Abstract. 1 Introduction

Similar documents
Electrical Power Engineering Group, School of Electronics and Computer Science, University of Southampton, Highfield, Southampton, SO17 1BJ, UK 2

Y. Tian, P. L. Lewin The Tony Davies High Voltage Laboratory University of Southampton Southampton, Hampshire SO17 1BJ, UK

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 11, No. 5; October

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Partial Discharge Patterns in High Voltage Insulation

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

PD Solutions. On-Line PD Measurement Devices

On-line Partial Discharge Analysis of Transmission and Distribution Assets

PARTIAL DISCHARGE MEASUREMENT

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

PD Diagnostic Applications and TechImp solutions

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Coherence and time-frequency analysis of impulse voltage and current measurements

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James

Investigation of PD Detection on XLPE Cables

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

Partial discharge diagnostics on very long and branched cable circuits

Partial Discharge Monitoring and Diagnosis of Power Generator

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

1409. Comparison study between acoustic and optical sensors for acoustic wave

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Integrated Optical Waveguide Sensor for Lighting Impulse Electric Field Measurement

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform

LEVEL DEPENDENT WAVELET SELECTION FOR DENOISING OF PARTIAL DISCHARGE SIGNALS SIMULATED BY DEP AND DOP MODELS

CVVOZE Power Laboratories (CVVOZEPowerLab)

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Model Series 400X User s Manual. DC-100 MHz Electro-Optic Phase Modulators

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION *

IEEE Transactions on Power Delivery. 15(2) P.467-P

MONTRANO. Continuous monitoring system for power transformers

CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD

Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors

UHF PARTIAL DISCHARGE DIAGNOSIS OF PLUG-IN CABLE TERMINATIONS

NON-AMPLIFIED PHOTODETECTOR USER S GUIDE

Partial Discharge Source Classification and De-Noising in Rotating Machines Using Discrete Wavelet Transform and Directional Coupling Capacitor

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Transient calibration of electric field sensors

ELECTROMAGNETIC FIELD APPLICATION TO UNDERGROUND POWER CABLE DETECTION

A Broadband High-Efficiency Rectifier Based on Two-Level Impedance Match Network

NON-AMPLIFIED HIGH SPEED PHOTODETECTOR USER S GUIDE

Module 16 : Integrated Optics I

Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications

On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories

High Field Electrical Conduction and Breakdown in Solid Dielectrics

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

Why partial discharge testing makes good sense

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER

Fundamentals of Partial Discharge in the Context of Field Cable Testing Key words: Partial discharge, power cable, electrical testing

USING DAMPED AC VOLTAGES

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.

Spurious-Mode Suppression in Optoelectronic Oscillators

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

TECHIMP Power Transformer Monitoring

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

Analysis of Partial Discharge Detection in Power Cable by WTST-NST Filter Technology

Software System for Finding the Incipient Faults in Power Transformers

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM

This is an author-deposited version published in : Eprints ID : 18192

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

Laboratory investigation of an intensiometric dual FBG-based hybrid voltage sensor

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

E/O and O/E Measurements with the 37300C Series VNA

UltraTEV Locator Portable Partial Discharge (PD) investigation system.

Simulation Model of Partial Discharge in Power Equipment

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

New Techniques for the Monitoring of Transformer Condition

Transcription:

Using optical couplers to monitor the condition of electricity infrastructure S.G. Swingler, L. Hao, P.L. Lewin and D.J. Swaffield The Tony Davies High Voltage Laboratory, University of Southampton, Southampton Abstract Increases in renewable and distributed generation will change the operational characteristics of our ageing power networks. To cope with these changes improved monitoring of the performance of network infrastructure is needed. Defects developing in electrical plant give rise to partial discharge (PD) activity. This paper describes an on-line PD monitoring system based on electro-optic modulators. This technique does not require a power supply at the site of the sensors and the optical transmission of signal data is a significant advantage in electrically noisy environments. Laboratory based experiments and field trials are described, which show that this approach is feasible for HV transformers and underground cable. Intelligent filtering techniques have been developed to improve the sensitivity of detection and identify PD signals without assuming any knowledge of their characteristics. 1 Introduction Increasing renewable and distributed generation is changing the loading characteristics and current flows on our ageing power networks. The need to load particular parts of the system to maximise renewable output will also change the logistics of maintenance outages. To cope with these changes improved monitoring of the performance and degradation of network infrastructure is needed. Electrical insulation ages as a result of thermal, mechanical and electrical stresses. Defects develop and may lead to catastrophic failure. Partial discharge (PD) activity is a prominent indicator of insulation defects. Continuous on-line PD monitoring provides information about progressive degradation under operational stress, thus reducing the likelihood of breakdown. This paper describes the development and testing of a monitoring system based on an optical sensing technique using electro-optic (EO) modulators. This system does not require a power supply at the site of the sensors and the optical transmission of signal data is a significant advantage in electrically noisy environments such as HV substations. Laboratory based experiments and field trials have shown that this approach is feasible. The monitoring system has been evaluated for use with underground cable circuits (using capacitative couplers on the cable joints) and HV transformers (via a broadband current transducer connected between the bushing tap point and earth). Intelligent filtering techniques based on a support vector machine have been developed to identify PD signals without assuming any knowledge of their - 1 -

characteristics. In theory it has a greater capability of generalization than traditional neural network approaches. Its application to PD signal processing is described. 2 The Electro-Optic Modulation Technique The PD monitoring technique is based on the use of a lithium niobate (LiNbO 3 ) electro-optic modulator. The basic principle of the technique is shown in figure 1. PD is detected using a conventional sensor, such as a capacitative coupler [1,2] and the measured PD signal is fed to an optical fibre coupled LiNbO 3 waveguide modulator. This modulates the intensity of any transmitted laser light as an approximately linear function of the voltage applied across it, turning the electrical PD signal into light beam of varying intensity. The optical network supplies polarized laser light via optical fibre to the modulator input, and monitors the optical output from the modulator using an optical receiver. The electro-optic modulator has the advantages of being compact and passive requiring no local power to operate. The laser source, which is controlled by a temperature and current laser diode controller, has a wavelength of 1550 nm and maximum power of 10 mw. A polarization tuner was used to ensure that the input light for the modulator was linearly polarized. The optical receiver has a bandwidth of 1 GHz. 1550nm Laser, 10mW output Polarisation Controller Laser controller (temperature & current) Polarisation Maintaining Fibre Photo-receiver EO Modulator To Digital Oscilloscope PD Signal Figure 1 EO modulator-based capture of PD signals 3 Model tests on a transformer bushing One of the laboratory models used to evaluate the EO modulator is based on a simple transformer bushing-tap system. The connection between the low voltage side of a transformer bushing and earth is monitored using a radio frequency current transformer (RFCT) connected to the EO modulator system (figure 2). The practical measurement bandwidth of the RFCT is 200 MHz. By using three turns on the primary side the measurement gain of the sensor - 2 -

is improved across the whole range of its bandwidth. For these tests the detection sensitivity of the EO modulator was enhanced by including a battery powered wideband amplifier (20 db gain with a bandwidth of 1 GHz). A digital oscilloscope, LeCroy LC684DXL with a bandwidth of 1.5GHz, was used to display, store and analyse the signals from the RFCT/photodiode. High Voltage PD source Input unit Bushing tap RFCT 20 db Amp EO modulator Polarised light source source Optical fibre Conventional PD detector Digital Oscilloscope Photodiode PC Fig. 2: Schematic of the experiment For comparison, a conventional PD detector (Robinson Model 700 with 40kHz-80kHz band-pass frequency) was used alongside the EO modulator system. This allowed conventional measurement of the magnitude (apparent charge) of any PD observed. The data were also displayed and saved in a computer via an oscilloscope and a GPIB card. PD signals were generated using two types of artificial PD source: These simulated a typical PD source external to a transformer under test and PD signals representative of internal PD in the transformer. External PD (corona in air) was generated by connecting a rod to the high voltage supply. Internal PD was simulated by covering a plane earth electrode with a 5mm thick Perspex sheet on which was placed a coil of tinned copper wire. A plane high voltage electrode was suspended over the Perspex leaving an oil gap of 10mm. Applying high voltage to the bushing producing PD from the floating wire. - 3 -

Fig. 3: Output from a corona pulse Fig. 3 compares the same corona discharge signal recorded at the amplified RFCT with the output of the photodiode. Although the photodiode signal is noisier, the discharge signal is clearly identifiable. From comparison with data from the Robinson detector the electro-optic modulator circuit can reliably detect discharge events above 40 pc. Corona discharge characteristically occurs around the negative peak of the voltage cycle and has a fairly consistent magnitude (around 50pC in this case). Internal discharges from the floating wire occur across the voltage cycle and are more variable in magnitude. Fig. 4 shows the phase, amplitude and number (ϕ-q-n pattern) for floating discharge during 500 continuous power cycles. The average discharge magnitude was 100pC and the peak magnitude 380pC. For the floating discharge source it was again possible to detect discharge events greater than 40pC. - 4 -

Fig. 4: ϕ-q-n patterns for floating discharges 4 Tests on full size 400 kv Cable joints In addition to tests carried out on model cable and a 132 kv cable joint at Southampton [1], practical PD measurements have been carried out on fullsize 400 kv cable joints at the Südkabel GmbH factory in Mannheim, Germany. Figure 5: The 400 kv prefabricated cable joint - 5 -

A short length of 400 kv cable containing a prefabricated joint (figure 5) was energised with alternating voltage using a series resonant supply. The earth screen of the pre-moulded joint was isolated from that of the XLPE cable screen to permit PD measurement across the screen interruption. PD was monitored using both the EO modulator and a conventional PD detector (a Robinson Model 5). Artificial defects were introduced into a joint, which had been shown to be PD up to an applied voltage of 250 kv. The locations of the defects are shown in figure 6. Firstly four metal wires were placed on the surface of the stress cone near to the HV copper stress shield (position A) and the joint reassembled and electrically tested. The wires were then removed and replaced by copper filings about halfway along the stress cone as can be seen at position B. B A Figure 6: Location of the artificial defects: (A) the metal wires and (B) the copper filings on the stress relief cone within the cable joint With the copper wires the joint began to discharge (PD inception) at 13 kv. The voltage was further increased and measurement was carried out at 70 kv. A typical PD signal is shown in Figure 7. The conventional PD detector indicated a PD level was 20 30 pc. With copper filings on the stress cone the PD inception voltage was found to be 180 kv. At 480 kv discharges of magnitude 10-12 pc were observed (see figure 8). - 6 -

signal (mv) 25 20 15 10 5 0-5 -10-15 0 5 10 15 20 time (us) Figure 7: PD signal due to metal wires within the cable joint 12 10 8 6 signal (mv) 4 2 0-2 -4-6 0 2 4 6 8 10 time (us) Figure 8: PD signal due to copper filings within the cable joint During the test programme one joint without artificially introduced defects showed a PD inception voltage of 41 kv. The voltage was increased to 186 kv and PD of 30 pc was observed. Subsequent inspection revealed that the PD activity was due to a manufacturing defect (void) between the stress shield and the epoxy resin within the joint. During these tests various optical and electronic configurations were examined to optimize the performance of the system and consideration was given to the trade-off between performance and cost [3]. - 7 -

5 Improving detection sensitivity The performance of the PD detection system can be enhanced by improving both the hardware and the data analysis techniques. Analysis of the measurement data revealed that much of the background noise is caused by the optical system itself having a resonant frequency of about to 1 MHz. Inserting a band-stop filter (stop band: 540 khz 1.6 MHz) will therefore increase measurement sensitivity. The sensitivity of PD measurements made on-site is often impaired by high levels of background interference (electromagnetic noise), particularly where many items of plant are co-located in substations. The use of multi-resolution wavelet transforms to improve the discrimination of PD signals has been investigated at Southampton [1, 4]. Results indicate that with the appropriate selection of wavelet family and number of decomposition levels, the wavelet analysis technique is effective at distinguishing real PD pulses from corona discharge, narrow-band radio interference and random noise. Further removal of interference has been achieved by applying level dependent threshold values. This use of wavelet packets [5] to remove measurement noise/interference from PD data acquired in the field has also assessed. Results from cables in normal operation indicate that wavelet packet de-noising was capable of filtering signals heavily corrupted by noise without assuming a priori knowledge of the PD signal characteristics. Extending this concept of developing intelligent filtering techniques to identify PD signals without assuming any knowledge of their characteristics has lead to the application of a pattern recognition tool, namely the support vector machine (SVM) in order to extract PD signals from EO modulator based measurements [6]. The approach combines wavelet filtering with a SVM which is based on statistical learning theory and principles of structural risk minimisation. Wavelets have the advantage of combining time domain and frequency domain information, thus providing more useful information to analyze than using a single domain. In theory, the SVM possesses a greater capability for generalization than traditional neural network methods. It is particularly useful in situations involving sparse data sets. Initial trials indicated that the SVM could distinguish between PD emanating from different sources [7]. Wavelet decomposition effectively applies a pair of high-pass and low-pass filters, which decompose the original signal into a series of detail coefficients (high pass) and approximation coefficients (low pass). The decomposition process is iterative. Hence if a signal is decomposed into detail coefficients (D1) and approximation coefficients (A1) the resulting approximation coefficients can themselves be broken down into detail coefficients (D2) and - 8 -

approximation coefficients (A2), and so on. The coefficients of each level have half the bandwidth and half the length of the level above. The technique was investigated further using data generated with the transformer bushing rig (figure 2). PD signals were simulated using a UHF calibrator injecting calibration pulses directly into the bushing core bar. Conventional PD measurements were also taken using a Robinson detector. The background noise and the simulated PD signals were decomposed using the Daubechies family order 7 as the mother wavelet, since research to date indicates this gives promising results [8]. Figure 10 shows the decomposition coefficients at seven different levels for the noise and 160pC PD data. (160pC is the minimum detectable PD level without filtering). The detail coefficients at level 3 (D3) clearly discriminate between noise and the 160 pc PD signal. Therefore the D3 coefficients were selected as the feature for SVM discrimination. Two sets of noise data were recorded and eight sets of PD data (at magnitudes of 30pC, 40pC, 50pC, 70pC, 90pC, 110pC, 130pC and 160pC). The SVM was trained with one set of noise data and the 160pC PD data.. Subsequently the SVM was tested with the rest of the data sets. In all cases 2800 signals were analysed for each level of discharge. The number of signals correctly identified as PD is shown in Table 1. It is seen that the SVM can reliably identify discharge activity to 50 pc and only failed to recognise 1 in 200 events at 30 pc. Similar tests using the frequency spectrum of the PD signal as the input feature for the SVM correctly identified only 14% of 30pC discharges[9]. Thus the combination of wavelet analysis and the SVM can achieve substantial improvement in the detection and measurement of PD in noisy environments. Data sets WDEC3 Noise2 100% (2800/2800) 30pC 99.4643% (2785/2800) 40pC 99.8214% (2795/2800) 50pC 100% (2800/2800) 70pC 100% (2800/2800) 90pC 100% (2800/2800) 110pC 100% (2800/2800) 130pC 100% (2800/2800) Table 1 Identification rates achieved using the D3 feature. - 9 -

Figure 10 Wavelet decomposition coefficients - 10 -

6 Conclusions This paper has described the continuing development of a PD detection technique based on the electro-optic modulator. The potential application of the technique for PD monitoring in high voltage transformers has been assessed using a simple laboratory experiment. Results indicate that it is possible to detect internal discharge activity above 40pC using a RFCT at the bushing tap point to modulate transmitted laser light via a waveguide modulator. Practical PD measurements on both a 132 kv cable joint at the University of Southampton and 400 kv cable joints at Südkabel GmbH, Germany, have demonstrated the effectiveness of the technique for monitoring high voltage cable assets. PD of 10-15 pc could be clearly measured using the optical remote sensing technique. The measurement sensitivity of this technique can be further increased by applying suitable filters and amplifiers to process the optical receiver output signals and remove any inherent noise of the measuring system. The combination of digital filtering and a pattern recognition tool (wavelet analysis and the support vector machine) can achieve substantial improvement in the detection and measurement of PD in noisy environments. Acknowledgement This paper summarises research supported through the EPSRC Supergen V, UK Energy Infrastructure(AMPerES) grant in collaboration with UK electricity network operators working under Ofgem's Innovation Funding Incentive scheme; - for full details see http://www.supergen-amperes.org References [1] Tian, Y., Lewin, P. L., Davies, A. E., Swingler, S. G., Sutton, S. J. and Hathaway, G. M. Comparison of On-line Partial Discharge Detection Methods for HV Cable Joints, IEEE Trans. DEI, Vol. 9, No. 4, pp. 604-615, (2002) [2] Y. Tian, P.L. Lewin, A.E. Davies, S.J. Sutton and S.G. Swingler, Partial Discharge Detection in Cables using VHF Capacitive Couplers, IEEE Trans. DEI, Vol. 10, No. 2, pp. 343-353, (2003) [3] Tian, Y., Lewin, P. L., Wilkinson, J. S., Shroeder, G., Sutton, S. J. and Swingler, S. G. An improved optically based PD detection system for continuous on-line monitoring of HV cables. IEEE Transactions on Dielectrics and Electrical Insulation, 12 (6). pp. 1222-1234. (2005) - 11 -

[4] P. Wang, P. L. Lewin, Y. Tian, S. J. Sutton and S. G. Swingler, Application of wavelet-based denoising to online measurement of partial discharges, Proceedings of 8th IEEE International Conference on Solid Dielectrics, pp 619-622, Toulouse, France (2004) [5] A. Kyprianou, P.L. Lewin, V. Efthimiou, A. Stavrou and G.E. Georghiou, Wavelet packet denoising for online partial discharge detection in cables and its application to experimental field results. Measurement Science and Technology 17(9) pp. 2367-2379. (2006) [6] L. Hao, P.L. Lewin and S.J. Dodd, Extraction of PD Signals from an Electro-optic Modulator Based PD Measurement System. Proceedings of 2006 IEEE Conference on Electrical Insulation and Dielectric Phenomena, pp. 623-626, Kansas City, Missouri, USA. (2006) [ [7] L. Hao, P.L. Lewin and S.J. Dodd, Comparison of Support Vector Machine Based Partial Discharge Identification Parameters Proccedings of 2006 IEEE International Symposium on Electrical Insulation, pp 110-113, Toronto, Canada (2006). [8] X. Ma, C. Zhou and I.J. Kemp Interpretation of Wavelet Analysis and its Application to Partial Discharge Detection IEEE Trans DEI, Vol. 9, No. 3, pp 446-457. (2002). [9] Hao, L., Lewin, P. L. and Swingler, S. G. Improving detection sensitivity for partial discharge monitoring of high voltage equipment,. Measurement Science and Technology, Vol. 19 No.5, (April 2008) - 12 -