APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1

Similar documents
Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682

Actuating Terminal Equipment Controller (ATEC) Base VAV - Cooling or Heating, Application Application Note

INTAC Microprocessor Humidifier Controller

BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665

VT8600 Series User Interface Guide Rooftop Unit, Heatpump and Indoor Air Quality Controller

TEC Controller Constant Volume with Hot Water Reheat, Application Application Note Building Technologies

ELECTRONIC THERMOSTAT: T951

Modbus VAV Controller Configuration Properties

ELECTRONIC THERMOSTAT: T920

Universal Controller

Room Controller Thermostat

Stryker BACnet VAV Wizard Configuration Guide (WEBs-N4)

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

SE8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

PIR Ready VT72xx & VT(R) 73xx Series 24 Vac Fan Coil and Zoning Thermostats For Commercial and Lodging HVAC Applications

TLC3-BCR-U Series Thermostat

OVEN INDUSTRIES, INC. Model 5C7-362

PROCESS & TEMPERATURE CONTROLLERS

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

SRC-110 Series Zone Controllers with Modbus RTU

SRC-110 Series Zone Controllers. BACnet MS/TP. Product sheet CT2.143 SRC-110-BAC

Model 12200A RCN PTAC/PTHP/FAN COIL CONTROL NODE OPERATION OUTPUTS G1 = FAN 1 G2 = FAN 2 G3 = FAN 3 O/B = Rev Valve W = HEAT Y = COMPRESSOR

Fan Coil Actuator FCA 2

Digital Room Sensor Technical Guide

Intelligent Compact Controller

PIR Ready SE7200, SE7300 & SER7300 Series

Introduction to BAS Technology

BACnet Integration Manual

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

Model No. DFC Support DIGITAL ENHANCED GAS FIRED MODULATING CONTROL

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Modbus Integration Integration for Modbus Functionality for VT8300 Series

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

1 Digital input (24Vac or dry contact) Inputs

M a y 3 rd, / R4

Control equipment. Regula 1.4. lindab we simplify construction

SRC-200 Series Climate Controllers with BACnet MS/TP

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

TC LV-Series Temperature Controllers V1.01

SE7000 Series Application guide

BACnet- MS/TP COMMUNICATION V

Device connection and commissioning can only be carried out by qualified professionals. Always make the connections while the power is switched off.

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

NX Series Inverters. HVAC Pocket Programming Guide

VT8300 Series Installation Guide 24 Vac Low Voltage

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER

Metasys Zoning Package Commissioning

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

CONTENTS Installation Location

VT7600F Series RTU Terminal Equipment Controller with Modulating Heat. Installation Guide

Installation Guide. Contents. VT7600E Series RTU Terminal Equipment Controller with IAQ Control

8510 AC Spindle Drive System

Ma y 3 rd, 2012 / R4

BAS Integration Manual

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Instruction Notes for 108A L Sensor Input

ECL-VAV Series Preloaded Applications. User Guide

The MFT B-Series Flow Controller.

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

Communicative heating and cooling controller, BACnet MS/TP UB200. Summary

SRC-21x Series Climate Controllers with BACnet MS/TP

SmartZone-2 & SmartZone-4

INSTALLATION, WIRING & CONFIGURATION

BOILER MANAGEMENT SYSTEM

CONTENTS Installation Location

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE

HARDWARE GUIDE. Digital Sensor - T1100 Series. Specifications and Operational Guide

ECM HIGH EFFICIENCY CIRCULATORS

Obtaining Flat Test Port Power with the Agilent 8360 s User Flatness Correction Feature. Product Note

Stryker CVAHU WEBs-N4 Configuration Wizard Guide

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

October 25 th 2010 / R1

SE7600F Series. RTU Terminal Equipment Controller with Modulating Heat. Installation Guide For Commercial HVAC Applications CONTENTS.

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description

Initial Power-Up Tests

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

Multi-Input Field Unit User Manual

Product Specification for model TT Transducer Tester Rev. B

E-BUS Digital Room Sensor Technical Guide

APPENDIX APPENDIX A 1

Rev UltraSite User s Guide BEC Supplement

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

Satchwell IAC420 UNIVERSAL MULTI-LOOP INTELLIGENT ADVANCED CONTROLLER GENERAL CONTROLLER DETAILS MODULE LIST

Modbus communication module for TCX2: AEX-MOD

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

N2000S UNIVERSAL PROCESS CONTROLLER FOR SERVO POSITIONING OPERATING MANUAL. (Manual Key): toggles the AUTO/MANUAL mode.

Application Note CTAN #287

Temperature Controller

Sales Bulletin #CT007

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

BAC-IO9 BACnet MS/TP Input / Output Modules, Wall Mounted

PWM. Design, Installation, and Operation. (Pulse Width Modulation Zone Controller)

Site Controls Room Thermostat

Transcription:

APPLICATION GUIDE Delta Network Sensor Thermostat: BACstat II DNS-24, DNT-T103, & DNT-T221 Document Edition 3.1 Product Description The BACstat II is an intelligent 4-button room sensor/thermostat with a custom 3-value, 96 segment LCD display that is used with Delta s product line of BACnet Application Controllers. It is capable of displaying a wide range of digital or analog values, and is capable of communicating on Delta s proprietary LINKnet network or directly on a BACnet MS/TP network. When connected to an Application Controller on a LINKnet network it provides programmable remote sensor and expanded I/O capabilities to the controller. When connected on an MS/TP network it functions as an independent BACnet sensor device or a small local controller. The DNS-24 model does not have additional I/O and built-in control strategies, while the DNT-T103 has 1 extra input, 3 binary outputs and a number of built-in application control strategies. The DNT-T221 has 2 extra inputs, 2 analog and 1 binary outputs and built-in application control strategies. As a result, the DNT- T103 and DNT-T221 BACstats are capable of simple stand-alone control when directly connected on an MS/TP network. When connected to a LINKnet network, the additional I/O may be MUXed or otherwise controlled from the Application Controller it is connected to. Contents OTHER RELEVANT DOCUMENTS... 2 IMPORTANT INFORMATION... 2 SETUP & CONFIGURATION... 3 NETWORK COMMUNICATIONS... 3 DEVICE CONFIGURATION (KEYPAD)... 3 SERVICE TOOL MODE (KEYPAD)... 6 INPUT CALIBRATION... 8 INPUT SCALE RANGES... 8 SOFTWARE & PROGRAMMING... 9 OBJECTS... 9 PROGRAMMING... 10 CONTROL FUNCTIONS... 12 OVERVIEW... 12 SOFTWARE LOOP CONTROLLER... 13 SETPOINTS... 16 CONTROL DIAGRAM... 17 CONTROL APPLICATIONS (MUX, VAV, VVT, HPU, FCU, RAD, HUM)... 18 OUTPUT FUNCTIONS & TYPES... 26 OWS FUNCTIONS... 30 APPENDIX (LCD Object Property Values & Programming Notes)... 32 Document Edition 3.1 Page 1 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide Other Relevant Documents Associated BACstat II Installation Guide (DNS-24, DNT-T103, DNT-221, etc.) RS-485 Network Installation Guide (DOC818-11) ORCAview Operator Guide ORCAview Technical Reference Manual (particularly Appendix G) Release Notes for V3.21 Firmware, V3.22 Firmware, V3.30 Firmware, and BACstats Important Information This document has been updated to include features and capabilities of Release 3 firmware for BACstat II products. And although BACstat firmware is independent from ORCAview, DCU, and Application Controllers, certain BACstat capabilities require support in the other products. It is also important to note that BACstats are not flash loadable in the field an upgrade requires swapping out physical product. 1. V3.21 FIRMWARE & SOFTWARE Note the following issues when BACstats are used with ORCAview, DCU, and Application Controllers loaded with V3.21 firmware/software. MS/TP NETWORK CONNECTION A DCU is required (to which the MS/TP network is connected) Local BACstat display handling and control strategies may be enabled All data exchange must be done in GCL programming in the DCU LINKNET NETWORK CONNECTION The BACstat must be connected to an Application Controller that supports LINKnet devices Local BACstat display handling and control strategies must both be disabled Additional I/O cannot be MUXed All functionality for the BACstat must be done in GCL programming in the Application Controller (i.e., display handling, setpoint adjust, and strategies using the space temperature) 2. V3.22 FIRMWARE & SOFTWARE OR HIGHER Note the following issues when BACstats are used with ORCAview, DCU, and Application Controllers loaded with V3.22 firmware/software. MS/TP NETWORK CONNECTION A DCU is not necessarily required (as long as one System device exists on the MS/TP network) Local BACstat display handling and control strategies may be enabled Data exchange may be done in GCL programming in any DCU or Application Controller on the MS/TP network LINKNET NETWORK CONNECTION The BACstat must be connected to an Application Controller that supports LINKnet devices Local BACstat display handling may be enabled (so GCL programming in the Application Controller for setpoint adjust and LCD display is not necessary) Local BACstat control strategies must be disabled, as this is more suitable on an MS/TP connection Additional I/O may be MUXed Additional BACstat strategies may be done in GCL programming in the Application Controller Page 2 of 35 Document Edition 3.1

Delta Controls Setup & Configuration NETWORK COMMUNICATIONS On an MS/TP network BACstats communicate at a default speed of 76,800 bps. Refer to the ORCAview Technical Reference Manual for further detail on configuring the MS/TP network or changing baud rates, etc. On LINKnet BACstats communicate at 76,800 bps. Refer to the ORCAview Technical Reference Manual for further detail on the NET1 object located in the MS/TP DAC device. Also refer to the associated BACstat II Installation Guide for network installation details. DEVICE CONFIGURATION (KEYPAD) To use ORCAview OWS to configure BACstats refer to OWS Functions on page 30. 1. CONFIGURATION MENU USER ACCESS Access to the Configuration Menu is protected by an access code or PIN. You must enter the valid PIN before access is granted, which works as follows: First press the Up Arrow (σ), and then press the Down Arrow (τ) while still pressing the Up Arrow, and hold them both down for at least 5 seconds. When the Pin text is displayed you are being prompted for the valid PIN or access code, a pre-configured 4-digit code, which you must enter before you can gain access to the Configuration Menu. The buttons on the left side of the BACstat have a value of 0, while the buttons on the right side have a value of 1. Press the proper button sequence to match the password. The default PIN is 1011. Note that the PIN access code, contained in AV31, can be changed through the OWS when the BACstat is connected to an MS/TP network, but not over LINKnet or through the keypad. Once you have entered the valid 4-digit code you will gain access to the Configuration Menu, and CFg will be displayed immediately to indicate you are now in Configuration mode. If you haven t entered a valid code (or if you do not press a button within about 10 seconds), the process will be aborted and you will be returned to normal display mode. If at any time after you have gained access to the Configuration Menu you do not press a button for 2 minutes, the BACstat will exit the Configuration Menu and return to normal display mode. 2. BUTTON & NAVIGATION FUNCTIONS The Button functions are as follows within the Configuration Menu: Button Top Left Top Right Bottom Left (Down: τ) Bottom Right (Up: σ) Description Represents a value of 0 when entering the PIN access code. PREVIOUS: Enter the current setting (and go backward in the menu). Represents a value of 1 when entering the PIN access code. NEXT: Enter the current setting (and go forward to the next item in the menu). Represents a value of 0 when entering the PIN access code. Rotates downward through menu items and options. Decreases a numeric value with each button press. Represents a value of 1 when entering the PIN access code. Rotates upward through menu items and options. Increases a numeric value with each button press. Document Edition 3.1 Page 3 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide Use the NEXT and PREVIOUS buttons to navigate through the menu options. Once you have navigated to the desired item you wish to display or change, use the arrow buttons to make any necessary changes. Once the changes are made or you wish to move on, press NEXT or PREVIOUS. 3. CONFIGURATION MENU OPTIONS The Configuration Menu is a list of items which you can navigate through and make changes to as you need for setup purposes. The Configuration Menu items are as follows: Menu Item CFg [Application] OP1 OP2 OP3 [More] DEG [Settings] Description Displayed momentarily to indicate you have successfully entered the Configuration Menu. The Control Application (AV12). You may choose from any of the following applications: None VAV VVT HPU FCU Unt rad This disables all control strategies and allows the outputs and control icons to be controlled remotely from another device. This enables the VAV control strategy and allows you to configure the outputs for your VAV application. This enables the VVT control strategy and allows you to configure the outputs for your VVT application. This enables the HPU control strategy and allows you to configure the outputs for your Heat Pump Unit application. This enables the FCU control strategy and allows you to configure the outputs for your Fan Coil Unit application. This is no longer an option. Configure control for a Unit Heater using the FCU application. This enables the Radiation control strategy and allows you to configure the outputs for your Radiant Heating application. HuM This enables the Humidity control strategy and allows you to configure the outputs for your Humidity application. Output 1 Configuration. This includes the output function and type (what it will control and how) and other setup parameters as required (such as delays or limits). Output 2 Configuration. This includes the output function and type (what it will control and how) and other setup parameters as required (such as delays or limits). Output 3 Configuration. This includes the output function and type (what it will control and how) and other setup parameters as required (such as delays or limits). Additional parameters to set, which are dependent on the Application and Output Configuration, may include: Run Actuator Runtime in seconds (AV24) AFF Air Flow Factor for VAV only (AV25) Min Minimum Air Flow for VAV and Damper Minimum for VVT (AV26) MAM Maximum Air Flow for VAV and Damper Maximum for VVT (AV27) The Temperature Units Setting (degrees C or F). Additional control settings, which are particularly useful when an Application is selected for local control, typically include: Set Day Setpoint (AV6) HI Max. Day Setpoint (AV8) DIF Day Differential (AV9) Pb CO Proportional Band (AV19) LO Min. Day Setpoint (AV7) rr CO Reset Rate (AV20) Page 4 of 35 Document Edition 3.1

Delta Controls Menu Item DSP Ser Lnt DNA Description The LCD Display Code Setting (AV15), a 4-digit value (ABCD) configures local display and button handling as follows: A Line 1 (Top Left i.e., Outside Value): 1 to 4 1 - Disabled 2 - Value from AV5 (i.e., remote value such as OAT) 3 - Value from AI2 (i.e., external sensor) 4 - Value from AI3 (i.e., Humidity) B Line 2 (Center i.e., Inside Value): 1 to 4 1 - Disabled 2 - Temperature from AI1 3 - Humidity from AI3 4 - Alternates between Temperature (AI1) & Humidity (AI3) C Line 3 (Bottom i.e., Setpoint Value): 1 to 5 1 - Disabled 2 - No Setpoint until an arrow button is pressed (adjustable) 3 - Setpoint is always displayed (adjustable) 4 - No Setpoint until an arrow button is pressed (not adjustable) 5 - Setpoint is always displayed (not adjustable) D House & Day/Night Mode Icons: 1 to 9 HOUSE OUTLINE ON/OFF TEXT MAN SUN/MOON 1 No No No No 2 No Flash No No 3 No Yes No No 4 No No No Yes 5 Yes No No No 6 Yes Yes No No 7 Yes Yes Yes No 8 Yes No Yes No 9 Yes No No Yes NOTE: When connected to LINKnet with V3.21 firmware/software the Display Code should be set to 1111. When connected to MS/TP, or LINKnet with V3.22 firmware/software or higher, the Display Code may be set to any valid value making it unnecessary to write GCL programs for display and button handling. Note that whenever an application is selected, a matching default Display Code is also set automatically (typically 1237), but this can be set to something else if so desired. The Service Tool Mode access setting (AV32) has the following options: 0 Disables all access to Service Tool Mode 1 Provides limited access for VAV, or full access for other applications 2 Provides full access with advanced Air Balancer functions for VAV The LINKnet Communications Setting (ON or OFF), to match the connection method. When turned ON the network communications is set to LINKnet, and when OFF the communications is set to MS/TP. The DNA Setting (ON or OFF), for inheriting a derived address from higher-up devices on an MS/TP network, or not, and is not an option when LINKnet is ON. Document Edition 3.1 Page 5 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide Menu Item Add SYS ArE OEM Description The device Address (1 to 99), which is used internally as the MAC Address. As the BACstat can only be a Subnet device on MS/TP, this address is always mapped in as the Subnet value. On LINKnet, this address is the physical address for the device (limited to 1 to 12) and the other address settings are irrelevant. Note: On MS/TP the complete BACnet address is in the form of OEM_Area_System_Subnet The System number (0 to 99), which can only be set manually when on MS/TP and DNA is turned OFF and is inherited when DNA is ON. The Area number (0 to 99), which can only be set manually when on MS/TP and DNA is turned OFF and is inherited when DNA is ON. The OEM number (0 to 3), which can only be set manually when on MS/TP and DNA is turned OFF and is inherited when DNA is ON. BAU The Network Speed (9.6 KB, 19.2 KB, 38.4 KB, or 76.8 KB). The default for both LINKnet and MS/TP is 76.8 KB. While the baud rate for MS/TP devices may need to be adjusted to suit, the speed for LINKnet networks should remain at 76.8 KB. End To exit the Configuration Menu (Yes or No). If you do not press a button within 1 minute the device will automatically exit and return to its normal display mode. NOTE: AI2 (and AI3 for the DNT-T221) are not configured through the Configuration Menu. These objects must be configured through the OWS (i.e., for Scale/Units) except when AI2 is used for VAV airflow. Refer to OWS Functions on page 30 for more information. SERVICE TOOL MODE (KEYPAD) Note that a new BACstat II Quick Reference Card for Service Tool Mode (product number REF-817) now exists for quick and easy reference for navigating and using the various Service Tool features. Although shipped with the product, additional copies can be ordered as necessary. 1. SERVICE TOOL MODE USER ACCESS & NAVIGATION Access to Service Tool Mode and its associated menu options is not protected by an access code or PIN. However, user access must be enabled (via AV32 or the setting located in the Configuration Menu) and the valid key sequence must be entered. To enter Service Tool mode, first press the Down Arrow (τ), and then the Up Arrow (σ), and hold them both down for at least 5 seconds (which is the opposite sequence to the Configuration menu). There is no PIN or password. Once you have entered the valid user key sequence you will gain access to Service Tool Mode, and SEr will be displayed immediately along with a main menu of several options. You may now use the up and down arrow buttons to navigate through the main menu options, and the NEXT or PREVIOUS buttons to penetrate deeper into their associated options. Once you have navigated to the desired item you wish to display or change, use the arrow buttons to make any necessary changes. Once the changes are made or you wish to move on, press NEXT or PREVIOUS. If at any time you do not press a button for 30 minutes, the BACstat will exit Service Tool Mode and return to normal display mode. Any outputs commanded manually will remain in manual, and a VAV box commanded to various Air Balancer modes (Minimum, Maximum, Close, Open, Zero Calibration) will also remain as commanded. A subsequent user command (CtL) is required to put the BACstat and associated outputs back under control (or Auto). 2. SERVICE TOOL MENU OPTIONS Service Tool Mode contains two menus: the Main menu and an Air Balancer menu (which is only available when the application is configured for VAV). Page 6 of 35 Document Edition 3.1

Delta Controls Service Tool Main Menu Options Menu Item SEr [Option] Description Displayed on line 2 of the LCD (center screen) to indicate you are at the Main menu of the Service Tool Mode. Service Tool Mode has these following main menu options, which you rotate through using the arrow keys. Press the NEXT or PREVIOUS buttons to select the option and penetrate deeper. CAL MAn bal End To calibrate Inputs AI1 to AI3 as compared to an external measuring device. Navigate past the inputs you don t wish or need to calibrate. To manually command AV1 to AV3 (0-100% for tri-state or PWM, and OFF or ON for binary outputs), associated with OP1 to OP3 respectively. This allows for end-to-end commissioning of output devices. Navigate past the outputs you don t wish or need to command. [When outputs are defined as tri-state in the Configuration menu, modifications can only be made to the primary output the other output cannot be modified.] To enter Air Balancing mode, which is only an option when VAV is selected as the Application in the Configuration Menu. To exit Service Tool mode (Yes or No). At any time within the Service Tool menus, if you do not press a button within 30 minutes the device will automatically revert to its normal temperature display mode (but retains manually commanded outputs and stays in any forced VAV box mode: MIN, MAX, CLOSED, OPEN). Air Balancer Menu Options Menu Item BA [Option] Description Displayed on line 1 of the LCD (top left) to indicate you are in the Air Balancer Mode. Air Balancer Mode has these following menu options, which you rotate through using the arrow keys. Press the NEXT or PREVIOUS buttons to penetrate deeper. AF MIn MAM CLO Opn CtL End Displays the current Air Flow, and penetrating deeper allows you to view the internal Air Flow Setpoint and the Air Flow Factor (with possible adjustment). Displays the current Minimum Air Flow setting, and penetrating deeper allows you to adjust the value and force the box to the minimum value. Displays the current Maximum Air Flow setting, and penetrating deeper allows you to adjust the value, force the box to the maximum value, and calibrate the display value to match a measured value. Penetrating deeper allows you to force the box fully closed and autocalibrate for zero flow. Penetrating deeper allows you to force the box fully open. Penetrating deeper puts the box back under control (releasing the box from forced modes: MIN, MAX, CLOSED, OPEN, or ZERO Calibrate). To exit Service Tool mode (Yes or No). At any time within the Service Tool menus, if you do not press a button within 30 minutes the device will automatically revert to its normal temperature display mode (but retains manually commanded outputs and stays in any forced VAV box mode: MIN, MAX, CLOSED, OPEN, or ZERO Calibrate). Document Edition 3.1 Page 7 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide INPUT CALIBRATION MS/TP CONNECTION The inputs are typically calibrated in their associated local AI objects. These same calibration fields are also mapped to variables (AV16 to 18) to provide access to other vendors in a multi-vendor installation, which can be also used to calibrate the inputs. Besides this, the inputs may also be calibrated right at the BACstat using the Service Tool Menu. LINKNET CONNECTION With local handling of the LCD display and buttons disabled (AV15 = 1111), the BACstat sends A/D values to its associated AI objects in the Application Controller, where calibration and filtering is applied. Calibrate the AI objects in the Application Controller. Do not calibrate the BACstats locally (via Service Tool Menu) or use the AV objects (mapped to AV16 to 18). With local handling of the LCD display and buttons enabled (AV15 > 1111), the BACstat sends actual values to its associated AI objects in the Application Controller all calibration and filtering is done in the BACstat. Calibrate the BACstats locally (via Service Tool Menu) or use the AV objects (mapped to AV16 to 18). Do not calibrate the AI objects in the Application Controller. INPUT SCALE RANGES Local Input Scale Ranges are selected by setting the units, from the following available options. Input Valid Units Scale Description Application Notes 1 C / F Standard 10K Thermistor (in ºC or ºF) Only available options for AI1. 2 C / F Standard 10K Thermistor (in ºC or ºF) Available whenever the VAV application is not enabled. % 0-5 or 0-10v input signal (depending on jumper) converted to a 0-100% value CFM / LPS Air Flow (in CFM or LPS) using a 0-1 DP Sensor (Kavlico or Setra) Available whenever the VAV application is not enabled. Fixed whenever the VAV application is enabled. 3 C / F Standard 10K Thermistor (in ºC or ºF) Available whenever the HUM application is not enabled. % 0-5 or 0-10v input signal (depending on jumper) converted to a 0-100% value %RH Built-in Custom Humidity Sensor (optional) Available whenever the HUM application is not enabled. Fixed whenever the HUM application is enabled. Unless inputs are multiplexed, many of the input units and associated scale ranges are automatically set when a built-in application is selected. Also refer to page 31 for configuring AI2 and AI3. MS/TP CONNECTION Only those units and associated scale ranges resident locally in the BACstat may be used. LINKNET CONNECTION With local handling of the LCD display and buttons disabled (AV15 = 1111), the AI objects in the Application Controller may be configured for any valid units and scale ranges that are available up in the Application Controller. With local handling of the LCD display and buttons enabled (AV15 > 1111), only those units and associated scale ranges resident locally in the BACstat may be used. Page 8 of 35 Document Edition 3.1

Delta Controls Software & Programming OBJECTS The following is a list of predefined or fixed objects that reside in the BACstat II products, which you cannot create or delete. When connected to an MS/TP network, these objects are readily accessible over the network. When connected to a LINKnet network, many of these objects are mapped into matching AI or AV objects residing in the Application Controller above. Object Name Description Default Value DEV1 BACstat * Device Object N/A AI1 Temperature Input 1 (10K Thermistor Value) N/A AI2 Input 2 * Input 2 (Available Input) N/A AI3 Humidity Input 3 (Humidity on DNT-T103) N/A Input 3 Input 3 (Extra Input on DNT-T221) N/A AV1 Output 1 * Output 1 (0 100%, Name Changes) N/A AV2 Output 2 * Output 2 (0 100%, Name Changes) N/A AV3 Output 3 * Output 3 (0 100%, Name Changes) N/A AV4 KeyPress KeyPress Value N/A AV5 External * External Object Value (i.e., OAT) N/A AV6 Day Setpoint Room Setpoint ºC = 21; ºF = 71; % = 30 AV7 Day Minimum Minimum Adjustable Day Setpoint ºC = 18; ºF = 65; % = 20 AV8 Day Maximum Maximum Adjustable Day Setpoint ºC = 25; ºF = 77; % = 55 AV9 Day Differential Room Setpoint Differential ºC = ±0.5; ºF = ±1, % = ±2.5 AV10 Night Heat Setpoint Night Setpoint for Heating (or Humidity) ºC = 16; ºF = 60; % = 30 AV11 Night Cool Setpoint Night Setpoint for Cooling ºC = 30; ºF = 86; % = 30 AV12 Application Control Application (Name Changes) None AV13 Alg Mode Algorithm Mode 0 (OFF or Night) AV14 Controller Status Status of Internal Control Loop N/A AV15 Display Code Local Display & Button Handling As per Control Application AV16 AI1 Calibration Input 1 Calibration (Temperature) 0.0 AV17 AI2 Calibration Input 2 Calibration (MUXed IP) 0.0 AV18 AI3 Calibration Input 3 Calibration (Humidity) 0.0 AV19 Proportional Band Control Loop Tuning Parameter ºC = 1; ºF = 2; % = 10 AV20 Reset Rate Control Loop Tuning Parameter 1.0 AV21 Output 1 Config Output 1 Configuration Variable As per Application Setup AV22 Output 2 Config Output 2 Configuration Variable As per Application Setup AV23 Output 3 Config Output 3 Configuration Variable As per Application Setup AV24 Setup 1 Setup Variable 1 (Name Changes) As required AV25 Setup 2 Setup Variable 2 (Name Changes) As required AV26 Setup 3 Setup Variable 3 (Name Changes) As required AV27 Setup 4 Setup Variable 4 (Name Changes) As required AV28 Setup 5 Setup Variable 5 (Name Changes) As required AV29 Setup 6 Setup Variable 6 (Name Changes) As required AV30 Baud Rate Network Baud Rate 76,800 bps AV31 PIN PIN (4-Bit Configuration Access Code) 1011 AV32 Service Tool Mode Service Tool Access Disable/Enable (0-2) 1 (or 2 when AV12 = VAV) AV33 Box Mode Heating & Cooling Modes for VAV/VVT 0 (Cooling) * Names are user settable (to a maximum of 8 characters), and only on outputs when they are controlled remotely (i.e., MUXed). These are the typical objects that may be commanded on-the-fly by a user or from GCL, and would also include the Outputs (AV1-3) when they are MUXed. Never command the Configuration Variables (AV12, AV21-13) on-the-fly. Refer to page 34. Document Edition 3.1 Page 9 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide NOTE: The DNS-24 model does not have any extra inputs, any outputs, and does not support control applications, so it only contains a subset of these objects (highlighted in bold). The DNT-T103 and DNT-T221 models support the full compliment. PROGRAMMING MS/TP CONNECTION Objects All of the existing predefined BACstat II objects are readily accessible over the MS/TP network. Control Applications BACstats with I/O may be configured to run one of seven possible built-in control applications. Another option disables local control altogether. GCL Programming BACstats are not programmable devices GCL does not reside in a BACstat. Rather, when connected to an MS/TP network you configure a BACstat for local operation and write GCL located elsewhere as necessary to do additional functions. In this way you configure the BACstat for local operation (both display & button handling and local control) and then write any necessary GCL in another controller for additional strategies. For example: Through the Configuration Menu, you typically configure the BACstat II display and buttons to functional locally, so GCL programs are not necessary for handling the display value or adjusting setpoint (i.e., AV15 = 1237). With a BACstat that has additional I/O, you may also select a suitable control application for local control. Then, using GCL programming located in another controller (i.e., DCU or other System Device) you make mode and setpoint changes based on Timeof-Day or other conditions. WITH V3.21 FIRMWARE: All GCL programming for mode changes, data exchange, and other strategies must be written in the DCU. WITH V3.22 FIRMWARE OR HIGHER: A DCU is no longer necessary and since data exchange is supported across MS/TP-based products, no specific GCL is required for this. GCL programming for mode changes, or other strategies may be written in any appropriate controller on the network. Refer to Appendix G in the V3.22 ORCAview Technical Reference Manual for further programming information, and the Programming Notes on page 34. LINKNET CONNECTION Device Limitations Note that there are inherent limitations to the total number of devices per LINKnet network, as well as the number of devices that have outputs. Refer to Appendix G in the V3.22 ORCAview Technical Reference Manual for further information. Objects Only the BACstat information that is represented by objects resident in the Application Controller is readily accessible over the network. The objects resident within each BACstat are not directly accessible to other devices in the system. To gain access to BACstat objects, you create objects in the Application Controller that correspond to the objects located in its respective BACstats. Page 10 of 35 Document Edition 3.1

Delta Controls Object Name Description Creation LCDx01 LinkLCD# Object for BACstat LCD & Button Presses Automatic AIx01, 02, 03 [User Specified] Matching object for the Input Value Manually AVx01, 02, etc. [User Specified] Matching object for the corresponding AV Manually where x refers to the device address (1 to 12) multiplied by 100. An LCD object is automatically created for each BACstat connected to the LINKnet network. However, the associated AI objects representing the room temperature in each BACstat must be created manually, and must follow a predefined numbering scheme. The object instance number is the LINKnet device address (1 to 12) multiplied by 100, plus 1. For example, you would create AI501 in the Application Controller to represent the 10K Thermistor value on a BACstat with a LINKnet device address of 5. With V3.22 loaded in the Application Controller, AV objects may be created in a similar fashion to the AI objects, which map to corresponding AV objects in the BACstat. You can then use these in GCL programming as well. With V3.21, mapped AV objects are not supported. Control Applications BACstats with I/O should have their built-in control applications disabled. If you wish to have BACstats running a local control strategy, then it should be connected to an MS/TP network instead. GCL Programming All GCL programming for BACstats on a LINKnet network is written in the Application Controller that the BACstats are connected to, using the mapped objects resident in the Application Controller. The LCD object is used for display and button handling. The mapped AI objects are used for reading values. And with at least V3.22 firmware on the Application Controller, the mapped AV objects are used for outputs, setpoints, and various other settings. WITH V3.21 FIRMWARE: When connected to LINKnet, local display and button handling should be disabled (i.e., AV15 = 1111), which is the default when you set the LINKnet Communications Setting to ON. This way, the LCD and buttons are fully accessible from the Application Controller for custom programming. Then, with GCL and the LCD and AI objects resident up in the Application Controller, you program the BACstat to operate as you want (similar to how ISTATs were programmed) all BACstat functionality is written in GCL located in the Application Controller. Note that none of the AV objects are accessible with V3.21 firmware. WITH V3.22 FIRMWARE OR HIGHER: You may disable local display and button handling (i.e., AV15 = 1111) and program everything in GCL in the Application Controller as previously described for V3.21 firmware. Or, by setting the Display Code to something other than 1111, the display and buttons may be configured to function locally and GCL commands from the Application Controller for display and button handling (via the LCD object) are ignored. This may be the preferred method as no GCL needs to be written to handle setpoint adjust and the display of values on the LCD. In addition to this, BACstats with outputs may be controlled as MUXed outputs through corresponding AV objects (AV1-3). And the setpoints and other settings are also accessible through their corresponding AV objects. Refer to Appendix G in the V3.22 ORCAview Technical Reference Manual for further programming information, and the Programming Notes on page 34. Document Edition 3.1 Page 11 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide Control Functions OVERVIEW 1. CONTROL APPLICATIONS (DNT-T103 AND DNT-T221 ONLY) When connected to an MS/TP network, the DNT-T103 BACstat may configured to operate according to one of 8 possible application control strategies, and displayed in the Application variable (AV12). Application Description AV12 None (MUX) Provides remote control of the outputs from another device. 0 VAV Provides control of a simple VAV box and optional fan. 1 VVT Provides control of a simple VVT box and optional fan. 2 HPU Provides control of a Heat Pump Unit with a reversing valve and a fan. 3 FCU Provides control of a Fan Coil Unit with heating/cooling and a fan. 4 Unit Heater No longer supported. Use FCU instead. Radiation/Reheat Provides control of single or multi-stage heating with no fan. 5 Humidity Provides control of a Humidifier and assumes a model of the BACstat with a humidity sensor. Refer to the Application section of this guide for further detail on each of these control strategies, starting on page 18. 6 2. ALGORITHM MODE The application control strategy operates in one of various basic modes, as determined by the Algorithm Mode variable (AV13). Algorithm Mode Description AV13 Unoccupied (Night) Uses Night Setpoints 0 Occupied (Day) Uses Day Setpoints 1 Minimum VAV Only: Forces the box to its minimum position 10 Maximum VAV Only: Forces the box to its maximum position 11 Closed VAV Only: Forces the box to its fully closed position 12 Open VAV Only: Forces the box to its fully open position 13 Zero Calibration VAV Only: Forces calibration of the bias so the air flow reads zero at current conditions. This assumes that the Air Handler has been shut down and that there is no air flow at the box. 14 Heating Lockout Cooling Lockout All heating control and associated icons are completely disabled (as though no heating stages even exist) All cooling control and associated icons are completely disabled (as though no cooling stages even exist) Heating/Cooling Lockout Both heating and cooling control and their icons are disabled 22 Unless the fourth digit of the Display Code (AV15) is set to 1 or 5, or Fan Control is configured as Manual, the top two buttons on the BACstat OFF (O) and ON (I) will switch between Night and Day modes. Changing to the other modes for VAV is keypad accessible in Air Balancer mode within the Service Tool menus. The Alg. Mode (AV13) is also fully accessible from another device over the network (via GCL or ORCAview OWS or 3 rd Party devices), to command it to any mode as required (including the lockouts). 20 21 Page 12 of 35 Document Edition 3.1

Delta Controls Lockout Modes Heating and cooling lockout modes are operational for all Control Applications. Basically, once a BACstat has been configured for various stages of heating and cooling, either the heating and/or cooling may be disabled on-the-fly as necessary for various control strategies simply by commanding the Alg. Mode (AV13). In all other regards, control continues to function the same as it would when in Occupied mode. Communications Reset Enable The Algorithm Mode variable also has a property represented by a checkbox in the object dialog called Comm Reset Enable. This can be enabled or disabled, depending on the requirements of the installation. Disabled The BACstat does not try a reset on the loss of communications Should the device reset, the mode reverts to whatever it was just prior to the reset (i.e., last value as stored in non-volatile memory) Enabled (the default as of Release 3 Firmware) The BACstat will reset once on the loss of communications to try to re-establish communications Should the device reset, the mode is set to DAY 3. BOX MODE (DNT-T103 AND DNT-T221 ONLY) When the application control strategy is configured for either VAV or VVT, the Box Mode (variable AV33) can be set to either cooling (default) or heating. When set to cooling, the air supply is treated as the first stage of cooling. When set to heating, the cooling controller is inverted and the air supply is treated as the first stage of heating. Box Mode Description AV33 Cooling Duct Supply Air to the box provides cooling (default) 0 Heating Duct Supply Air to the box provides heating 1 Note that this variable cannot be commanded or changed from the BACstat. As this function is completely dependent on the air supplied to the boxes from another source, this variable would normally be commanded over the network (i.e., typically via GCL) whenever the air system changes between heating and cooling. NOTE: In Release 3, VAV and VVT applications can no longer be configured with more than 1 stage of cooling. In earlier releases of firmware, do not configure a BACstat with more than 1 stage of cooling, as additional stages of cooling don t work properly when Box Mode is ever set to heating. SOFTWARE LOOP CONTROLLER (DNT-T103 and DNT-T221 Only) 1. GENERAL The operation of the BACstat II is centered around a software controller. The controller uses the following parameters in its operation. Parameter Object Default Value Notes Room Temperature AI1 N/A Input 1 ** Temperature Setpoint* OCCUPIED: Uses Day Setpoint (AV6) UNOCCUPIED: Uses Night Heat Setpoint (AV10) if the Input is below the Day Setpoint (AV6); and uses the Night Cool Setpoint (AV11) if the Input is above the Day Setpoint (AV6); otherwise it is in a null zone. Proportional Band AV19 4.0 ºF / 2.0 ºC Degrees F or C as configured for AI1 Reset Rate AV20 1.0 Resets per hour Day Differential AV9 1.0 ºF / 0.5 ºC Degrees F or C as configured for AI1 * Humidity Setpoint if operating as a Humidity controller ** Input 3 (AI3) if operating as a Humidity controller Document Edition 3.1 Page 13 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide 2. CONTROLLER OPERATION 100% NORMAL CONTROLLER ACTION -100% Controller Output (Heating) Deadband Day Differential Controller Output (Cooling) Heating Cooling 0% Temperature 0% Proportional Band Proportional Band Heating Setpoint Day Setpoint Cooling Setpoint Deadband is a span of 0.2 around setpoint (heating or cooling) over which neither heating nor cooling takes place. Here are a few rules and restrictions to how the internal Loop Controller functions: Heating and Cooling will not be ON at the same time If the Input temperature is less than (Day Setpoint (Day Differential ½ Deadband)) then the controller is in HEATING If the Input temperature is greater than (Day Setpoint + (Day Differential + ½ Deadband)) then the controller is in COOLING If the Input temperature is between these two extents for Heating and Cooling, then the controller is in A null zone For all control applications (except when Box Mode is heating in VAV or VVT) the Controller Status (AV14) will modulate from -100 to 100% and sequence any necessary output stages. A value of 0 to 100% represents heating output from the controller, while a value of 0 to -100% represents cooling output from the controller. 200% WITH BOX MODE = HEATING Day Differential 100% Auxilary Heating Controller Output Flow Damper Deadband 0% Temperature Proportional Band Proportional Band Heating Setpoint Day Setpoint Cooling Setpoint Page 14 of 35 Document Edition 3.1

Delta Controls For VAV or VVT applications, when the Box Mode is changed to heating, cooling is inverted and used for controlling the flow damper as the first stage of heating, and the null zone is placed on the far right. Moving from right to left, away from setpoint, the Controller Status (AV14) will modulate from 0 to 200% and sequence all the necessary heating stages. The flow damper modulates open over the first 0 to 100% and in so doing provides the first stage of heating. Any additional stages of heating modulate open over 100 to 200%. Therefore, only when the Box Mode is in heating does the Controller Status (AV14) modulate to a value greater than 100%, where 200% indicates all heating is fully open. For heating lockout (in all applications), the heating output from the controller is forced to 0%, and the heating icon is disabled on the LCD. Similarly, for cooling lockout, the cooling output from the controller is forced to 0%, and the cooling icon is disabled on the LCD. As a result, the Controller Status (AV14) will be limited accordingly. 3. CONTROLLER STAGING Each controller can be split up into as many as three stages. The number of stages is automatically determined by the output configuration associated with the selected application control strategy. The controller stages are cascaded. 100% Cooling Controller 0% 100% 0% C1 C2 C3 4. RESET ACTION (RESET RATE IN REPEATS PER HOUR) If the Reset Rate is non-zero, reset action is enabled. As long as there is a difference (or error) between the input value (i.e., space temperature) and setpoint value, reset action will increment or decrement the Controller Status value (AV14) over time - in proportion to the value of the reset rate and the magnitude of the error - in an attempt to remove the error. In this way, the Controller Status value is continually fluctuating in order to reach setpoint. Also note that the amount of reset does not decrease internally as the input value approaches setpoint, but the reset value is frozen while in deadband. The only time reset action has no affect on the controller output is when the input is equal to the setpoint (no error). For this reason, be cautious about applying too much reset action, otherwise you may cause unnecessary movement on actuators. By setting Reset Rate to 0, you disable reset action altogether. Document Edition 3.1 Page 15 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide SETPOINTS The BACstat II uses a series of setpoints for various purposes, most of which interact with one another. For a complete list of these setpoints and other objects and their defaults, refer to the Object table on page 9. It is important to note that when you change the units setting between ºC and ºF all of these setpoints will revert back to their matching default values the BACstat does not do a conversion on-the-fly. What follows hereafter is a working description for each of these setpoints. If the particular setpoint is settable in the Configuration Menu it is indicated with its LCD text. Day Setpoint (AV6) SEt This is the setpoint used when in DAY mode. With the Display Code (AV15) set to an appropriate value the setpoint can be adjusted up or down by pressing the buttons. Whether or not this setpoint is displayed or is adjustable on the LCD, it is used internally for control. The units for the setpoint are ºC or ºF (as per AI1) unless the second digit of the Display Code (AV15) is set to 3 (for Humidity), in which case the units become %RH. The value for Day Setpoint can also be set in the Configuration Menu, or by commanding the variable (via GCL or ORCAview OWS or 3 rd Party devices). Day Minimum Setpoint (AV7) LO This is the minimum value a user can adjust the Day Setpoint to. If an attempt is made to adjust the Day Setpoint lower, it will not change. If a lower value is commanded from the OWS or another device, it will not accept the change. The value for Day Minimum Setpoint can be set in the Configuration Menu, or by commanding the variable (via GCL or ORCAview OWS or 3 rd Party devices). Day Maximum Setpoint (AV8) HI This is the maximum value a user can adjust the Day Setpoint to. If an attempt is made to adjust the Day Setpoint higher it will not change. If a higher value is commanded from the OWS or another device, it will not accept the change. The value for Day Maximum Setpoint can be set in the Configuration Menu, or by commanding the variable (via GCL or ORCAview OWS or 3 rd Party devices). Day Differential (AV9) DIF This is the differential setting between the Day Setpoint and the internal Heating Setpoint (which is used for heating control), and between the Day Setpoint and the internal Cooling Setpoint (which is used for cooling control). The one value is used for both, one on each side of the Day Setpoint. Refer to the diagram on page 14. The purpose of this setting is to separate heating from cooling so as to prevent overlap, and to create a reasonable null zone, within which no modulating control takes place preventing unnecessary actuator wear when the measured value is close to or on setpoint. The value for Day Differential can be set in the Configuration Menu, or by commanding the variable (via GCL or ORCAview OWS or 3 rd Party devices). Day Heating Setpoint (Internal) This is the setpoint used internally for heating control (which is the Day Setpoint - Day Differential). This value is not directly adjustable. It can only be adjusted by setting either the Day Setpoint or the Day Differential. Day Cooling Setpoint (Internal) This is the setpoint used internally for cooling control (which is the Day Setpoint + Day Differential). This value is not directly adjustable. It can only be adjusted by setting either the Day Setpoint or the Day Differential. Page 16 of 35 Document Edition 3.1

Delta Controls Night Heating Setpoint (AV10) This is the setpoint used when in NIGHT mode and night setback heating is required. If the current temperature is below the current Day Setpoint when in NIGHT mode, this value will be displayed on the BACstat LCD (depending on how setpoint display has been defined by the Display Code). Please note that this value is not adjustable either by a user or through the keypad in any Configuration or Service menu. It can only be changed by commanding the variable (via GCL or ORCAview OWS or 3 rd Party devices). Pressing the up or down arrow will cycle to show the Night Cooling Setpoint. Night Cooling Setpoint (AV11) This is the setpoint used when in NIGHT mode and night setback cooling is required. If the current temperature is above the current Day Setpoint when in NIGHT mode, this value will be displayed on the BACstat LCD (depending on how setpoint display has been defined by the Display Code). Please note that this value is not adjustable either by a user or through the keypad in any Configuration or Service menu. It can only be changed by commanding the variable (via GCL or ORCAview OWS or 3 rd Party devices). Pressing the up or down arrow will cycle to show the Night Heating Setpoint. CONTROL DIAGRAM (DNT-T103 and DNT-T221 Only) The following diagram helps to provide an illustration of the relationship between the internal software loop controller and various objects, including outputs. Output 1 Binary (Dir or Rev) Input (AI1) Setpoint (AV6) BACstat Buttons (or remote command via GCL or OWS) Controller & Sequencing Algorithm Mode (AV13) Heating Heating Stage 1 (H1) Heating Stage 2 (H2) Heating Stage 3 (H3) Cooling Fan Cooling Stage 1 (C1) Cooling Stage 2 (C2) Cooling Stage 3 (C3) Constant Fan Operation (C) Intermittent Fan Operation (I) PWM (Dir or Rev) Analog (Dir or Rev) Analog VAV Flow Damper Tri-State Actuator Tri-State VAV Flow Damper Output 2 Binary (Dir or Rev) PWM (Dir or Rev) Analog (Dir or Rev) Time Proportioned (D or R) Tri-State Actuator Tri-State VAV Flow Damper Manual Fan Operation (M) Notes: 1. indicates the output type is only applicable for the DNT-T103. 2. indicates the output type is only applicable for the DNT-T221. 3. An analog output type for outputs 1 & 2 on a DNT-T221 when HPU has been selected provides a 0 or 10v signal - it is not a 0 to 10v signal nor a dry contact. 4. The output functions and types that are available are dependent on the control application selected and what was selected for the previous output. 5. This is not a comprehensive diagram and does not include all output functions. Refer to Output Functions and Types later in this document. Output 3 Binary (Dir or Rev) PWM (Dir or Rev) Time Proportioned (D or R) Binary Fan (On/Off) Document Edition 3.1 Page 17 of 35

Error! No text of specified style in document. DNS-24, DNT-T103, & DNT-T221 Application Guide CONTROL APPLICATIONS (DNT-T103 and DNT-T221 Only) 1. NONE (or MUX) [Application (AV12) = 0] Function: No local control strategy, allowing the outputs (via AV1 to AV3) to be directly controlled from a remote device. Triac outputs may be configured as Binary (which are not delayed; their values are transferred immediately upon being received), PWM, and Tri-state (on Outputs 1 & 2). Analog outputs may be configured for 0-10v actuators (DNT-T221 only). Outputs configured as Pulse Width Modulation require that their Low and High variables are appropriately configured for the particular type of device the outputs are connected to. Default values of 59 and 293 are suitable for Belimo PWM actuators (representing 0.59 and 2.93 seconds respectively). Outputs 1 and 2 configured as a Tri-State pair require that the Tri-State Runtime (AV24) be configured for the associated Tri-State actuator. The default of 120 seconds is suitable for certain Honeywell actuators. NOTE: BACstats (particularly with I/O) that are connected to a BACnet MS/TP network are designed to operate as stand-alone devices using a local control application. For custom applications and MUXing purposes, connect the BACstat to a LINKnet network. 2. VAV [Application (AV12) = 1] Function: Control of a simple VAV box with air flow measured with a Kavlico sensor (DFT740-A) or Setra sensor on Input 2 (0 to 1 range), a Tri-State damper on Outputs 1 and 2 (for DNT-T103) or an analog damper on Output 1 (for DNT-T221), and various options on the remaining outputs (some no longer available in Release 3). DNT-T103 I/O (Outputs 1 to 3 are Triacs) Input AI1 Input AI2 Input AI3 Remote AV5 Output 1 Output 2 Output 3 Room Temp. Air Flow N/A Optional OAT Tri-State Flow Tri-State Flow Heating 1 (0 to 1 ) Damper (Open) Damper (Close) Room Temp. Room Temp. Room Temp. Air Flow (0 to 1 ) Air Flow (0 to 1 ) Air Flow (0 to 1 ) N/A Optional OAT Tri-State Flow Damper (Open) N/A Optional OAT Tri-State Flow Damper (Open) N/A Optional OAT Tri-State Flow Damper (Open) DNT-T221 I/O (Outputs 1 & 2 are Analog, and Output 3 is a Triac) Tri-State Flow Damper (Close) Tri-State Flow Damper (Close) Tri-State Flow Damper (Close) Cooling 2 (not in R3) Fan None (MUX) Input AI1 Input AI2 Input AI3 Remote AV5 Output 1 Output 2 Output 3 Room Temp. Air Flow N/A Optional OAT Analog Flow Heating 1 Heating 2 (0 to 1 ) Damper Room Temp. Room Temp. Room Temp. Room Temp. Room Temp. Room Temp. Room Temp. Air Flow (0 to 1 ) Air Flow (0 to 1 ) Air Flow (0 to 1 ) Air Flow (0 to 1 ) Air Flow (0 to 1 ) Air Flow (0 to 1 ) Air Flow (0 to 1 ) N/A Optional OAT Analog Flow Damper N/A Optional OAT Analog Flow Damper N/A Optional OAT Analog Flow Damper N/A Optional OAT Analog Flow Damper N/A Optional OAT Analog Flow Damper N/A Optional OAT Analog Flow Damper N/A Optional OAT Analog Flow Damper Heating 1 Cooling 2 (not in R3) Heating 1 Heating 1 Cooling 2 (not in R3) Cooling 2 (not in R3) Cooling 2 (not in R3) None (MUX) Fan None (MUX) Heating 1 Fan None (MUX) None (MUX) Page 18 of 35 Document Edition 3.1