Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities 3000 V AC high-pot test Generates up to 800 A (option: 2000-3000 - 4000 A) Microhmmeter function (option): up to 400 A DC Large graphic display Test results and settings are saved in the local memory RS232 interface for PC connection Compact and lightweight T 2000 is a unique solution for all testing operations during commissioning and maintenance of substations, as it allows to perform the test of over-current relays, current and voltage transformers. In addition, T 2000 incorporates a powerful multimeter and phase angle meter, and oscilloscope functions. The following table lists the tests that can be performed on Current Transformers (CT) and Voltage Transformers (VT), Power Transformer (PT), Ground Grid. N. TEST TEST DESCRIPTION 1 CT Ratio, Voltage mode 2 CT Ratio, polarity and burden, Current mode 3 CT Burden; secondary side 4 CT Excitation curve 5 CT Winding or burden resistance 6 CT Voltage withstand 7 CT Polarity by impulses 8 VT Ratio; polarity 9 VT Burden, secondary side 10 VT Ratio, electronic transformers 11 VT Voltage withstand 12 VT Secondary over-current protection 13 PT Ratio per TAP 14 PT Static and dynamic TAP Changer resistance test 15 GR Earth resistance 16 GR Soil resistivity RELAY TYPE IEEE NO Thermal 26 Over/under-voltage 27/59 Under current 37 Instantaneous overcurrent 50 Ground fault 50N Timed overcurrent 51 Circuit breaker 52 Differential (pick-up) 87 Tripping relay 94 OTHER DEVICES Timers Transducers Energy meters
Transformer test set CURRENT TRANSFORMER TESTS CT RATIO AND POLARITY - VOLTAGE METHOD OUTPUT: 90V, 250V or 3000 V AC. MEASUREMENT: 10 V AC. CT RATIO, POLARITY AND BURDEN CURRENT METHOD OUTPUT: 800 A AC. MEASUREMENTS:10 A AC, 10 V AC. CT BURDEN SECONDARY SIDE: OUTPUT: 10 A or 40 A AC. MEASUREMENT: 10 V AC. CT EXCITATION CURVE OUTPUT: 90V, 250V or 3000 V AC. Internal measurement.
WINDING RESISTANCE OUTPUT: 6 A DC. MEASUREMENT: 10 V DC. VOLTAGE WITHSTAND OUTPUT: 3000 V AC. Internal measurement. VOLTAGE TRANSFORMER TESTS VT RATIO AND POLARITY OUTPUT: 3000 V AC. MEASUREMENT: LOW or HIGH AC VOLTAGE - 10 V AC OR 600 V AC. VT BURDEN OUTPUT: 10 A AC. MEASUREMENT: LOW or HIGH AC VOLTAGE - 10 V AC OR 600 V AC. VOLTAGE WITHSTAND OUTPUT: 3000 V AC. Internal measurement.
Transformer test set RATIO OF ELECTRONIC VOLTAGE TRANSFORMERS OUTPUT: 3000 V AC. MEASUREMENT: 10 V AC. POWER TRANSFORMER TESTS RATIO PER TAP OUTPUT: 3000 V AC. MEASUREMENT: LOW or HIGH AC VOLTAGE - 10 V AC OR 600 V AC. STATIC AND DYNAMIC TAP CHANGER RESISTANCE TEST OUTPUT: 6 A DC. MEASUREMENT: 10 V DC. PROTECTIVE RELAY TESTS PRIMARY INJECTION OUTPUT: 800 A. INPUT: TIMER. SECONDARY INJECTION OUTPUT: 800 A, 40 A or 10 A. INPUT: TIMER.
T 2000 includes a multiple generator, with six outputs: High AC current; Low AC current; Low DC current; Current impulses; High AC voltage; Low AC voltage. The selected output is adjustable and metered on the large, graphic LCD display. With the multi-purpose control knob and the graphic LCD display it is possible to enter the MENU mode, that allows to control all functions, and makes T 2000 the most powerful testing device, with manual and automatic testing capabilities, and with the possibility to transfer test results to a PC via the RS232 interface. These results can be recorded, displayed and analysed by the powerful TDMS software, which operates with all WINDOWS versions, starting from WINDOWS 98 included. Note: WINDOWS is a trademark of MICROSOFT inc. Additional features are:. Oscilloscope function: it is possible to display the current and voltage waveform measured;. Two independent measurement inputs, for current and voltage, and with High and Low inputs each, allow measuring CT or VT outputs or any other source;. The optional thermal printer gives the immediate printout of the CT saturation curve and other test results; The instrument is housed in a transportable aluminium box, which is provided with removable cover and handles for ease of transportation. The generator has six outputs: High AC current; Low AC current; Low DC current; Current impulses; High AC voltage; Low AC voltage. Output adjustment is performed via a knob. The following specification applies to the separate usage of these outputs. High AC current output APPLICATION:. CT TESTING: RATIO, POLARITY, BURDEN. PRIMARY INJECTION. RELAY TESTING: ELECTRO-MECHANICAL (HIGH POWER) AND NUMERIC (LOW POWER) CURRENT OUTPUT LOAD RECOVERY OUTPUT POWER TIME TIME A VA s min 100 600 steady - 150 800 15 min 30 200 1000 4 min 15 400 1600 15 5 600 2000 5 3 800 2000 1 2 Low AC current output APPLICATION:. CT TESTING: BURDEN, SECONDARY SIDE. VT TESTING: OVERCURRENT PROTECTION. OVER-CURRENT RELAY TESTING HIGH POWER RANGE RANGE CURRENT OUTPUT MAX RECOVERY A OUTPUT POWER TEST TIME AC A VA DURATION s min 40 12 300 steady - 18 15 min 30 24 4 min 15 36 800 15 5 48 5 3 60 1000 1 2 10 5 400 steady - 7.5 15 min 30 10 800 60 15 15 30 10 20 1000 15 5 LOW POWER RANGE RANGE CURRENT OUTPUT MAX RECOVERY A OUTPUT POWER TEST TIME AC A VA DURATION s min 40 12 60 steady - 17 10 min 30 23 60 10 36 1 2 10 5 60 steady - 6 10 min 45 7 60 2 10 1.5 2
Transformer test set Low DC current output APPLICATION:. CT TESTING: WINDING RESISTANCE, BURDEN RESISTANCE. PT TESTING: TAP-CHANGER CONTACT RESISTANCE CURRENT LOAD OUTPUT MAX TEST OUTPUT RESISTANCE POWER DURATION A Ohm VA min 6 0 0 steady 3 2 18 steady 1 8 8 steady Current impulses output APPLICATION:. CT TESTING: POLARITY TEST WITH IMPULSE METHOD - Current range: from 0 to 10 A peak. High AC voltage output Two version are available: 3000V or 1200V output. APPLICATION:. CT TESTING: EXCITATION CURVE, VOLTAGE WITHSTAND. VT TESTING: RATIO, POLARITY, ELECTRONIC VOLTAGE TRANSFORMER. PT TESTING: RATIO PER TAP 3000 V version. APPLICATION: 1A CT S VOLTAGE CURRENT OUTPUT MAX TEST OUTPUT OUTPUT POWER DURATION V A VA min 3000 0.2 600 steady 2500 0.6 1500 1 Low AC voltage output APPLICATION:. CT TESTING: RATIO WITH VOLTAGE METHOD, SATURATION CURVE VOLTAGE CURRENT OUTPUT MAX TEST OUTPUT OUTPUT POWER DURATION V A VA min 250 0.5 125 steady 220 1.15 250 3 Timer Available measurements: Timer start: at test start, or by an external contact; Metering of elapsed time between START and STOP; Current generation elapsed time. Time can be metered as seconds or cycles.. Inputs: free of voltage or with voltage.. Programmable voltage threshold: 24 V or 80 V.. Metering range, in seconds: from 0 to 9.999 s; 10.00 to 99.99 s; 100.0 to 999.9 s; 1000 to 9999 s.. Metering range, in cycles: from 0 to 1000.0 cycles; from 1000 to 500,000 cycles Counting mode: this mode is foreseen for the test of energy meters. Maximum input frequency: 10 khz. Auxiliary binary Output Contact range: 5 A; 250 V AC; 120 V DC. Measuring Section Output measurements Current and voltage AC and DC outputs measurement accuracy: ± 0.5%. 1200 V version. APPLICATION: 5A CT S VOLTAGE CURRENT OUTPUT MAX TEST OUTPUT OUTPUT POWER DURATION V A VA min 1200 0.5 600 steady 1200 1.5 1800 1
The following measurement are calculated from T 2000 generated outputs: Ratio Measurement Accuracy Ratio: 0.1 to 9999; 0.5% typical; 1% max error. OUTPUT MEASUREMENTS: ACTIVE POWER REACTIVE POWER APPARENT POWER POWER FACTOR IMPEDANCE ACTIVE IMPED. COMPONENT REACTIVE IMPEDANCE COMP. RATIO POLARITY BURDEN SATURATION KNEE P Q S p.f. Z and phase R X CT or VT or PT CT or VT or PT CT CT Resistance Up to 250 Ohm; 0.5% typical; 1% max error. Oscilloscope Function T 2000 has an additional oscilloscope function, that allows to display current and voltage waveforms. Phase angle measurement accuracy: 1. Frequency accuracy: 1 mhz. External Inputs Measurement Current measurements. Two inputs: 20 ma AC or DC or 10 A AC.. Accuracy: 0.5% Voltage measurement. Two inputs: 10 V or 600 V, AC or DC.. Accuracy: 0.5% Other measurements available on the T 2000, calculated from external inputs. EXTERNAL INPUTS MEASUREMENTS: ACTIVE POWER P REACTIVE POWER Q APPARENT POWER S POWER FACTOR p.f. IMPEDANCE Z and phase ACTIVE IMPEDANCE COMP. R REACTIVE IMPEDANCE COMP. X FREQUENCY f PHASE ANGLE IEXT to V AUX PHASE ANGLE VEXT to V AUX RESISTANCE R Graphic Display The large graphic display has the following characteristics: Pixels: 240x128; backlight colour: white; LCD type: FSTN; View area: 135x80 mm. Local Memory Test results can be stored in the T 2000 local memory (up to 500 results may be stored). At the end of test, settings and test results can be transmitted to a PC provided with TDMS. The software allows saving test results and examining them. Test settings can be stored and recalled from the memory. Up to 10 settings can be stored and recalled. TDMS Software When the PC is connected, settings can be created and transferred into T 2000 using TDMS. TDMS is a user friendly software that allows, via a graphical interface, to control the set-up of T 2000 and to download test results. TDMS is also a powerful report editor that allows to create professional test reports that can be exported in Access format.
Transformer test set - N. 1 Grounding cable, 8 m long, terminated on one side with a 4 mm banana plug, and on the other side with an earth connection clamp. - N. 4 Crocodiles for measurements connections (2 red, 2 black). - N. 4 Measurement inputs cables (4 cables: 2 red and 2 black), 2 m long, terminated on both sides with a 4 mm banana plug. - N. 1 Connection cables transport case. Software TDMS - CT test Other characteristics. Interface: serial RS232; baud rate 57600 baud. Mains supply: 230 V ± 10%; 50-60 Hz, or 110 V ± 10%; 50-60 Hz; to be specified at order. (There are power reductions for mains voltage below 220V).. Dimensions: 455 (W) x 325 (D) x 290 (H) mm.. Weight: 31 kg. The instrument comes complete with the following items:. User s manual;. Spare fuses (no. 5), T16A;. Software TDMS with user manual.. Set of connection cables, included in a suitable transport case with wheels and handle. Thermal printer Optional thermal printer, for the printout of the V-I curve in the CT saturation test and other test results. Thermal Paper 112 mm wide. Transit case Heavy duty aluminium transit case with wheels; it allows delivering T 2000 with no concern about transport shocks. Heavy duty transport case in black plastics is also available. Connection cable and test connectors T 2000 is always supplied with a complete kit of testing cables: - N. 2 High current connection cables, 100 sq. mm, 4 m long, for tests up to 800 A. Terminated on both sides with an high current connector (M+F). - N. 2 High current connection cables, 100 sq. mm, 0.5 m long, for tests up to 800 A. Terminated on one side with an high current connector (M) and on the other side with an high current clamp. - N. 2 High voltage connection cables, 4 m long, 5 kv, with earth screen. Terminated on one side with an HV connector, and on the other side with a safety banana plug. - N. 2 Low current connection cables, 2.5 sq. mm, 10 m long. Terminated on both side with 4 mm banana plugs. - N. 4 Clamps to connect low voltage or low current or measurements. - N. 1 Cable for low voltage measurement connection, shielded, 10 m long. Terminated on one side with the measurement connector, and on the other side with two measurement clamps. - N. 1 Cable for the 600 V measurement connection, shielded, 10 m long. Terminated on one side with three 4 mm banana plugs and on the other side with two clamps. Aluminium transport case Plastics transport case Current clamp The current clamp allows to avoid opening the secondary current circuit when performing the primary test of CT burden.
High IDC Module - 400 A The high DC current module allows the measurement of the low contact resistance of high voltage breakers or of joints. The option is connected to the high AC current output of T 2000; the current measurement is connected to the low DC current measurement input; the drop voltage is connected to the low voltage measurement input. DC current output is: 100 A steady; 200 A for 4 minutes; 400 A for 15 s. The selection of this function is performed via menu; the screen displays: test current; joint voltage; contact resistance. Resistance measurement ranges: 100.0 µohm; 1.000, 10.00, 100.0 mohm; 1.000 Ohm, auto-ranging. Connection cables are included with the option. The test set conforms to the EEC directives regarding Electromagnetic Compatibility and Low Voltage instruments. A) Electromagnetic Compatibility: Directive no. 2004/108/EC. Applicable Standard : EN61326-1 + A1 + A2. B) Low Voltage Directive: Directive n. 2006/95/EC. Applicable standards, for a class I instrument, pollution degree 2, Installation category II:. CEI EN 61010-1. In particular:. Inputs/outputs protection: IP 2X - IEC 60529; 4X for the HV output.. Operating temperature: 0 to 50 C; storage: -20 C to 70 C.. Relative humidity: 5-95% without condensing. FT 1000 current filter It is connected in series to the current output and guarantees a sinusoidal waveform also when testing current relays with heavily saturating burdens, that tend to distort the current waveform. Earth resistance and resistivity test kit The test of earth resistance and resistivity is included in T 2000 as a standard feature. The option is referred to the kit of connection cables and auxiliary spikes that allows executing these tests. T 2000E This model allows performing high current tests with more power. It is based upon the 1200 V high voltage generator. The corresponding changes to the high current output are the following. Weight: 37 Kg. CURRENT MAX MAX OFF A POWER ON TIME TIME VA s min 100 850 CONT. - 150 1200 15 min 30 200 1550 4 min 15 300 2050 15 5 400 2400 15 5 600 2600 5 3 800 2100 1 2 CODE MODULE 10110 T 2000-3000 V OUTPUT - 230 V complete with TDMS software and test cable kit 20110 T 2000-3000 V OUTPUT - 115 V complete with TDMS software and test cable kit 30110 T 2000-1200 V OUTPUT - 230 V complete with TDMS software and test cable kit 40110 T 2000-1200 V OUTPUT - 115 V complete with TDMS software and test cable kit 50110 T 2000 E - 1200 V OUTPUT - 230 V complete with TDMS software and test cable kit 17102 Aluminium transport case 24102 Plastics transport case 16102 Current Clamp 1/1000 Max 100A 14102 Thermal Printer 112 mm 13102 High I DC module 400 A 26102 SU 3000 Safety device for the line impedance measurement 19102 Earth Resistance and Soil Resistivity Kit 16093 FT 1000
High Current Booster The current output of T 2000 can be increased to up to 2000 A with a new type of optional booster controlled by the T 2000 control unit. The BU 2000 option is an innovative design concept that allows to avoid the power losses due to long cables connections. To achieve this, the BU 2000 transformer is placed very close to the device under test (CT primary side, Circuit Breaker main contacts), thus avoiding losses on the high current cables. The BU 2000 is then connected with a long (20 m) low current cable to T 2000 unit. The option can use one, two or four transformers, as a function of the maximum test current and/or the test duration (see table below). In case of 2 to 4 BU 2000 units, an Interposing Module is necessary. Number of Weight Number Maximum MAX ON transformers of turns current Kg A s 1 MAIN 19.5 3 1000 100 3 2000 6 1 MAIN + 29.5 2 1000 900 1 AUX + 2 2000 27 Interposing 2 3000 6 1 MAIN + 49.5 2 1000 900 3 AUX + 2 2000 27 Interposing 2 3000 6 2 4000 2 1 1000 INFINITE 1 2000 900 1 3000 100 BU 2000 Main Module - Supply voltage: 230 V. - Voltage output (one turn): 0,91 V. - Steady power: 1000 VA. - Weight: 11 kg. - Dimensions: external diameter 190 mm; height 120 mm. - Connection of the transformer: by a cable, 20 m long, terminated with connectors on both sides. - Output current metering: by a current transformer with ratio 1000//1. Accuracy class: 0.5%. - Connection of the CT: by a cable, 20 m long, that includes a shunt, rated 0.1 Ohm, 25 W, accuracy 0.1%. The cable is terminated with a connector for the connection to the 10 V input of T 2000. BU 2000 Auxiliary Module - Supply voltage: 230 V. - Voltage output (one turn): 0,89 V. - Steady power: 1000 VA. - Weight: 10 kg. - Dimensions: external diameter 190 mm; height 120 mm. The option is also provided with two high current screw-driven clamps for the connection to high bars and with four high current clamps for the connection to bars located into narrow places. BU 2000 Auxiliary Module
BU 2000 Interposing Module - Mains connection: by a 64 A rated connector, provided. - Power-on: by means of a circuit breaker rated 63 A. - Coarse current adjustment: by means of a four-position selector switch. - Connections to T 2000: power supply cord; Variable voltage output; auxiliary contact, timer START input. - Capable to drive up to four transformers. - Weight: 5 kg. - Dimensions: 33 x 30 x 20 cm (WHD). NOTE: in case of one transformer, the BU 2000 INTERPOSING MODULE is not necessary. Auxiliary Module High current cable Connecting cable CODE MODULE Interposing Module 50102 BU 2000 - External Advanced Booster up to 2000 A : (1) Main Module with high current clamps and high current cables, connecting cables. 51102 BU 2000 - External Advanced Booster up to 3000 A : Main Module with high current clamps, high current cables, Auxiliary Module (1), Interposing Module, connecting cables. 52102 BU 2000 - External Advanced Booster up to 4000 A : Main Module with high current clamps, high current cables, Auxiliary Modules (3), Interposing Module, connecting cables. 53102 BU 2000 - Interposing Module 54102 BU 2000 - Auxiliary Module 55102 Heavy Duty plastic transport case for BU 2000 (50102) 56102 Heavy Duty plastic transport case for BU 2000 (51102; 52102) The document is subject to change without notice. Always refer to our technical specification for more detailed information and as formal contract document.