The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms

Similar documents
Regional Technical Seminar

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

Transformer Protection

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Tap Changer Analyzer & Winding Ohmmeter RMO25TD

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Back to the Basics Current Transformer (CT) Testing

Welding Transformer: Principle, Requirement and Types

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Regional Technical Seminar TAP CHANGERS

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer

Tap Changer Condition Assessment Using Dynamic Resistance Measurement

Impact of Distributed Generation on Network Voltage Levels

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Type KLF Generator Field Protection-Loss of Field Relay

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Three-Phase Transformer Demagnetizer DEM60

FERRORESONANCE SIMULATION STUDIES USING EMTP

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Problems connected with Commissioning of Power Transformers

Dynamic Testing for On Load Tap Changer Condition Assessment

Load Tap Changers for Power Transformers

COPYRIGHTED MATERIAL. Index

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

Phase Shifting Transformers. Presented by

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Unit Protection Differential Relays

Earth Fault Protection

DIAGNOSIS. TRANSFORMERS MAGAZINE Volume 3, Issue 2

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Demagnetization of Power Transformers Following a DC Resistance Testing

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Transformer Protection Principles

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Topics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control

Transformer energisation after network blackout

Tab 2 Voltage Stresses Switching Transients

Winding Ohmmeter RMO-TW

Testing Numerical Transformer Differential Relays

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

Transformer Fault Categories

Three-Phase Winding Ohmmeter TWA25K

SCOPE TRM 25 TRM 25+ Transformer Winding Resistance Meter. The most advanced Transformer Winding Resistance Meter injects up to 25A DC...

Curve accuracy (enough data points to be statistically significant): See Attachment B.

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Importance of Transformer Demagnetization

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

TWA Series Three-Phase Winding Ohmmeters & Tap Changer & Winding Analyzers

Hands-On Transformer Testing and Maintenance

Simultaneous AC-DC Transmission Scheme Under Unbalanced Load Condition

Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Electrical Theory 2 Lessons for Fall Semester:

Tap Changer Analyzer & Winding Ohmmeter RMO60TT

Electrical Machines I : Transformers

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Preface...x Chapter 1 Electrical Fundamentals

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

Winding Ohmmeter & Tap Changer Test Set RMO10TW

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Beyond the Knee Point: A Practical Guide to CT Saturation

HIGH-VOLTAGE EQUIPMENT. Read this entire manual before operating.

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

INTERNATIONAL STANDARD

Guidelines to Using a Three Phase Voltage Monitor

Tap Changer Analyzer & Winding Ohmmeter RMO-TD Series

R438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE

Ordering Information. Latching Relay MMK. Available Models. Models Conforming to Auxiliary Power Relay Specifications

Transformer Technology Seminar Winding Selection

ISSN: Page 298

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Tap Changer Analyzer & Winding Ohmmeter RMO-TT

R448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A

2 PDT Coil supply. Contacts rated at. Contact rating per pole and load type. Load Current in 100,000 cycles 100,000 cycles

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Long lasting transients in power filter circuits

Power Measurements and Basic Electrical Diagnostic Tests

Power Transformers Basics

Low voltage circuit breakers

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

Reactor-type tap changers testing. Dynamic resistance measurement for on load tap changers

Substation Test Equipment Guidebook

Transformer Protection

Reyrolle Protection Devices. 7PG11-18 Alpha Electromechanical Relays. Siemens. Answers for energy.

148 Electric Machines

Tap Changer Analyzer & Winding Ohmmeter RMO-TT

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

Phase Shifter Application Workshop. Siemens Energy, Inc.

TECHNICAL BULLETIN 004a Ferroresonance

The Engineering Problem. Calculating GIC Flow through the EHV System

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

www. ElectricalPartManuals. com Type CGR Ratio Ground Relay Descriptive Bulletin Page 1

7SG14 Duobias-M Transformer Protection

Transcription:

Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited turns Loose connections improper crimping Broken strands Poor efficiency - I 2 R component of conductor losses Measurement of winding temperature Calculate the winding temperature at the end of a heat run Principle of Measurement To remove the effect of inductance (L), the change in current needs to be zero. There are two requirements to achieve this: Transformer core saturation, Ø = E * t (seconds) Current must be stable Megger, Valley Forge,, SA P1

The larger the winding (inductance), the greater the difficulty in achieving current stabilization. (On) Load Tap Changers Reactive Type The reactive LTC utilizes a reactor or preventive autotransformer to limit the circulating current when in the bridging position. They can be designed to operate at high speeds (0.3-0.7 seconds) or at relatively slow speeds (1-3 seconds). Resistive Type Figure 1: Graph of Reactive LTC with Preventive Auto The resistive LTC utilizes transition resistors to limit the circulating current during a tap change. The bridging position is NOT a normal stopping tap position for a resistive LTC. Resistive types are typically designed to arc either at the selector switch or the transfer (diverter) switch and operate at higher speeds (0.3-0.7 seconds). Megger, Valley Forge,, SA P2

Figure 2: Graph of a Resistive Type LTC with Reversing Switch Detecting Break Before Make (BBM) Condition nder BBM conditions, current in the circuit drops and is monitored. If the current drops to a threshold value (10%) for a defined time, duration is used to detect BBM condition. Depending upon the age, number of operations, and type of LTC, one can select the sensitivity for BBM criteria. Open Circuit Voltage Open circuit voltage from the test set defines the time required for voltage to be applied to generate enough magnetic flux to saturate the transformer core. ɸ = volts x seconds (E*t) The time needed would also be dependent upon number of windings being tested simultaneously and prior level of core magnetization. This is contrary to a common belief that current saturates the core. Current magnitude does help to stabilize low resistance windings with high rated currents (>1000A). Megger, Valley Forge,, SA P3

Principal relationship between applied voltage, resistance and core saturation Selecting Test Current Range One should always try to inject above 1% of rated current, but do not exceed 15% rating (15% as per IEC/ANSI standards) Typical test currents range from 0.1% - 15% of rated current of winding 0.1% to <1% becomes more difficult to maintain stability When test current is < 1% transformer rated current, measured resistance may not be consistent and/or time for stability may increase to an unreasonable time Applying Large Test Currents Higher test currents can have an adverse effect on the measurements: One can saturate the transformer core to a significant level such that residual flux (magnetization) causes protective relay to trip when re-energizing transformer (if not demagnetized properly) Megger, Valley Forge,, SA P4

When testing high side windings, large test currents may increase the test time unnecessarily High test currents (>15% rated current of winding) will change the winding resistance values over time during testing due to heating Dual Injection Testing It can be an advantage to inject test current in the high voltage and low voltage windings simultaneously. This increases the flux in the core so the core saturates more quickly. This is particularly the case for transformers with a low voltage delta winding where the phase being measured saturates quickly, but the other 2 phases are in parallel and are only slowly saturated with 50% of the voltage. Core demagnetization The transformer core may remain magnetized as a result of DC measurements of winding resistance. This can lead to issues when re-energizing the transformer or when performing frequency response analysis. Today s test equipment has a demagnetization feature. The user can demagnetize the core of the transformer at the completion of the test. Megger, Valley Forge,, SA P5

Summary: WRM is NOT a simple test Not just an Ohm s law test R= V/I. there is a lot more to it V= I*R +L*dI/dt, inductance of the winding Saturation of the core (volts*sec) Transient state before steady state is reached Stabilization of DC current Time constant of the circuit L/R Delta windings Make before break operation of (O)LTC s Return winding to original state - demagnetization Megger, Valley Forge,, SA P6