A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Similar documents
A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Indirect Current Control of LCL Based Shunt Active Power Filter

Power Quality improvement of a three phase four wire system using UPQC

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Chapter 2 Shunt Active Power Filter

Enhancement of Power Quality Using Advanced Series Active Power Filters

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Harmonics Reduction using 4-Leg Shunt Active Power Filters

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Power Quality Improvement using Shunt Passive Filter

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

Exploration in Power Quality Furtherance on Shunt Active Power Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Improvement of Power Quality Using a Hybrid Interline UPQC

A Hysteresis based Active Shunt, Passive Series Hybrid Filter for Power Quality Improvement

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I.

PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Review on Shunt Active Power Filter for Three Phase Four Wire System

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

2020 P a g e. Figure.2: Line diagram of series active power filter.

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Power Quality Improvement using Active shunt Power filter using PI Controller

SPWM Switching Strategy for Compensation of Unbalanced and Non Linear Load Effects in Three Phase Four Wire System Using D-Statcom

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Control Of Shunt Active Filter Based On Instantaneous Power Theory

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

ABSTRACT I. INTRODUCTION

Improving the Power Quality by Four Leg VSI

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

Control of Photovoltaic System with A DC-DC Boost Converter Fed DSTATCOM Using Icos Algorithm

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

CHAPTER 4 DESIGN OF DC LINK VOLTAGE CONTROLLER FOR SHUNT ACTIVE POWER FILTER

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Universal power quality conditioner

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

A New Control Method for Series Active Filter in Distribution System using Unit Vector Control

Enhancement of Power Quality with Multifunctional D-STATCOM Operated under Stiff Source for Induction Motor Applications

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

ISSN Vol.03,Issue.07, August-2015, Pages:

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Compensation of Harmonics Power by using Shunt Active Filter

Dynamic Modeling and Simulation of Unified Power Quality Conditioner

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

POWER QUALITY IMPROVEMENT USING SHUNT ACTIVE FILTER

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Comparison of Three leg and Four Leg VSC DSTATCOM for Power Quality Assessment

HARMONIC contamination, due to the increment of nonlinear

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction

Control of Shunt Active Power Filter for Improvement of Power Quality

Harmonics Elimination Using Shunt Active Filter

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Experimental Verification of Unified Power Quality Conditioner with Transformation Less Combined Mode Control

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Power Control and Quality Management in DG Grid Interfaced Systems

Using dspace in the Shunt Static Compensators Control

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Transcription:

International Journal of Electrical Engineering. ISSN 0974-2158 Volume 6, Number 4 (2013), pp. 473-483 International Research Publication House http://www.irphouse.com A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation P. V. Ram Kumar * and Dr. M. Surya Kalavathi Assoc.Professor, R.S.R Engineering College, Kavali, D.No.27-8- 1000/1, Kinnera Prasad Lay out, Near NTR Nagar Arch, NTR Nagar, Nellore (District), Andhra Pradesh, India (e-mail: ramkumar_pv@yahoo.co.in & purigilla.venkata.ramkumar@gmail.com) Professor in Department of Electrical and Electronics Engineering, J.N.T.U.College of Engg, Hyderabad, INDIA 500085 (e-mail: munagala12@yahoo.co.in). ABSTRACT Power quality issues are becoming a major concern of today's power system engineers. Shunt active power filter (SAPF) is one of the effective means for harmonic current compensation in electrical power system. The performance and dynamic characteristics of a three-phase SAPF with a simple control algorithm is presented and analyzed in this paper. This algorithm operates at fixed switching frequency and compensates the reactive power and the current harmonics of nonlinear loads. Reactive power compensation is achieved without sensing and computing the reactive component of the load current, thus simplifying the control implementation. Current harmonic compensation is done in time domain. The proposed controller is compared with the conventional proportional-integral (PI) controller method on compensating reactive power and harmonic currents of the load. The simulations of these two schemes are carried out in Matlab/Simulink. Keywords: Hysteresis band current control, Power quality improvement, Peak detection and, shunt active power filter. 1.INTRODUCTION Shunt active power filters (SAPF) operate as controlled current sources injecting current harmonic components to the power distribution system, the point of

474 P. V. Ram Kumar and Dr. M. Surya Kalavathi connection must be carefully selected so that generated harmonic components flow to the nonlinear loads and do not propagate through the distribution system [1]. The SAPF can compensate for the harmonics, correct the power factor and work as a reactive power compensator, thus providing enhancement of power quality in the system [2, 3]. The control scheme of a SAPF must calculate the current reference waveform for each phase of the inverter, and generate inverter gating signals. The current reference circuit generates the reference currents required to compensate the load current harmonics and reactive power [4]. In literature [1-14], most reference compensation current strategies of the SAPF are determined either with or without reference-frame transformations. For instance, the theory proposed in [2, 3] requires transformation of both source voltages and load currents from the reference frame to the reference frame to determine the SAPF reference compensation currents in the three-phase three-wire system. For detecting the reference compensating current, the instantaneous active and reactive power theory (p-q theory) are widely used, which can provide an instantaneous and accurate reference compensating current [3, 4]. Grady et al. [5] have presented a survey of active power line conditioning methodologies with a list of the advantages and limitations of each one. Cavallini and Montanari [6] have proposed the unity power factor strategy known as classic strategy in which conditions the line currents to fit the voltage waveform, provides line current RMS values always lower than those obtained by keeping the instantaneous real power equal to its mean value. Chang and Shree [7] have proposed a simple and efficient compensation strategy that is suitable for three-phase shunt active power filters without reference-frame transformation requirement. Bhim Singh and Verma [8] have proposed an indirect current control scheme of parallel hybrid power filter system consists of a shunt passive filter with an active filter in series with it connected at the point of common coupling (PCC) in parallel with nonlinear load. Bhuvaneswari and Nair [9] have proposed an algorithm based on the real component of fundamental load current (I cosφ). Tang et al. [10] have proposed a LCL-filter-based shunt active power filter which gives good switching harmonic suppression and minimizes the possibility of over-modulation. Chandra et al. [11] have presented an improved control algorithm of the SAPF which used two closed loop PI controllers and carrier wave PWM signal generation. Akagi [12] has listed trends in active power line conditioners. Singh et al. [13] have presented a review on classification of active filters for power quality improvement based on converter type, topology and the number of phases. In the generalized instantaneous reactive power theory [3], transformation of a-b-c axes to d q synchronous reference frame is done for harmonic and reactive power compensation. However, the synchronous reference frame (SRF) strategy [4] only computes the sinusoidal fundamental components of the load currents; the reactive power compensation and a null neutral current thus cannot be achieved if the load imbalance at the fundamental frequency occurs. A phase-locked loop (PLL) per each phase must be used. In theory, the aforementioned approaches work very well on harmonic and/or reactive power compensation for nonlinear loads under ideal source voltages. However, if the source voltages are imbalanced and/or distorted, the generated SAPF reference compensation currents are discrepant and the desired

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter 475 balanced/sinusoidal source currents cannot be maintained [7]. Among different PWM methods, hysteresis is one of the most popular PWM strategies [7-9] and widely applied in SAPF for current quality compensation, owing to its advantages such as ease of implementation, fast dynamic response and current limiting capability. To achieve full compensation of both reactive power and harmonic currents of the load, this paper presents a simple method to determine the SAPF reference compensation currents using dc voltage PI controller, source voltages and source currents. This method does not require any reference frame transformations. Hysteresis band current control PWM strategy is used to drive current controlled voltage source inverter (CC-VSI). A MATLAB based simulation is performed on this method and the results are presented to discuss in regard to the harmonic elimination of the SAPF system. 2.Control Scheme of SAPF The block diagram of the control scheme of a shunt active power filter is shown in Fig. 1. The current reference circuit generates the reference currents required to compensate the load current harmonics and reactive power, and also try to maintain constant the dc voltage across the electrolytic capacitors. Also, the compensation effectiveness of an active power filter depends on its ability to follow with a minimum error and time delay, the reference signal calculated to compensate the distorted load current. Finally, the dc voltage control unit must keep the total dc bus voltage constant and equal to a given reference value. The dc voltage control is achieved by adjusting the small amount of real power absorbed by the inverter. This small amount of real power is adjusted by changing the amplitude of the fundamental component of the reference current. 2.1 Generation of Source Currents SAPF is controlled to draw/supply a compensating current from/to the utility, so that it cancels current harmonics on the ac side and makes the source current in phase with the source voltage. From Fig. 1, the instantaneous currents can be written as; i s t = i L t - i c t (1) Source voltage is given by; v s t = V m sinωt (2) If the nonlinear load is applied, then the load current will have a fundamental component and harmonic components, which can be expressed as; i L t = n=1 I n sin nωt + φ n = I 1 sinnωt + φ 1 + n=2 I n sinnωt + φ n (3)

476 P. V. Ram Kumar and Dr. M. Surya Kalavathi a b c s s s i sa i sb i sc Z L, R PCC v sa Z f L f, R f v sb vsc i la i lb i lc i ca i cb i cc C dc V dc i l R L L L Fig. 1. Basic Compensation Principle of Shunt Active Power Filter (SAPF). The instantaneous load power can be given as; p L t = v s t * i L t = V m I s in 2 ω t * c o s φ + V 1 1 m I s in ω t * co s ω t * s in φ 1 1 + V m sin ω t * n= 2 I n sin n ω t + φ n = p f t + p r t + p h t From (4), the real power drawn by the load is p t =V m I si 2 t* cosφ = v s t* i s t (5) f 1 n ω 1 From (5), the current supplied by the source, after compensation is p f t i s t = = I 1 * cosφ 1 * sinωt = I smsinωt Where v s t (4) I sm = I 1 * cosφ 1 There are also some switching losses in the PWM converter and, hence, the utility must supply a small overhead for the capacitor leakage and converter switching losses in addition to the real power of the load. The total peak current supplied by the source (I sp ) is therefore (6) I sp = I sm + I sl

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter 477 Where I sl is the peak value of loss current. If the active filter provides total reactive and harmonic power, then i s (t) will be in phase with the utility voltage and purely sinusoidal. At this time, the active filter must provide the following compensation current: i c t = i L t - i s t (7) 3. Peak detection Method with PI Controller There are many possibilities to determine the reference current required to compensating the non-linear load. Normally, shunt active power filters are used to compensate the displacement power factor and low-frequency current harmonics generated by non-linear loads. One alternative to determine the current reference required by the VSI is the use of the instantaneous reactive power theory, proposed by Akagi [1], the other one is to obtain current components in d q or synchronous reference frame [2], and the third one to force the system line current to follow a perfectly sinusoidal template in phase with the respective phase-to-neutral voltage [3]. There are other possibilities to generate the current reference signal required to compensate reactive power and current harmonics. Basically, all the different schemes try to obtain the current reference signals that include the reactive components required to compensate the displacement power factor and the current harmonics generated by the non-linear load. In this paper, a simple method is used to generate the source reference currents using DC voltage error and load current peak detection. The main characteristic of this method is the direct derivation of the compensating component from the load current, without the use of any reference frame transformation. Fig. 2 shows the scheme used to generate the current reference signals required by a SAPF. 3.1 Design of Current Reference Generator In this case, the ac current generated by the inverter is forced to follow the reference signal obtained from the current reference generator. In this circuit, the distorted load current is filtered, extracting the fundamental component, i l1. The band-pass filter is tuned at the fundamental frequency (50 Hz), so that the gain attenuation introduced in the filter output signal is zero and the phase-shift angle is 180 0. Thus, the filter output current is exactly equal to the fundamental component of the load current but phase shifted by 180 0. If the load current is added to the fundamental current component obtained from the second-order band-pass filter, the reference current waveform required to compensate only harmonic distortion is obtained. In order to provide the reactive power required by the load, the current signal obtained from the second-order band-pass filter I l1 is synchronized with the respective phase to- neutral source voltage so that the inverter ac output current is forced to lead the respective inverter output voltage, thereby generating the required reactive power and absorbing the real power necessary to supply the switching losses and also to maintain the dc voltage constant. The real power absorbed by the inverter is controlled by adjusting the amplitude of the fundamental current reference waveform, I l1, obtained from the reference current generator. The amplitude of this sinusoidal waveform is equal to the amplitude of the

478 P. V. Ram Kumar and Dr. M. Surya Kalavathi fundamental component of the load current plus or minus the error signal obtained from the dc voltage control unit. In this way, the current signal allows the inverter to supply the current harmonic components, the reactive power required by the load, and to absorb the small amount of active power necessary to cover the switching losses and to keep the dc voltage constant. The scheme is necessary for each phase. The expression for i Ma is: I cos (2t ) i 1 Ma = I 1 cos ( )+ 2 (8) I + n cos(n 1)t n cos (n 1)t n n= 2k-1 2 with k = 1, 2, 3,.. Fig.2 Generation of Reference currents required by SAPF The current distortion of the compensated current depends on the phase angle of the fundamental load current component. The supply voltage has no effect on the reference current generation. Synchronization with the ac mains voltage is the important issue in this scheme as well as in the synchronous reference frame theory. Unbalanced loads do not affect the reference generation. Nevertheless, the method cannot achieve active power balance in four-wire systems. The control circuit implementation of the peak detection method is simple and does not require complex calculation, so the processing time on a DSP is lower than the required in the two previous implementations, (T < 10μs). The use of this method minimizes the distortion introduced on current harmonics [14].

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter 479 3.2 Design of DC Link Voltage PI Controller The three phase reference currents (peak value) for the control of active filter are generated in accordance with the PI controller error between the average dc bus voltage V dc (n) and its reference value V dcref (n) of the active filter. The dc bus voltage error V e (n) at n th sampling instant is V e n = V dcref n - V dc n (9) This error signal V e (n) is processed in PI controller and output K (n) at n th sampling instant is expressed as K n = K n -1 + K p V e nv e n-1 K i V e n (10) where K p and K i are the gains of the PI controller. 3.3 Design of Hysteresis Current Controller for PWM Switching The active filter is comprised of three-phase IGBT based current controlled VSI bridge. The upper device and the lower device in one phase leg of VSI are switched in complementary manner. The switching logic for phase-a is formulated as follows: if i sa < (i* sa - h b ), upper switch is OFF and lower switch is ON in the phase a leg then S a = 0. If i sa > (i* sa +h b ) upper switch is ON and lower switch is OFF in the phase a leg then S a = 1. Between the transitions the previous value of switches are maintained. Where, is switching function for switches of phase a and is the width of the hysteresis band around reference currents. Similarly, the switching logic of the other two phases ( b and c ) is formulated. Ideal compensation requires the mains current to be sinusoidal and in phase with the source voltage, irrespective of the load current nature. The source reference currents, after compensation, can be given as * i sa = I sp sinωt * 0 * 0 i sb = I sp sin ωt - 120 i sc = I sp sin ωt +120 (11) where I sp is the amplitude of the desired source current, while the phase angle can be obtained from the source voltages. Hence, the waveform and phases of the source currents are known, and only the magnitudes of the source currents need to be determined. 4.Simulation Results and Discussion Following are the system parameters considered for the study of SAPF with proposed peak detection method for PI controller. V s = 100 V (Peak), f = 50 Hz, R s = 0.1 Ω, L s = 0.15 mh, R f = 0.1 Ω, L f = 0.66 mh, R l = 6.7 Ω, 15 Ω; L l = 20mH, C DC = 2000 µf, V dcref = 220 V. In case of PI the gains chosen are k p = 0.2 and k i = 9.32. Initially,

480 P. V. Ram Kumar and Dr. M. Surya Kalavathi the load chosen is of R l = 6.7 Ω, L l = 20mH and later, a 15 Ω is connected across this R-L combination. The performance results of shunt active power filter with peak detection method are presented in Fig. 3 Comparisons of different controllers are presented in Table I based on % THD. 100 SourceCurrent(A) CompensatingCurrent (A) LoadCurrent(A) SourceVoltage(V) 50 0-50 -100 0.45 0.46 0.47 0.48 0.49 0.5 0.51 0.52 0.53 0.54 0.55 40 20 0-20 Time (s) (a) -40 0.45 0.46 0.47 0.48 0.49 0.5 0.51 0.52 0.53 0.54 0.55 40 20 0-20 Time (s) (b) -40 0.45 0.46 0.47 0.48 0.49 0.5 0.51 0.52 0.53 0.54 0.55 50 0 Time (s) (c) -50 0.46 0.48 0.5 0.52 0.54 0.56 Time (s) (d) (e) Fig. 3. Performance results of shunt active power filter with peak detection method for the load of R l = 15 Ω, and L l = 20 mh

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter 481 (a) Fig. 4. THD % of a) load current, and b) source current with PI controller Fig. 5. THD % of (a) Load curent (b) source current With p-q Theory for Load1 (c) source current for load2

482 P. V. Ram Kumar and Dr. M. Surya Kalavathi Fig. 6. THD % of source current With peak detection method for (a) Load1 (b) Load2 150 100 50 0-50 -100 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 Fig. 7 Power factor correction obtained inphase a with the proposed method. x 10 5 TABLE I: THD % Comparison between Different Controllers % THD at two different loads R l = 6.7 Ω, L l = 20mH 15Ω in parallel with R 1 = 6.7 Ω L l = 20mH Without controller 28.10 27.72 With inst. PQ theory 1.66 2.45 With peak detection method 1.78 2.61 4.Conclusion This paper has presented a simple control method for PI based hysteresis current controlled shunt active power filter for harmonic and reactive power compensation of the non-linear load. This method is implemented to generate source reference currents without reference frame transformation using DC voltage regulator, source voltages and source currents. It gives less complexity in realizing the control circuit of the active power filter and still maintains good filter performance. The scheme has the advantage of simplicity. References: [1] L. T. Morán, J. J. Mahomar, and J. R. Dixon Careful connection- selecting the best point of connection for shunt active power filters in multibus power distribution systems IEEE Industry Applications Magazine, pp. 43-50, Mar- Apr 2004.

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter 483 [2] H. Akagi, Y. Kanzawa, and A. Nabae Instantaneous reactive power compensators comprising switching devices without energy Components IEEE Transactions on Industrial Applications, Vol. 20, No. 3, pp. 625 630, 1984. [3] H. Akagi, E. Watanabe, M. Aredes Instantaneous Power Theory and Applications to Power Conditioning: Wiley- IEEE Press, 2007. [4] M.H. Rashid Power Electronics Handbook: Devices, Circuits, and Application, Elsevier Inc., Section Edition, 2007. [5] W. M. Grady, M. J. Samotyj and A. H. Noyola Survey of Active Power Line Conditioning Methodologies IEEE Transactions on Power Delivery, Vol. 5, No. 3, pp. 1536-1542, July 1990. [6] A. Cavallini and G. C. Montanari Compensation Strategies for Shunt Active- Filter Control IEEE Transactions on Power Electronics, Vol. 9, No. 6, pp. 587-593, November 1994. [7] G. W. Chang, and T. C. Shee A Novel Reference Compensation Current Strategy for Shunt Active Power Filter Control IEEE Transactions on Power Delivery, Vol. 19, No. 4, pp. 1751 1758, October 2004. [8] Bhim Singh, and Vishal Verma An Indirect Current Control of Hybrid Power Filter for Varying Loads IEEE Transactions on Power Delivery, Vol. 21, No. 1, pp. 178-184, January 2006. [9] G. Bhuvaneswari, and Manjula G. Nair Design, Simulation, and Analog Circuit Implementation of a Three-Phase Shunt Active Filter Using the Icos Φ Algorithm IEEE Transactions on Power Delivery, Vol. 23, No. 2, pp. 1222 1235, April 2008. [10] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, Generalized Design of High Performance Shunt Active Power Filter With Output LCL Filter IEEE Transactions on Industrial Electronics, Vol. 59, No. 3, pp. 1443-1452, March 2012. [11] Ambrish Chandra, Bhim Singh, B. N. Singh, and Kamal Al-Haddad, An Improved Control Algorithm of Shunt Active Filter for Voltage Regulation, Harmonic Elimination, Power-Factor Correction, and Balancing of Nonlinear Loads IEEE Transactions on Power Electronics, Vol. 15, No. 3, pp. 495-507, May 2000. [12] H. Akagi, New Trends in Active Filters for Power Conditioning IEEE Transactions on Industry Applications, Vol 32, No 6, pp. 1312-1322, December 1996. [13] Bhim Singh, Kamal Al-Haddad, and Ambrish Chandra A Review of Active Filters for Power Quality Improvement IEEE Transactions on Industrial Electronics, Vol. 46, No. 5, pp. 60 71, October 1999. [14] L. A. Moran, J. W. Dixon, and R. R. Wallace A Three-phase Active Power Filter Operating with Fixed Switching Frequency for Reactive Power and Current Harmonic compensation IEEE Transactions on Industrial Electronics, Vol. 42, No. 4, pp. 402-4-8, August 1995.