Automatic Generation Control of an Interconnected Hydro-Thermal System Using Fuzzy Logic and Conventional Controller

Similar documents
Improvement in Dynamic Response of Interconnected Hydrothermal System Using Fuzzy Controller

Automatic Generation control of interconnected hydrothermal power plant Using classical and soft computing Technique

LFC in hydro thermal System Using Conventional and Fuzzy Logic Controller

International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 ISSN

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

Automatic Load Frequency Control of Two Area Power System Using Proportional Integral Derivative Tuning Through Internal Model Control

Load Frequency Control of Interconnected Hydro-Thermal Power System Using Fuzzy and Conventional PI Controller

CHAPTER 1 INTRODUCTION

An intelligent fuzzy logic controller applied to multi-area load frequency control

AUTOMATIC GENERATION CONTROL OF REHEAT THERMAL GENERATING UNIT THROUGH CONVENTIONAL AND INTELLIGENT TECHNIQUE

AGC in Five Area Interconnected Power System of Thermal Generating Unit Through Fuzzy Controller

Load Frequency Control in an Interconnected Hydro Hydro Power System with Superconducting Magnetic Energy Storage Units

Performance Analysis of PSO Optimized Fuzzy PI/PID Controller for a Interconnected Power System

International Journal of Advance Engineering and Research Development. Fuzzy Logic Based Automatic Generation Control of Interconnected Power System

Automatic Generation Control of Two Area using Fuzzy Logic Controller

ADVANCES in NATURAL and APPLIED SCIENCES

1. Governor with dynamics: Gg(s)= 1 2. Turbine with dynamics: Gt(s) = 1 3. Load and machine with dynamics: Gp(s) = 1

Performance Improvement Of AGC By ANFIS

Load Frequency Control of Three Different Area Interconnected Power Station using Pi Controller

TWO AREA CONTROL OF AGC USING PI & PID CONTROL BY FUZZY LOGIC

NEURAL NETWORK BASED LOAD FREQUENCY CONTROL FOR RESTRUCTURING POWER INDUSTRY

Load Frequency Control of Multi-Area Power Systems Using PI, PID, and Fuzzy Logic Controlling Techniques

ROBUST TECHNIQUE LFC OF TWO-AREA POWER SYSTEM WITH DYNAMIC PERFORMANCE OF COMBINED SMES AND SSSC CONTROL

A new approach for Tuning of PID Load Frequency Controller of an Interconnected Power System

MODELING AND ANALYSIS OF THREE AREA THERMAL POWER SYSTEM USING CONVENTIONAL CONTROLLERS

Stability Control of an Interconnected Power System Using PID Controller

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

Effect of Non-linearities in Fuzzy Based Load Frequency Control

Design of PI Controller using MPRS Method for Automatic Generation Control of Hydropower System

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

[Jahangir* et al., 5.(6): June, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

LOAD FREQUENCY CONTROL FOR TWO AREA POWER SYSTEM USING DIFFERENT CONTROLLERS

Design of Self-Tuning Fuzzy PI controller in LABVIEW for Control of a Real Time Process

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller

Design of GA Tuned Two-degree Freedom of PID Controller for an Interconnected Three Area Automatic Generation Control System

AUTOMATIC VOLTAGE REGULATOR AND AUTOMATIC LOAD FREQUENCY CONTROL IN TWO-AREA POWER SYSTEM

LOAD FREQUENCY CONTROL FOR THREE AREA SYSTEM WITH TIME DELAYS USING FUZZY LOGIC CONTROLLER

Artificial Intelligent and meta-heuristic Control Based DFIG model Considered Load Frequency Control for Multi-Area Power System

FUZZY LOGIC BASED DIRECT TORQUE CONTROL OF THREE PHASE INDUCTION MOTOR

Hybrid evolutionary algorithm based fuzzy logic controller for automatic generation control of power systems with governor dead band non-linearity

ISSN: Journal of World s Electrical Engineering and Technology J. World. Elect. Eng. Tech. 1(1): 43-50, 2012

Control of Load Frequency of Power System by PID Controller using PSO

Load Frequency Control of Multi-Area Power System with PI Controller

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Load Frequency Control of Multi Area Hybrid Power System Using Intelligent Controller Based on Fuzzy Logic

Load frequency control of interconnected system

Stability Issues of Smart Grid Transmission Line Switching

Load frequency control in Single area with traditional Ziegler-Nichols PID Tuning controller

Keywords: Two area power system, Diverse sources of power generation, Automatic generation Control,Particle Swarm Optimization, PID controller2

CHAPTER 4 ON LINE LOAD FREQUENCY CONTROL

Fuzzy Controllers for Boost DC-DC Converters

AUTOMATIC GENERATION CONTROL OF INTERCONNECTED POWER SYSTEM WITH THE DIVERSE SOURCES USING SUPERCONDUCTING MAGNETIC ENERGY STORAGE (SMES)

Optimal PID Tuning for AGC system using Adaptive Tabu Search

COMPUTATION OF STABILIZING PI/PID CONTROLLER FOR LOAD FREQUENCY CONTROL

Fuzzy Intelligent Controller for the MPPT of a Photovoltaic Module in comparison with Perturb and Observe algorithm

Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh

Performance Analysis of Fuzzy Logic And PID Controller for PM DC Motor Drive Khalid Al-Mutib 1, N. M. Adamali Shah 2, Ebrahim Mattar 3

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

DSPACE BASED FUZZY LOGIC CONTROLLED BOOST CONVERTER

SSRG International Journal of Electrical and Electronics Engineering ( SSRG IJEEE ) Volume 3 Issue 1 January 2016

Study and modeling of Speed control of Hydraulic Governing System using PD and PID Controllers

Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction

Load frequency control in two area multi units Interconnected Power System using Multi objective Genetic Algorithm

A Stabilization of Frequency Oscillations in a Parallel AC-DC Interconnected Power System via an HVDC Link

Comparative analysis of Conventional MSSMC and Fuzzy based MSSMC controller for Induction Motor

Simulation of Synchronous Machine in Stability Study for Power System: Garri Station as a Case Study

Comparison of Adaptive Neuro-Fuzzy based PSS and SSSC Controllers for Enhancing Power System Oscillation Damping

Application of Fuzzy Logic Controller in Shunt Active Power Filter

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Ant colony optimization algorithm based PID controller for LFC of single area power system with non-linearity and boiler dynamics

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Fuzzy Adapting PID Based Boiler Drum Water Level Controller

CHAPTER 3 WAVELET TRANSFORM BASED CONTROLLER FOR INDUCTION MOTOR DRIVES

DESIGNING POWER SYSTEM STABILIZER FOR MULTIMACHINE POWER SYSTEM USING NEURO-FUZZY ALGORITHM

Development of a Fuzzy Logic Controller for Industrial Conveyor Systems

Self-Tuning PI-Type Fuzzy Direct Torque Control for Three-phase Induction Motor

Decentralized Model Predictive Load Frequency Control of deregulated power systems in tough situations

Self Tuning Mechanism using Input Scaling Factors of PI like Fuzzy Controller for Improved Process Performance

Automatic Generation Control of Three Area Power Systems Using Ann Controllers

Fuzzy Logic Based Speed Control System Comparative Study

EFFECT OF CUCKOO SEARCH OPTIMIZED INTEGRAL - DOUBLE DERIVATIVE CONTROLLER WITH TCPS FOR CONTAINING OSCILLATIONS IN AUTOMATIC GENERATION CONTROL (AGC)

High Frequency Soft Switching Boost Converter with Fuzzy Logic Controller

Tuning of PID Controller in Multi Area Interconnected Power System Using Particle Swarm Optimization

LOAD FREQUENCY CONTROL OF TWO AREA POWER SYSTEM

Knowledge-based Adaptive Frequency Control of Gas Turbine Generator Model for Multi-machine Power System

Comparison of Fuzzy Logic Based and Conventional Power System Stabilizer for Damping of Power System Oscillations

FUZZY CONTROLLER FOR A SHUNT ACTIVE POWER FILTER

Comparison of Multi-Area Load Frequency Control by PI and Fuzzy Logic Controller Using SMES

Design Of PID Controller In Automatic Voltage Regulator (AVR) System Using PSO Technique

Simulation and Analysis of Cascaded PID Controller Design for Boiler Pressure Control System

Simulation of Optimal Speed Control for a DC Motor Using Conventional PID Controller and Fuzzy Logic Controller

Interconnected System for Grid Stability with PI and Fuzzy-PID Controller

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

Digital Simulation and Analysis of Sliding Mode Controller for DC-DC Converter using Simulink

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Transcription:

International Journal of Scientific & Engineering esearch, Volume 3, Issue 8, August0 ISSN 9558 Automatic Generation Control of an Interconnected HydroThermal System Using Fuzzy Logic and Conventional Controller Ashis Tripathy a, Ajit umar Mohanty b, Shubhendu umar Sarangi c Abstract This paper deals with Automatic Generation Control (AGC) of interconnected two area HydroThermal System using conventional integral and fuzzy logic controllers. The hydro area is considered with an electric governor and thermal area.is considered with reheat turbine. Effects of different number of triangular membership functions and inputs for fuzzy logic controller on dynamic responses have been explored. % step load perturbation has been considered occurring either in individual area or occurring simultaneously in all the areas. In this thesis, fuzzy sets and fuzzy logic are highly reflected by applying to the system. Consequently, improved results are also obtained. However, as fuzzy logic is human being dependent rule base, misinterpretation can corrupt the result. Hence by focusing on its proper methodology it is possible to acquire a low expenditure of time and effort as an optimal result. Index Terms ACE, Integral Control, Membership function, Step load Petrubation, Steady State, fuzzy logic controller, TieLine INTODUCTION MODEN power system network consists of a number of utilities interconnected together & power is exchanged between utilities over tielines by which they are connected. Automatic generation control (AGC) plays a very important role in power system as its main role is to maintain the system frequency and tie line flow at their scheduled values during normal period and also when the system is subjected to small step load perturbations. In analyzing the problems associated with the controlled operation of power systems, there are many possible parameters of interest. In the classical AGC system the balance between generation and load was achieved by detecting frequency and tieline flow deviations, which were used in generating an ACE signal. The ACE signal was used for an integral feedback control strategy. At steady state, the generation would be matched exactly with the load, causing tieline power and frequency deviation to drop to zero. At transient state, there should be a flow of power from other areas to supply the excess load in the area where transient drop (during a sudden area load change, area frequency experiences a load, known as transient drop) occurs. Concordia and irchmayer [3] have studied the AGC of a hydrothermal system considering nonreheat type thermal system neglecting generation rate constraints. othari, aul, Nanda [4] have investigated the AGC problem of a hydrothermal system provided with integral type supplementary controllers. Ashis Tripathy. Department of Electronics & Instrumentation Engineering, S O A University, Bhubaneswar, India,Email:ashisbidyarthi@gmail.com Ajit umar Mohanty is Currently Working as Assistant Manager at Odisha Power Transmission Corporation Limited, Basta, Balasore75609, Odisha, India.,Email: ajit_04@yahoo.com Shubhendu umar Sarangi,Department of Electronics & Instrumentation Engineering, S O A University, Bhubaneswar, India,Email:shubhendu977@gmail.com IJSE 0 In modern hydro thermal system, reheat type turbine and electric governor [] are used. Perhaps Nanda, othari and Satsangi [5] are the first to present comprehensive analysis of AGC of an interconnected hydrothermal system in continuousdiscrete mode with classical controllers. OPEATIONAL SIMULATION MODEL While two areas are operating in unison, the ultimate motive is to maintain the stability. To maintain stable operating condition frequency of the tielines should always be constant. If any unstable situation is raised in the system, load frequency relay should catch that and immediate action will be taken by the controller. Actually the relationship between speed and load can be adjusted by changing the input load reference set point. By changing the load reference the, the generator characteristics can be set to give the reference frequency at any desired output. The basic control input to a generating unit as far as generation control considered is the load reference set point. It is seen that steadystate frequency can be brought back to the scheduled value by adjusting the speed changer set. This is achieved by integral control, which acts on the load reference setting of the governor of the unit. The integral control action ensures zero frequency error in steadystate. This supplementary control action is much slower than the primary speed control action. As such, it takes effect after the primary speed control has stabilized the system frequency.

International Journal of Scientific & Engineering esearch Volume 3, Issue 8, August0 ISSN 9558 B AEA.THEMAL AEA B Z O H i s Z O i H s rtr s T g s T s s d r AEA.HYDO AEA s d s p p f s i i p T t s Tp s w Tws 0.5T s T s p Tp s Fig. 4. P Tie (MW) Vs time (Sec) 3. With Fuzzy Logic Controller 3.. Model () 3 MF with 9 ules In a fuzzy scale, each membership functions have three linguistic stages and those are Low (L), Normal (N) and High (H). L N H Fig.. Transfer function Model of a TwoArea Interconnected HydroThermal System. 3 ESULTS 3. With Integral Controller When fig.3. is considered where the integral controller is used to control the operation of the interconnected twoarea hydrothermal system, the response curves shows a lot of improvement and fast response. Dynamic responses (Δf, Δf, ΔPG, ΔPG and ΔP Tie) are obtained for % step load perturbation considered either in hydro area or thermal area. A sampling period of second is considered in this system. The values of Integral gains considered are =0. and =0.09 for thermal area and hydro area respectively. The response curves become like under damped step response curve, which quite preferable in industrial arena. The frequency response curves for two area interconnected hydrothermal system are given below. Fig.. f (Hz) Vs Time (Sec) a 0 a Fig. 5. Possible Fuzzy Quantization of the range [a, a] by triangular shaped fuzzy numbers With the 3MFs 9 rules are formed and applied to the system. Here from the curves of change in frequency (Δf ) for the hydro area it can be concluded that 9 rules gives a very good result as compared to integral controller approach. The results show that the maximum peak overshoot is not reduced but the settling time is reduced as compared to integral controller approach. Similarly the other responses are observed. TABLE FUZZY ULE FO THEE MEMBESHIP FUNCTIONS Variable L N H L L L N N L N H H N H H But the curves of Δf, Δf and ΔP Tie show very good result as compared to that of integral controller approach. Because both the maximum peak overshoot and settling time are reduced. Here ΔP Tie is considered by taking % step load perturbation in both the areas. Fig. 3. f (Hz) Vs Time (Sec) Fig. 6. f (Hz) Vs Time (Sec) IJSE 0

International Journal of Scientific & Engineering esearch Volume 3, Issue 8, August0 3 ISSN 9558 For different membership functions appropriate feedback gain t has been found that corresponds to zero steady state error in the dynamic responses. Here % step load perturbation is considered either in thermal and hydro area for Δf, Δf. But for ΔP Tie % step load perturbation is considered in both the areas. The response curves show very good results as compared to 3MFs. Here both the settling time and maximum peak overshoot are reduced. Fig. 7. f (Hz) Vs Time (Sec) Fig. 9. f (Hz) Vs Time (Sec) Fig. 8. P Tie (MW) Vs time (Sec) 3.. Model () 5 MF with 5 ules In a fuzzy scale, each membership functions of five linguistic states of triangular type are mapped into the values of Negative Large (NL), Negative Small (NS), Zero Error (ZE), Positive Small (PS) and Positive Large (PL). With the 5MFs 5 rules are formed and are applied to the system. The response curves of Δf and Δf shows more stability. It shows typical hydrothermal area like behavior with fast settling time. TABLE FUZZY ULE FO 5 MEMBESHIP FUNCTIONS Variable NL NS ZE PS PL NL NL NL NS NS ZE NS NL NL NS ZE ZE ZE NS NS ZE PS PS PS ZE PS PS PL PL PL ZE ZE PS PL PL TABLE 3 OPTIMUM VALUES OF FEEDBAC GAINS FO DIFFEENT MEMBE SHIP FUNCTIONS Number of MFs t t 3 0.887 0.887 5 0.007 0.0 7 0.999.0 9 0.007 0.0 Fig. 0. f (Hz) Vs Time (Sec) Fig.. P Tie (MW) Vs Time (Sec) 3..3 Model (3) 7 MF with 49 ules In a fuzzy scale, each membership functions are divided into seven linguistic stages of triangular type and are given as Negative Large (NL), Negative Medium (NM), Negative Small (NS), Approximately Zero (AZ), Positive Small (PS), Positive Medium (PM) and Positive Large (PL). By using these 7 MF s 49 governing rules are formed and applied to the system. TABLE 4 FUZZY ULE FO 7 MEMBESHIP FUNCTIONS Variable NL NM NS AZ PS PM PL NL NL NL NL NL NM NS AZ NM NL NL NL NM NS AZ PS NS NL NL NM NS AZ PS PM AZ NL NM NS AZ PS PM PL PS NM NS AZ PS PM PL PL PM NS AZ PS PM PL PL PL PL AZ PS PM PL PL PL PL The response curves produce not only the best results among all the controllers like integral controller and FLC with 3MFs even if its give the result almost like the ideal case. From the response curves, it can be concluded that the response curve became under damped system with the maximum peak over IJSE 0

International Journal of Scientific & Engineering esearch Volume 3, Issue 8, August0 4 ISSN 9558 shoot 0.05 unit. Here a step load perturbation of % is considered either in thermal or hydro area for Δf, Δf, but for ΔP Tie % step load perturbation is considered in both the areas. Fig.. f (Hz) Vs Time (Sec) Fig. 5. f (Hz) Vs Time (Sec) Fig. 3. f (Hz) Vs Time (Sec) Fig. 6. f (Hz) Vs Time (Sec) Fig. 4. P Tie (MW) Vs time (Sec) 3..4 Model (4) 9 MF with 49 ules In a fuzzy scale, each membership functions are divided into nine linguistic stages of triangular type and are given as Too Low (TL), Negative Large (NL), Negative Medium (NM), Negative Small (NS), Approximately Zero (AZ), Positive Small (PS), Positive Medium (PM), Positive Large (PL) and Too High (TH). TABLE 5 FUZZY ULE FO 9 MEMBESHIP FUNCTIONS Variable TL NL NM NS AZ PS PM PL TH Fig. 7. P Tie (MW) Vs Time (Sec) 3.3 Stability Analysis From the response curves maximum peak shoot and settling time can be calculated. From that damping ratio can be calculated by the formula TL TL TL TL TL TL NL NM NS AZ NL TL TL TL TL NL NM NS AZ PS NM TL TL TL NL NM NS AZ PS PM NS TL TL NL NM NS AZ PS PM PL AZ TL NL NM NS AZ PS PM PL TH PS NL NM NS AZ PS PM PL TH TH PM NM NS AZ PS PM PL TH TH TH PL NS AZ PS PM PL TH TH TH TH TH AZ PS PM PL TH TH TH TH TH Here a step load perturbation of % is considered either in thermal or hydro area for Δf, Δf, but for ΔP Tie % step load perturbation is considered in both the areas. The response curves show very good results as compared to integral controller but comared with FLC 3MFs, 5MFs and 7MFs the show poor results. IJSE 0 % M P e 00 Where ξ= the damping ratio and M P is the maximum peak overshoot. By the following table, the stability of the system investigated by five controller approaches (four different FLC and Integral Controller) can be analyzed by comparing them. Controllers TABLE 6 COMPAISION OF TS, MP AND Ξ Settling Time,Ts (Sec) Max. Peak Overshoot Mp Damping atio ξ Integral 34.7 0.05 0.50 3 MF 7.56 0.05 0.50 5 MF 6.9 0.03 0.54 7 MF 7.33 0.05 0.50

Damping atio Mp Ts in Second International Journal of Scientific & Engineering esearch Volume 3, Issue 8, August0 5 ISSN 9558 9 MF 7.43 0.07 0.490 Stability Analysis based on Ts controllers. Finally from the above analysis and graphical representation it is clear that the FLC with 5MFs shows very good result as compared to other controllers with both the settling time and maximum peak overshoot reduced. 40 35 30 5 0 5 0 5 0 0.08 0.06 0.04 0.0 0.0 0.008 0.006 0.004 0.00 0 INTEGAL 3MF 5MF 7MF 9MF Different Controllers Fig. 8. 3.7 Stability Analysis Analysis Based Based on Ts on Ts Stability Analysis based on Mp INTEGAL 3MF 5MF 7MF 9MF Different Controllers Fig. 9. Stability Analysis Based on Mp 0.5 0.55 0.5 0.505 0.5 0.495 0.49 0.485 0.48 0.475 Stability Analysis based on Damping atio INTEGAL 3MF 5MF 7MF 9MF Different Controllers Fig. 0. Stability Analysis based on ξ From the graphical representation it can be concluded that the FLC with 3MFs, 5MFs, 7MFs and Integral controllers help the system to be within very controllable margin as their %M p is very small and the damping ratio is also small enough to control. According to settling time, FLC with 3MFs, 5MFs and 7MFs reached to the stable point very quickly than the other Mp Ts Damping atio 4 CONCLUSION In this paper different controlling schemes are applied for the automatic generation control (AGC) of an interconnected hydrothermal system. From the response curves and the stability analysis, the conclusion has come that Fuzzy logic controller shows very good dynamic response than conventional integral controller. The number of triangular membership functions (MFs) has an impact on dynamic responses and hence needs to be properly selected. FLC with 5MFs shows very good result as compared to all the other controllers The presence of fuzzy logic controller (FLC) in both the areas and a small step load perturbation in one area provides small steady state error. 5 APPENDICES Appendix A: Symbols f = Nominal System Frequency. i = Subscript referred to area i (, ). * = Subscript denotes optimum value. P ri =Area ated Power. H i= Inertia Constant. ΔP Tie = Incremental change in tie line power ΔP Di = Incremental load change in area i. ΔP gi = Incremental generation change in area i. D i = ΔP Di/Δf i. T ij = Synchronizing coefficient. i = Governor speed regulation parameter. T gi = Steam governor time constant of i th area. ri = Steam turbine reheat constant of i th area. T ri = Steam turbine reheat time constant for i th area. T ti = Steam turbine time constant for i th area. B i = frequency bias constant for i th area. T pi = H i/f*d i. (Power system time constant of i th area). pi = /D i. (Power system gain for i th area). Ii = Integral gain for i th area. d, p, i = Electric governor derivative, proportional and integral gains respectively. β i = (D i / i); Area frequency response characteristics. T w = Water starting time. ACE i = Area Control Error of area i. a = P r/p r. J = Cost Index. T = Sampling time period. Appendix B: Nominal Parameters P r =P r =000 MW; IJSE 0

International Journal of Scientific & Engineering esearch Volume 3, Issue 8, August0 6 ISSN 9558 H =H =5 Seconds D =D = 8.33*0 3 P.U.MW/Hz; r = r =0.5 = =.4 Hz/P.U.MW; T r =T r =0 Seconds p =; d =4; i=5 T p =T p =T P3 =0 Seconds T t =T t= 0.3 sec f=60 Hz; P tie, Max =00 MW; T g =0.08 sec Tw= sec.; a =; 6 EFEENCES [] [] N. Cohn, Some aspects of tieline bias control on interconnected power systems, Amer. Inst. Elect. Trans. Vol.75, pp. 45 436. Feb 953. [] [] C. Cordia, L.. irchmayer and E. A. Szymanski, Effect of speed governor dead band on tie line power and frequency control performance, Amer. Inst. Elect. Trans., Vol. 76, pp. 49 435, Aug 953. [3] [3] C. Concordia and L.. irchmayer, Tie line power and frequency control of electric power system: Part II AISE Trans, IIIA, Vol. 73. pp. 33 46, Apr. 954. [4] [4] L.. irchmayer, Economic Control of interconnected systems New York: Wiley 959. [5] [5] IEEE Trans. Power Apparat System. IEEE Committee ep. Vol. PAS 86, pp. 384 395, 966. [6] [6] M. Leum, The development and field experience of a transistor electric governor for hydro turbines, IEEE Trans. Power App Syste; Vol. PAS 85, pp. 393 40, 966. [7] [7] F. Schleif and A. B. Wilbor, The coordination of hydraulic turbine governors for power system operation, IEEE trans. Power App. Syst; Vol. PAS 85, pp. 750 758, July 966. [8] [8] C.W. oss, A comprehensive direct digital load frequency controller, in proc. IEEE, PICA conf., Pittsburgh, PA, 967, pp 3 38. [9] [9] D.G. amney and J.W. Skoogund, Detailed hydro governor representation for system stability studies IEEE trans. Power Apparat Syst., Vol. PAS 85, pp. 750 758, July 966. [0] [0] O. I. Elgard and C. E. Fosha, Optimum megawattfrequency control of multiarea electric energy systems, IEEE trans. Power Apparat Syst., Vol. PAS 89, pp. 556 563, April 970. [] [] O. I. Elgard, Electric Energy Systems Theory. New York: Mc GrawHill, 97, pp 35 389. [] [] E.C. Thacker, TW eddoch, OT Pan and T. D. Linton, Automatic generation control of electric energy system A simulation study, IEEE Trans. Syst. Man Cybern., Vol. SMC 3, no.4, pp. 403 5, Jul. 973. [3] [3] J. Nanda and B. L.aul, Automatic generation control of an interconnected power system, Proc. Inst. Elect. Eng., Vol. 5, no 5, pp. 385 439, May 978. [4] [4] M.L. othari, B.L.aul, and J. Nanda, Automatic generation control of hydrothermal system, J. Inst. Elect. Eng India., pt. EL, Vol.6, pp.85 9, Oct. 980. [5] [5] J. Nanda, M.L. othari, and P. S. Satsangi, Automatic generation control of an interconnected hydrothermal system in continuous and discrete modes considering generation rate constraints, Proc. Inst. Elect. Eng; pt. D; Vol. 30, no, pp. 7 7, Jan 983. [6] [6] M.L. othari, J. Nanda, and P. S. Satsangi, Automatic generation control of hydrothermal system considering generation rate constraints, J. Inst. Eng. India Vol. 63, no, pp. 89 97, Jun 983. [7] [7] S.C. Tripathy, T.S. Bhatti, C. S. Jha, O. P. Malik, Microprocessor based adaptive load frequency control of Hungarian power system, IEEE Trans. Power App. Syst., Vol. PAS.03, no 5, pp. 045 05, May, 984. [8] [8] J. anniah, S. C Tripathi, and O. P. Malik, Microprocessor based adaptive load frequency control, Proc. Inst. Elect. Eng. C; Vol. 3, no 4, pp. 8, 984. [9] [9] I. Vajk, M. Vajta and L. eviczky, Adaptive load frequency control of Hungarian power system, Automatica, Vol., no., pp. 9 37, 985. [0] [0] L. Hari, M.L. othari, and J. Nanda, Optimum selection of speed regularization parameter for automatic generation control in discrete mode considering generation rate constraint, Proc. Inst. Elect. Eng., Vol. 38, no 5, pp. 40 406, Sep. 99. IJSE 0