Bauart gepruft Sicherheit egelma ge od o s be wac g Mean Well www. tuv.com ID 00000000
SPECIFICATION MODEL RSP-00-12 RSP-00-24 RSP-00-48 DC OLTAGE 12 24 48 RATED CURRENT A A 42A CURRENT RANGE 0 ~ A 0 ~ A 0 ~ 42A RATED POWER 10W 19W 16W RIPPLE NOISE (max.) Note.2 150mp-p 0mp-p 300mp-p OUTPUT OLTAGE ADJ. RANGE 10.5 ~ 14 21 ~ 28 42 ~ 56 OLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0% LINE REGULATION ±1.0% ±0.5% ±0.5% REGULATION SETUP, RISE TIME ±1.0% 1500ms, ms/230ac at full load ±0.5% ±0.5% HOLD UP TIME (Typ.) 16ms/230AC at 75% load 10ms/230AC at full load OLTAGE RANGE Note.5 90 ~ 264AC 127 ~ 370DC FREQUENCY RANGE 47 ~ 63Hz INPUT POWER FACTOR (Typ.) EFFICIENCY (Typ.) 0.97/230AC at full load 87% 90.5% 92% AC CURRENT (Typ.) Note.5 13A/115AC 7A/230AC 16A/115AC 10A/230AC 16A/115AC 10A/230AC INRUSH CURRENT (Typ.) LEAKAGE CURRENT COLD START 50A <2mA / 2AC 105 ~ 125% rated output power OER Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover PROTECTION 14.7 ~ 17.5 29.5 ~ 35 57.6 ~ 67.2 OER OLTAGE Protection type : Shut down o/p voltage, re-power on to recover OER TEMPERATURE Shut down o/p voltage, recovers automatically after temperature goes down OUTPUT OLTAGE PROGRAMMABLE(P) Adjustment of output voltage is allowable to ~ 115% of nominal output voltage. Please refer to the Function Manual. CURRENT SHARING Up to 00W or (3+1) units. Please refer to the Function Manual. FUNCTION AUXILIARY POWER 5 @ 0.3A, 12 @ 0.8A REMOTE ON-OFF By electrical signal or dry contact Power ON:open Power OFF:short. Please refer to the Function Manual. REMOTE SENSE Compensate voltage drop on the load wiring up to 0.5. Please refer to the Function Manual. DC OK SIGNAL The isolated TTL signal out. Please refer to the Function Manual. ENIRONMENT WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY -35 ~ +70 (Refer to "Derating Curve") ~ 90% RH non-condensing - ~ +85, 10 ~ 95% RH TEMP. COEFFICIENT IBRATION ± 0.03%/ (0 ~ 50 ) 10 ~ 500Hz, 2G 10min./1cycle, min. each along X, Y, Z axes SAFETY STANDARDS UL950-1, TU EN950-1 approved WITHSTAND OLTAGE I/P-O/P:3KAC I/P-FG:2KAC O/P-FG:0.5KAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:M Ohms / 500DC / 25 / 70% RH Parameter Standard Test Level / Note SAFETY EMC (Note 4) OTHERS NOTE EMC EMISSION EMC IMMUNITY Conducted Radiated Harmonic Current oltage Flicker EN55024, EN614-3, EN-6-2 Parameter ESD Radiated EFT / Burst Surge Conducted Magnetic Field oltage Dips and Interruptions EN55022 (CISPR22) / EN55011 (CISPR11) Class A EN55022 (CISPR22) / EN55011 (CISPR11) Class A EN-3-2 ----- EN-3-3 ----- Standard EN-4-2 EN-4-3 EN-4-4 EN-4-5 EN-4-6 EN-4-8 EN-4-11 Test Level / Note, 8K air ; Level 2, 4K contact Level 4, 2K/Line-Line 4K/Line-Earth Level 4 >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods MTBF 159K hrs min. Telcordia SR-332 (Bellcore) ; 46.3K hrs min. MIL-HDBK-217F (25 )7F (25 ) DIMENSION 295*127*41mm (L*W*H) PACKING 1.95Kg; 6pcs/12.7Kg/1.15CUFT
Block Diagram PFC fosc : 110KHz PWM fosc : 90KHz +S I/P EMI ACTIE INRUSH CURRENT LIMITING PFC POWER SWITCHING ORING FET + - PFC PWM O..P. DETECTION CIRCUIT ORING FET -S P TRANSCEIERS DA/DB DETECTION CIRCUIT MCU O.T.P. AUX POWER FAN MCU 12/0.8A AUX POWER 5/0.3A DATA ISOLATION T-Alarm DC-OK Remote ON-OFF Static Characteristics INPUT MODEL 12 24 48 (%) 90 75 12 70 65 24,48 50 90 115 1 264 1~264AC 115AC AC 90AC 10W A 10W 90A 10W 85A 9W A 19W A 1632W 68A 14W A 1248W 52A 16W 42A 1713.6W 35.7A 1512W 31.5A 1310.4W 27.3A INPUT OLTAGE (AC) Hz Derating Curve Efficiency vs Load (48 Model) 94 92 (%) for 1~264AC 50 EFFICIENCY (%) 90 88 86 84 82-35 -25-10 0 15 30 50 70 AMBIENT TEMPERATURE ( ) (HORIZONTAL) 10 30 50 70 90 The curve above is measured at 230AC.
00W Power Supply with Single Output Mean Well RSP-00 series Function Manual 1. Remote Sense The Remote Sense compensates voltage drop on the load wiring up to 0.5 PIN2 -S PIN1 +S + - - + CN501 Sense lines should be twisted in pairs to minimize noise pick-up. The +S signal should be connected to the positive terminal of the load whereas -S signal to the negative terminal. 2. Output oltage Programming (or, P / remote voltage programming / remote adjust / margin programming / dynamic voltage trim) In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to ~115% of the nominal voltage by applying EXTERNAL OLTAGE. PIN2 -S PIN1 +S PIN3 P - + CN501 PIN4 GND EXTERNAL OLTAGE (DC) +S +, -S - also need to be connected on CN501. out OUTPUT OLTAGE(%) 115 30 0 0.4 for 12 model for 24,48 model Non-Linear 1 2 3 4 4.7 5 OUTPUT CURRENT (%) 87 115 OUTPUT OLTAGE (%) EXTERNAL OLTAGE (DC) The rated current should change with the Output oltage Programming accordingly. 3. Remote ON-OFF Control The power supply can be turned ON/OFF individually or along with other units by using the "Remote ON-OFF" function. PIN7 Remote ON-OFF switch PIN11 +5-AUX Between Remote ON-OFF and +5-AUX Switch Open Switch Short Power Supply Status ON OFF - + CN501
4.Current Sharing with Remote Sense RSP-00 has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below : The power supplies should be paralleled using short and large diameter wiring and then connected to the load. Difference of output voltages among parallel units should be less than 0.2. The total output current must not exceed the value determined by the following equation: Maximum output current at parallel operation=(rated current per unit) (Number of unit) 0.9 Under parallel operation, the minimum output load should be greater than 5% of total output load; otherwise, it is likely that only one unit operates whereas other units may enter standby mode or their LED status indicators may not turn on. When the total output current is less than 5% of the total rated current, or say (5% of Rated current per unit) (Number of unit) the current shared among units may not be fully balanced. CN502/CN504 Function pin connection PSU1 PSU2 PSU3 PSU4 Parallel CN502 CN504 CN502 CN504 CN502 CN504 CN502 CN504 1 unit X 2 unit 3 unit 4 unit X X X is CN502/CN504 connected to plug pin, X is CN502/CN504 not connected to plug pin. RSP-00 RSP-00 RSP-00 RSP-00 PSU1 PSU2 PSU3 PSU4 - + CN504 TB1 - + CN504 TB1 - + CN504 TB1 - + CN504 TB1 1 5 1 5 1 5 1 5 2 6 2 6 2 6 2 6 CN502 CN502 CN502 CN502 - + Fig 4.1 1 3 5 1 3 5 1 3 5 1 3 5 DA DB GND DA DB GND DA DB GND DA DB GND DA DB GND DA DB GND DA DB GND DA DB GND 2 4 6 2 4 6 2 4 6 2 4 6 PSU1 CN502 PSU2 CN502 PSU3 CN502 PSU4 CN502 If the lines of CN502 are too long, they should be twisted in pairs to avoid the noise. DA,DB and GND are connected mutually in parallel.