Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

Similar documents
104 Pattanakan 69, Pravet, Bangkok Thailand A VER

Type Test of a 145 kv Termination Type TS 145-II

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

High-Voltage Test and

TT 0710/03. TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1

About us. Vision. To lead our field in innovation, quality and customer service.

05e28 Di-electric Strength (High Voltage) Test and Leakage Current Test Proficiency Testing Program

ISSN: [IDSTM-18] Impact Factor: 5.164

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Cast resin transformers HARMONY TM

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Transformer Factory Testing

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Diagnostic testing of cast resin transformers

700 Series AC Dielectric Test Sets

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

86 chapter 2 Transformers

This Certificate consists of 75 pages in total.

ISOLATING TRANSFORMERS FOR TLC PLANTS

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Test description for dry-type transformers chapter for special tests

Power transformers for Network, Rectifiers, Furnace

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

Holiday Detector mod. 284/35KV

700 Series AC Dielectric Test Sets

MSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

MSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA FEATURES BENEFITS APPLICATIONS 1/6

VARIABLE FREQUENCY RESONANT TEST SYSTEM

Transformer Tests BEST BALIKESİR ELEKTROMEKANİK SANAYİ TESİSLERİ A.Ş. Facility 1 : Ağır Sanayi Bölgesi No Balıkesir / Türkiye

Three-Phase Transformer Test Systems

RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL

7. INSPECTION AND TEST PROCEDURES

EE High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Mitigating Murphy s Law While Test. Frédéric Dollinger

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL

Onsite Mobile AC High Voltage Test System

CAST RESIN DRY TRANSFORMER

Distribution transformers Part 2 Ground mounted transformers not closecoupled

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

REPORT OF PERFORMANCE TIC

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

Conventional Paper-II-2011 Part-1A

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE

Calibration of High-Voltage Test Equipment

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

3MElectrical Markets Division

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Power Engineering II. High Voltage Testing

TEST REPORT. Table Of Contents

TMC Transformers TMC

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

SGM series. AC Resonant Test System. Applications & Advantages

STS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

Electrical Description

INTERNATIONAL STANDARD

TEST REPORT NO. 046/081701/99

N. TEST TEST DESCRIPTION

Introduction. Centrado leading-edge transformer. Introduction

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

Mobile Power Transformer Test Systm

Test description for dry-type transformers chapter for routine tests

High Votage Module AC/DC/Impulse Test System

HOW TO SAFE GUARD THE TRANSFORMER..???

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Presco AG. Peak Voltmeter. Type PVM-100. Instruction Manual. Table of contents

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Specialists in HV and MV test and diagnostics. Testing in Substations

Arc Suppression Coils

MEDIUM & HIGH VOLTAGE

SOUTH AFRICAN NATIONAL STANDARD

NXCT 345 kv Test Performance Record For LAPEM

MINISTRY OF ELECTRICITY

METHODS AND CIRCUITS FOR POWER ARC TEST IN AC CURRENT OF THE SIMPLE AND DOUBLE INSULATOR SETS WITH COMPOSITE MATERIAL FOR AERIAL ELECTRIC LINES

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

CDAX 605 High Precision Capacitance & Dissipation Factor Test Set

Advanced Test Equipment Rentals ATEC (2832) Lightning Surge Simulator LSS-F02.

Regional Technical Seminar SHORT CIRCUIT FORCES

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

Transcription:

A6/028659 Test Report CESI Approved Page 1 Client MF Trasformatori s.r.l. - Calcinato (BS) Italy Tested equipment Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated windings, for continuous duty, with cooling by air natural convection (AN): MF - 1930/965/965 kva - 15 kv / 0,59/0,59 kv Tests carried out Verification of dynamic ability to withstand short-circuit PUBBLICATO A6028659 (PAD - 850659) Standards/Specifications IEC 60076-11 {Ed.1.0} (2004-05) Test date from September 28, 2006 to September 29, 2006 The results reported in this document relate only to the tested equipment. Partial reproduction of this document is permitted only with the written permission from CESI. No. of pages 14 No. of pages annexed 14 Issue date October 31, 2006 Prepared Verified Approved BU COM - M. Assolari BU COM - F. Pizzi BU COM - V. Scarioni CESI Centro Elettrotecnico Sperimentale Italiano Giacinto Motta spa Via R. Rubattino 54 20134 Milano - Italia Telefono +39 022125.1 Fax +39 0221255440 http://www.cesi.it Capitale sociale 8 550 000 Euro interamente versato Codice fiscale e numero iscrizione CCIAA 00793580150 Registro Imprese di Milano Sezione Ordinaria N. R.E.A. 429222 P.I. IT00793580150

A6/028659 Test Report CESI Approved Page 2 Tests witnessed by Mr. Bai MF Trasformatori s.r.l. Identification of the object not requested Only for laboratory requirement, in order to reproduce the test conditions, all the laboratory data are contained in the document marked: A6/025224 The measurement uncertainties of the test results reported in this document comply with the following limits: voltage : ± 5 % ; current : ± 5 % ; time : ± 5 % The measurement uncertainties are estimated at the level of twice the standard deviation (corresponding, in the case of normal distribution, to a confidence level of about 95 %) and have to be considered as maximum estimated values referred to that type of measurement. Activity code 56022M M2001IG

M2002IG Contents Page Test date Rated characteristics of the tested object assigned by the Client 4 Verification of dynamic ability to withstand short-circuit 5 to 8 Requested values 5 Test arrangements and test procedures 5 Short-circuit tests with three-phase current 6 September 28, 2006 Test circuit M0022 7 Measurement of short-circuit inductance 8 September 28, 2006 Verification after short-circuit tests 9 to 12 Dielectric routines tests 9 September 28, 2006 Partial discharge measurements 10 to 12 September 29, 2006 Photographs of test object and test arrangements 13 to 14 Pages annexed: Oscillogram (total pages: 14) Test Report CESI A6/028659 Approved Page 3

A6/028659 Test Report CESI Approved Page 4 Rated characteristics of the tested object assigned by the Client Dry-type power transformer with three windings Manufacturer MF Trasformatori s.r.l. Calcinato (BS) Manufacturer's serial number 260406/1 Year of manufacturing 2006 Number of phases 3 Rated voltage of the high-voltage winding (primary winding) 15 kv ± 4 x 2,5 % Rated voltage of the low-voltage windings (secondary windings) 590/590 V Rated voltage ratio 15 kv / 0,59-0,59 kv Rated frequency 50 Hz Rated power 1930/965/965 kva Rated current of the high-voltage winding (primary winding) 74,3A Rated current of the low-voltage windings (secondary windings) 944/944 A Short-circuit impedance V cc1-(2-3) 16,56 % Ratio X/R 16,095 Connection symbol Dd0y11 Cooling method AN Total mass 5100 kg Climatic class C2 Environmental class E2 Fire behaviour class F1 Service class VI Characteristics of the windings Highest voltage for equipment applicable to the high-voltage winding 17,5 kv Highest voltage for equipment applicable to the low-voltage windings 1,1 kv Rated insulation levels LI 95 AC 38 / AC 3 Insulation class F Type of construction with circular concentric coils High-voltage winding conductor aluminium Low-voltage windings conductor metal foil (aluminium) Traction transformer conforms to CEI EN 50329 Standard Name and signature of Client's witness: M2027IG

A6/028659 Test Report CESI Approved Page 5 Verification of dynamic ability to withstand short-circuit Requested values Test current values were calculated neglecting the system impedance. Tap-changer Short-circuit current (*) U position r Z SC X/R k x 2 r.m.s. value peak value - kv % - - A A 5-6/7-8 15,0 16,56 16,095 2,55 259,0 660,4 1-2/7-8 16,5 16,36 16,663 2,55 238,3 607,7 5-6/11-12 13,5 16,83 15,692 2,55 283,2 722,0 (*) Values of phase short-circuit current of the high-voltage winding (delta-connected). Test arrangements and test procedures The transformer was tested connecting a three-phase supply to the high-voltage winding (primary winding). The low-voltage windings were short-circuited before the application of the voltage to the other winding of the transformer (pre-set short-circuit). During each test were recorded the line-to-line supply voltages, the phase currents of the high -voltage winding and the fault current, if any, between the mass (insulated) of the transformer and earth. Nine tests were performed (three tests on each limb): three tests with the tap-changer on the principal tapping (with the maximum peak current on the middle limb), three tests with the tap-changer in the position corresponding to the highest voltage ratio (with the maximum peak current on one of the outer limbs), three tests with the tap-changer in the position corresponding to the lowest voltage ratio (with the maximum peak current on one of the other outer limbs). M2028IG

A6/028659 Test Report CESI Approved Page 6 Short-circuit tests with three-phase current Test circuit: Test frequency: Reference number of the oscillograms: Conditions of the transformer before the tests: Transformer prearranged on the voltage ratio: M0022 50 Hz MP-A6/025224 as supplied by the Client 15 kv / 0,59-0,59 kv Date: September 28, 2006 Tap-changer No-load Test current Test Oscillogram position supply peak r.m.s. average Duration voltage value value value No. No./sheets - V A A A s 176,1 1 1/1 5-6/7-8 -- 451,4 174,5 175,6 0,1 176,2 258,9 2 2/1 -- 662,5 256,1 258,0 0,5 258,9 258,8 3 3/1 -- 662,5 256,5 258,1 0,5 259,0 257,7 4 4/1 -- 656,8 254,7 256,8 0,5 257,8 5 5/1 1-2/7-8 -- 614,2 241,5 238,0 240,3 0,5 241,4 6 6/1 -- 608,5 241,4 236,2 239,4 0,5 240,7 7 7/1 -- 622,8 242,3 237,7 240,5 0,5 241,5 8 8/1 5-6/11-12 -- 278,9 275,8 278,2 0,5 709,5 279,9 9 9/1 -- 277,0 273,8 276,3 0,5 702,8 277,9 10 10/1 -- 278,9 275,7 278,0 0,5 707,6 279,5 Conditions of the transformer after the tests: see notes - Externally did not show any damage. M2029IG

A6/028659 Test Report CESI Approved Page 7 Test circuit M0022 The symbols used in this diagram are the same as those on the oscillograms. Correspondence between laboratory circuit phase and test object terminal Laboratory circuit phase R S T Test object terminal U V W M0022IG

M2032IG Measurement of short-circuit inductance The measurement of short-circuit inductance was performed before the short-circuit tests and after every series of three tests by means of a Schering bridge (Maxwell diagram) which allows a reproducibility of at least ± 0,2%. For all measurements the transformer was set-up in the following conditions: the tap-changer was placed in the position corresponding to the highest voltage ratio, the terminals of the low-voltage windings were short-circuited, the measurement points were applied to the terminals of the high-voltage winding, delta-connected. Date: September 28, 2006 short-circuit inductance variation short-circuit inductance variation tap-changer [mh] [%] [mh] [%] measurement effected position measured at the terminals from the initial measurement calculated for single limb from the initial value U-V U-W V-W U-V U-W V-W U V W U V W 1-2/7-8 before the tests 147,05 146,50 147,74 - - - 220,500 222,587 218,864 1-2/7-8 after the test no. 4 147,20 146,54 147,78 0,10 0,03 0,03 220,835 222,590 218,871 0,15 0,00 0,00 1-2/7-8 after the test no. 7 147,06 146,48 147,84 0,01-0,01 0,07 220,484 222,845 218,761-0,01 0,12-0,05 1-2/7-8 after the test no. 10 147,25 146,60 147,92 0,14 0,07 0,12 220,859 222,887 218,927 0,16 0,13 0,03 Maximum variation of short-circuit inductance stated by Standard: 4%. Test Report CESI A6/028659 Approved Page 8

A6/028659 Test Report CESI Approved Page 9 Verification after short-circuit tests Dielectric routines tests (at 100% of the original test values) Separate-source AC withstand voltage test The single-phase test voltage was applied between the terminals of the winding under test and the terminals of the other windings and core and frame, connected together to earth. Date: September 28, 2006 Winding Tap-changer Tapping voltage Test parameters under test position of HV winding voltage frequency duration - - kv kv Hz s high-voltage 5-6/7-8 15,0 38,0 50 60 low-voltage d 3,0 50 60 low-voltage y 3,0 50 60 Test result: no collapse of the test voltage occurred. Induced AC voltage test (ACSD) The three-phase test voltage was applied to the terminals of the low-voltage winding y and the relevant neutral terminal was connected to earth. Date: September 28, 2006 Winding Tap-changer Tapping voltage Test parameters under test position of HV winding voltage frequency duration - - kv kv Hz s low-voltage y 5-6/7-8 15,0 1,18 150 40 Test result: no collapse of the test voltage occurred. M2034IG

A6/028659 Test Report CESI Approved Page 10 Circuit A0153 Induced AC voltage test circuit for partial discharge measurement - Test circuit at 150Hz, three-phase connection CO - frequency converter NUOVA SACCARDO; power 80 kva; input voltage 380V/660V at 50 Hz; output voltage 660 V ± 10 % at 150 Hz G - Faraday cage R - three-phase voltage regulator; power 187 kva; voltage 380-658V/ 0 690-1200V E - earth connection V 1 - direct reading digital voltmeter FLUKE; CESI No. 06393 n - neutral connection K - charge pulse generator AMPERE; CESI No. 02526 D - capacitive voltage divider PASSONI & VILLA; type CD; C= 300 pf; V= 250 kv; scale factor 2551,0; CESI No.39116-39117 V 2 - direct reading digital voltmeter AGILENT 34401A; CESI No.55077 C a - C b - C c - coupling capacitor PASSONI & VILLA; C= 2000 pf; voltage 150 kv; CESI No.23772-23773-23774 (one for each phase) AKV - matching coupling quadrupole HAEFELY TRENCH; type AKV 573; CESI No. 13290 K - special, multi-wire, connecting cable PD - partial discharge detector HAEFELY TRENCH; type TE 571; CESI No. 13281 A0153IG

A6/028659 Test Report CESI Approved Page 11 Circuit A0160 Partial discharges measurement Direct circuit - Scheme 1a P - calibrator AMPERE; CESI No. 02526 C k - coupling capacitor PASSONI & VILLA; C= 2000 pf; voltage 150 kv; CESI No.23772-23773-23774 (one for each phase) AKV - matching coupling quadrupole HAEFELY TRENCH; type AKV 573; CESI No. 13290 K - special, multi-wire, connecting cable PD - partial discharge detector HAEFELY TRENCH; type TE 571; CESI No. 13281 A0160IG

A1262IG Partial discharge measurement (after short-circuit test) Test object: Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated windings, for continuous duty, with cooling by air natural convection (AN): MF 1930/965/965 kva - 15 kv / 0,59/0,59 kv Test circuit: A0153 Measurement circuit: A0160 (direct calibration 5 pc, oscillogram No.11) Arrangement: see photographs from No.3 to No.4 Test frequency: 150 Hz Atmospheric conditions and correction factor b t d /t w h Relative humidity kpa C g / m 3 % 100,23 25,0 / 17,0 10,07 43,9 Date: September 29, 2006 Phase Applied induced voltage Duration of the Partial discharge measurement Required voltage Temperature of lv side HV side voltage the test object voltage increase voltage decrease (phase-to-phase) (phase-to-phase) (phase-to-phase) application Oscillogram V 1 V 2 V HV =V 2 *K 2 * 3 PD level PD level kv rms V rms V rms kv rms s C pc pc No. 1W 1,8Ur direct reading on HV side 6,07 27,0 30 --- --- -- 25,0 1,3Ur direct reading on HV side 4,39 19,5 180 --- 0,5 12 1V 1,8Ur direct reading on HV side 6,07 27,0 30 --- --- -- 25,0 1,3Ur direct reading on HV side 4,39 19,5 180 --- 0,5 13 1U 1,8Ur direct reading on HV side 6,07 27,0 30 --- --- -- 25,0 1,3Ur direct reading on HV side 4,39 19,5 180 --- 0,5 14 Notes Ur is the rated voltage of the high-voltage winding (primary winding) equal to 15,0 kv (phase-to-phase) K 2 is the scale factor of the capacitive voltage divider (D) equal to 2566,4 Test Report CESI A6/028659 Approved Page 12

A6/028659 Test Report CESI Approved Page 13 Photo no. 1 Photo no. 2 M2009IG

A6/028659 Test Report CESI Approved Page 14 Photo no. 3 Photo no. 4 M2009IG