * (8 ohms) 62

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993) Application Burden Designation Impedance (Ohms) VA @ 5 amps Power Factor Metering B0.1 0.1 2.5 0.9 B0.2 0.2 5 0.9 B0.5 0.5 12.5 0.9 B0.9 0.9 22.5 0.9 B1.8 1.8 45 0.9 Relaying B1 1 25 0.5 B2 2 50 0.5 B4 4 100 0.5 B8 8 200 0.5 64

Voltage Transformers Voltage (potential) transformers are used to isolate and step down and accurately reproduce the scaled voltage for the protective device or relay VT ratios are typically expressed as primary to secondary; 14400:120, 7200:120 A 4160:120 VT has a VTR of 34.66 VP VS Relay 66

Typical CT/VT Circuits Courtesy of Blackburn, Protective Relay: Principles and Applications 67

CT/VT Circuit vs. Casing Ground Case Secondary Circuit Case ground made at IT location Secondary circuit ground made at first point of use 68

Equipment Grounding Prevents shock exposure of personnel Provides current carrying capability for the ground-fault current Grounding includes design and construction of substation ground mat and CT and VT safety grounding 69

System Grounding Limits overvoltages Limits difference in electric potential through local area conducting objects Several methods Ungrounded Reactance Coil Grounded High Z Grounded Low Z Grounded Solidly Grounded 70

System Grounding 1. Ungrounded: There is no intentional ground applied to the systemhowever it s grounded through natural capacitance. Found in 2.4-15kV systems. 2. Reactance Grounded: Total system capacitance is cancelled by equal inductance. This decreases the current at the fault and limits voltage across the arc at the fault to decrease damage. X 0 <= 10 * X 1 71

3. High Resistance Grounded: Limits ground fault current to 10A-20A. Used to limit transient overvoltages due to arcing ground faults. R 0 <= X 0C /3, X 0C is capacitive zero sequence reactance 4. Low Resistance Grounded: To limit current to 25-400A R 0 >= 2X 0 System Grounding 72

System Grounding 5. Solidly Grounded: There is a connection of transformer or generator neutral directly to station ground. Effectively Grounded: R 0 <= X 1, X 0 <= 3X 1, where R is the system fault resistance 73

Basic Current Connections: How System is Grounded Determines How Ground Fault is Detected Medium/High Resistance Ground Low/No Resistance Ground 79

Substation Types Single Supply Multiple Supply Mobile Substations for emergencies Types are defined by number of transformers, buses, breakers to provide adequate service for application 80

Industrial Substation Arrangements (Typical) 81

Industrial Substation Arrangements (Typical) 82

Utility Substation Arrangements (Typical) Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual Supply 2-sections Bus with HS Tie-Breaker, 2 Tx, Dual Supply 83

Utility Substation Arrangements (Typical) Bus 1 Bus 2 Breaker-and-a-half allows reduction of equipment cost by using 3 breakers for each 2 circuits. For load transfer and operation is simple, but relaying is complex as middle breaker is responsible to both circuits Ring bus advantage that one breaker per circuit. Also each outgoing circuit (Tx) has 2 sources of supply. Any breaker can be taken from service without disrupting others. 84

Tie breaker Utility Substation Arrangements (Typical) Main bus Aux. bus Main Reserve Transfer Bus 1 Bus 2 Double Bus: Upper Main and Transfer, bottom Double Main bus Main-Reserved and Transfer Bus: Allows maintenance of any bus and any breaker 85

Switchgear Defined Assemblies containing electrical switching, protection, metering and management devices Used in three-phase, high-power industrial, commercial and utility applications Covers a variety of actual uses, including motor control, distribution panels and outdoor switchyards The term "switchgear" is plural, even when referring to a single switchgear assembly (never say, "switchgears") May be a described in terms of use: "the generator switchgear" "the stamping line switchgear" 86

Switchgear Examples

A Good Day in System Protection CTs and VTs bring electrical info to relays Relays sense current and voltage and declare fault Relays send signals through control circuits to circuit breakers Circuit breaker(s) correctly trip What Could Go Wrong Here???? 94

A Bad Day in System Protection CTs or VTs are shorted, opened, or their wiring is Relays do not declare fault due to setting errors, faulty relay, CT saturation Control wires cut or batteries dead so no signal is sent from relay to circuit breaker Circuit breakers do not have power, burnt trip coil or otherwise fail to trip Protection Systems Typically are Designed for N-1 95

Protection Performance Statistics Correct and desired: 92.2% Correct but undesired: 5.3% Incorrect: 2.1% Fail to trip: 0.4% 96

Contribution to Faults 97

Fault Types (Shunt) 98

AC & DC Current Components of Fault Current 102

Useful Conversions 105

Per Unit System Establish two base quantities: Standard practice is to define Base power 3 phase Base voltage line to line Other quantities derived with basic power equations 106

Per Unit Basics 107

Short Circuit Calculations Per Unit System Per Unit Value = Actual Quantity Base Quantity V pu = V actual V base I pu = I actual I base Z pu = Z actual Z base 108

Short Circuit Calculations Per Unit System I base = MVA base x 1000 3 x kv L-L base Z base = kv2 L-L base MVA base 109

Short Circuit Calculations Per Unit System Base Conversion Z pu = Z actual Z base Z base = kv 2 base MVA base Z pu1 = MVA base1 kv 2 base1 X Z actual Z pu2 = MVA base2 kv 2 base2 X Z actual Z pu2 =Z pu1 x kv 2 base1 x MVA base2 kv 2 base2 MVA base1 110

A Study of a Fault. 123

Arc Flash Hazard 125

Protective Relaying Methods of Reducing Arc Flash Hazard Bus differential protection (this reduces the arc flash energy by reducing the clearing time Zone interlock schemes where bus relay selectively is allowed to trip or block depending on location of faults as identified from feeder relays Temporary setting changes to reduce clearing time during maintenance Sacrifices coordination FlexCurve for improved coordination opportunities Employ 51VC/VR on feeders fed from small generation to improve sensitivity and coordination Employ UV light detectors with current disturbance detectors for selective gear tripping 129

Arc Flash Hazards 131

Arc Pressure Wave 132

Copy of this presentation are at: www.l-3.com\private\ieee 136

Protection Fundamentals QUESTIONS? 137