Generator Speed Controller Model GSC 1

Similar documents
Electronic Amplifier Model VT 3017 and VT 3018 (Series 3X) for the control of proportional directional valves, without positional feedback

2-Way Proportional Logic Cartridge Valve Model FE.. (Series 1X and 2X) PSI (315 bar) F with electrical connection 12 X Y

AF91 Adjustable Frequency Drives Series B

Electronic amplifier for the control of proportional valves without position control Model VT 3024, Series 3X H/A 4149/94 VT X

Electronic amplifier for the control of proportional valves without position control Model VT 3006, Series 3X H/A 4240/94 VT X

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A.

RA / /6. Replaces: Table of contents RA /06.98

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939)

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

DLVP A OPERATOR S MANUAL

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR)

815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS

Ordering Part Numbers: SAE J1939 version Controller: AX022400

Programmable with Electronic Assistant Simulink

1525-BRS INFORMATION MANUAL SERV O D YN A M ICS. D y n ad r iv e Ave Crocker Suite 10 Valencia, CA

Applications: oil and gas equipment automation; off-highway machine automation; agricultural equipment

TECHNICAL DATASHEET #TDAX INPUTS, 5 OUTPUTS VALVE CONTROLLER

Optidrive Applications Support Library

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

TOSHIBA International Corp

GS1 Parameter Summary Detailed Parameter Listings...4 9

OVEN INDUSTRIES, INC. Model 5C7-362

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Looking For A High Power, Low Profile Power Supply? KEPCO. Has More Than One Way To Help Make Your Decision Easier! AN ISO 9001 COMPANY

LA-5000 SERIES LINEAR VALVE ACTUATORS

SixPac Series of SCR AC Controller and DC Converters

4-Way Servo Valve Model 4 WS. 2 E , (Series 2X) with Mounting Pattern to DIN or CETOP RP 115 H PSI (315 bar) H/A 3012 H/A 3013

B25A20FAC SERIES BRUSHLESS SERVO AMPLIFIERS Model: B25A20FAC 120VAC Single Supply Operation

TECHNICAL DATASHEET #TDAX CAN SAE J1939, Dual Output Valve Controller

Fuzzy Temperature Controllers E5AF

DynaDrive INFORMATION MANUAL SDFP(S)

TECHNICAL DATASHEET #TDAX QUAD VALVE CONTROLLER P/N: AX SERIES

Product Specification

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

FEATURES DESCRIPTION THE OEM ADVANTAGE

3050 Stereo Power Amplifier

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

TECHNICAL DATASHEET #TDAX021901

The new Yaskawa Varispeed G7 Inverter

6.9 Jump frequency - Avoiding frequency resonance

HB-25 Motor Controller (#29144)

SC1000 DGPS USCG Dual Transmitter

S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

Multi-function, Compact Inverters. 3G3MV Series

TECHNICAL DATASHEET #TDAX022420

MDSD (Series 2X) Mobile Dual Solenoid Driver

New Eagle PWM to Analog Converter

E3 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

Before you operate the inverter, the parameters that you must first program are the basic parameters.

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

S, SX & SXF Series S, SX & SXF. Packaged. Packaged Microstepping Systems. The X Series... An Indexer and Drive

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

The MP SERIES CONTROLLER. User s Manual. ISE, Inc.

MODEL KBWD-15 Pulse Width Modulated (PWM)

Fan and Pump AC Inverter

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

SPECIFICATION NO Model Automatic GTAW Welding System

Applications: Power generation, Cogeneration, Stationary power Large engines

SECTION AUTOMATIC TRANSFER SWITCH

Compact, Low-Cost Solutions

SHI Series Pure Sine Wave Inverter (SHI2000 AND SHI3000) User s Manual

Sealed Interface Control: EC20300

Peak Current. Continuous Current. See Part Numbering Information on last page of datasheet for additional ordering options.

TECHNICAL DATASHEET #TDAX INPUT, 12 OUTPUT VALVE CONTROLLER,

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS

SOUTHERN AVIONICS COMPANY. SE125 Transmitter. SE125 Transmitter 1-1

GEMINI PRESETTABLE DUAL RATE INDICATOR WITH RATIO (A/B)

VF-nC1 Adjustable Speed Drive Engineering Specification

Section 11 Electronic Position Controls & Encoders

BATCHMATE 1500 Batch Control Computer Technical Bulletin

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

The SSR P Series. Phase-Fired SCR Power Controllers. for resistive heating loads. Phase-Fired SCR Power Controllers AMPS VAC

Applications: Off-highway construction equipment Municipal vehicles Material handling equipment (forklifts, etc.) Ordering Part Numbers:

Design Specifications Operator Keypad Environmental and Operating Conditions

Installation, Operation and Maintenance Manual

IRT AT-Small. Technical Manual. quality IN MOTION. quality IN MOTION

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Rotek AS440 compatible VOLTAGE REGULATOR (AVR)

Boulder W Mono Power Amplifier

Boulder W Class A Stereo Power Amplifier

P/N: AX TECHNICAL DATASHEET #TDAX Single Input, Dual Output Valve Controller 1 Universal Input, +5V reference CAN (SAE J1939)

GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR)

PAM & SAM System User s Manual

DVC700 Series Programmable System Controller

BLuAC5 Brushless Universal Servo Amplifier

HAWK5000 Operators Manual

This convection-cooled series is designed for use in commercial and industrial environments in temperatures up to 50 C.

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

SPECIFICATION, CONTROLS AND ACCESSORIES

Transcription:

enerator Speed Controller odel SC 1 RA 29 977/09.95 Replaces: 4.92 Self contained controller for driving electrical power generators with a hydrostatic transmission 16 Bit microprocessor based controller 50 or 60 hertz generator operation Tunable PID controller to accommodate a wide range of pump/motor/generator combinations Fault safety shutdown Simple machine interface echanical and electrical "plug-in" compatability with the Rexroth SC1-1X controller enerator Speed Control SC-2X Features Internal alpha numeric display and keypad for setup and diagnostics enu based setup Descriptive display of faults Accepts a wide range of battery voltages 120 or 240 volt AC generator operation, 50 or 60 Hz Start/Stop external control with momentary pushbuttons and standard 3 wire circuit enerator safety shutdown for under/over frequency and generator output over voltage External LED indicators for enerator Run and Fault Frequency accuracy +/ 0.5 Hz Fine frequency trim Uses battery voltage for starting and generator power during running Self contained in water resistant enclosure with interface connector Requires only 2 wires to pump Radio frequency interference (RFI) filter for high noise environments Ordering code SC 1 2X 120 1 enerator Speed Controller Series 20 to 29 =2X (20 to 29 externally interchangeable) Running voltage (120 VAC/50-60 Hz) = 120 Running voltage (240 VAC/50-60 Hz) = 240 = * Further details to be written in clear text 1 = With RFI filter * ating Connector is included *14 pin S connector 1

Functional description The Rexroth SC-2X generator speed controller provides constant drive speed for an AC power generator. enerator speed is controlled to provide accurate frequency independent of changes in load and power take-off (PTO) drive speed. The controller operates by modulating the stroke of a Rexroth A4V transmission pump, with proportional solenoid control. The pump is typically driven by a diesel engine PTO. The pump flow hydraulically drives a fixed displacement Rexroth A2F hydraulic motor which is coupled to the AC generator. The generator speed feedback is by means of a magnetic pulse pickup, or by the generator s output frequency. If a magnetic pickup is used, a fan blade or toothed wheel normally provides a pulse signal to the magnetic pickup. If the generator frequency is used as the speed feedback, the magnetic pickup can optionally be used to provide drive (diesel) RP to the controller. This provides a feedforward control signal to improve response time to PTO speed changes. Power for the controller is provided in two ways. During starting, available engine battery voltage, in the range of 10 to 35 volts DC, is used to provide power to start the drive. Once the generator is running at sufficient speed, the AC output from the generator supplies the running power to the controller. enerator outputs of 120 or 240 volts AC can be accommodated. The voltage range is configured at the factory and must be specified on the order. The generator drive can be started and stopped remotely with a momentary pushbutton control circuit. For safety considerations, the stop pushbutton uses a normally closed circuit, so that interruption of the stop circuit will cause generator shutdown. During starting, the generator speed is ramped up to proper running speed, at a preset ramp rate. When speed is reached the controller is enabled. If the stop circuit is interrupted, the generator is ramped to a controlled stop. The controller also contains a temperature sensor that is used to measure ambient temperature. A startup mode can be selected that allows the generator starting conditions to be dynamically altered as a function of temperature. Lengthened ramp up time and altered starting PID tuning parameters can be selected as cold startup options. This mode provides compensation for changes in the hydraulic fluid viscosity, as well as providing slower startups to allow time for warm oil to circulate through the hydrostatic loop. Controller operation When DC power is applied to the SC controller, the microcontroller is activated and performs a power on self-test (POST). All parameters are then read from the EEPRO parameter storage memory. The control inputs are active at this time. Any error detected at this time, such as a parameter memory error or POST error, will be displayed on the internal readout. When the Start input is activated, several conditions must be met before the generator will start. There must be no errors that would prevent a startup, such as a memory error. Additionally the DC battery voltage must be over 9.4 volts to enable a start. Finally the Stop input must be on (closed circuit) to start the generator drive. If the above criteria is met, the controller will supply current to the A4V proportional solenoid to drive the pump on stroke. The ramp up rate (stroke rate), minimum and maximum proportional solenoid currents, as well as the proportional solenoid PW frequency are set as parameters in the controller. As the pump strokes and the generator starts rotating, the generator speed is measured by the controller. This speed signal comes from a predetermined option of either a pulse pickup or the AC voltage out of the generator. If a pulse pickup is used for generator speed feedback, the controller can be set to accept 1 to 200 pulses per revolution, corresponding to a nominal speed of 1800 RP (1500 RP in 50 hertz mode). As the pump stroke is increased, a check is made by the controller to determine that the feedback signal is present. If no speed feedback signal is detected, the controller causes a shutdown of the start sequence and a FEED- BACK FAIL fault is displayed. If feedback is present, the pump stroke is increased until the measured generator speed (frequency) is near the desired setpoint. At this point the closed loop PI controller is activated and takes over control of the pump stroke. The transition from ramp up to closed loop is smooth and shock free. The controller then regulates the pump stroke to maintain the generator rotational speed at the desired setpoint. The speed setpoint can be set to a nominal value of 50 or 60 hertz, with a +/- 10 hertz fine frequency trim from the setpoint. The measured speed is constantly compared with the setpoint and differences between these two values results in direct and time based corrections to the pump stroke. As a result, the generator is driven at a constant speed as load and pump input RP changes. While running, the generator speed and generator output voltage are monitored and compared to preset limits. If the generator speed varies from the setpoint by the preset value, a fault shutdown of the generator occurs, and the fault is displayed on the controller s display. The frequency fault can be disabled, if desired. The AC voltage into the controller is also measured and compared to a setpoint. If the AC voltage from the generator exceeds a preset limit, an overvoltage shutdown fault occurs, and the fault is displayed. The overvoltage fault can be disabled, if desired. The response time of the overvoltage fault can be selected between slow and fast response, to match the response time of the generator regulator, and to prevent false shutdown tripping. If the stop input is opened (no signal), the speed controller is shut down and the pump stroke, and thus the generator speed, is ramped down to a stop. Two additional modes of operation are provided. If generator AC frequency is used as the controller feedback, the pulse pickup input can be used to measure the PTO or prime mover speed, for feedforward control. In this mode of operation, changes in PTO speed cause a direct change in pump stroke, rather than generator speed error causing the correction. This results in quicker response to PTO speed changes. The feedforward compensation can be adjusted with a parameter in the controller. A manual mode is also provided. In the manual mode, the pump stroke is ramped to a preset value when the start circuit is activated. This mode provides no corrections from any feedback signal and is intended as a troubleshooting and diagnostic tool. anual mode can also be used as a drop dead mode of operation, if hardware failures prevent normal operation. Varying the stroke value or the PTO speed is necessary to set the correct generator drive RP. In cold starting conditions, the drive system performance may be affected by changes in the hydraulic fluid viscosity, as well as changes in other mechanical components. To compensate for these variations, the ambient temperature at the controller is measured. The measured temperature can be used to modulate the controller s speed control tuning parameters, as a function of 2

Controller operations (continued) RA 29 977/09.95 temperature. As the controller self heats, the parameters are slowly returned to normal running values. During this time the hydraulic and mechanical components are also warming as the generator is run. There is also a provision to slow the starting ramp up rate as a function of temperature. This feature allows the hydrostatic transmission to be started slowly, allowing the oil to warm the loop as the system slowly accelerates. Starting ramp rates of over 4 minutes can be selected. The controller contains other features to assist in set up and maintenance of the generator system. The controller s display can be selected to display system information when the generator is running. enerator AC frequency, generator AC output voltage, DC battery input voltage, ambient temperature and pump stroke proportional solenoid current can be displayed on the controller s display. Additionally, an analog output signal is provided for connection to an oscilloscope, chart recorder or data measurement system. The analog output can be selected in the controller to indicate frequency error, magnified frequency error (error X 10), speed controller output, proportional error correction, integral error correction, proportional solenoid command value, proportional solenoid actual current and generator speed feedback. The output can be changed at the controller and is always present. A communications port is also available at the controller for remote diagnostics and setup. CAUTIO: Instability may occur with generators exhibiting harmonic distortion. AC feedback will not work with generators that have significant distortion of the AC sine wave. Use Pulse feedback unless performance is proven satisfactory with your generator and AC feedback. Technical data (for operation outside these parameters, please consult us!) Power supply Starting VDC + 10 to 35, negative ground 2 Amp maximum Running VAC 120 to 240, 50/60 Hz ± 10% 50 VA maximum Output Drive A Up to 2.5 maximum to drive A4V pump solenoid, current controlled, Pulse Width odulation 80 to 250 Hz Frequency control range Hz 50 or 60 ±0.5 Hz (±10 Hz adjustment) Load response 15 kw load step, ±1% Hz error, recovery to steady state typical Speed Input change of 1000 rpm/sec. cause max of ±3 Hz frequency change, recovery to steady state START/STOP change response sec. Start/stop in 1 sec. typical. Settle to stable speed 2 sec. START/STOP circuit requirements 3 wire, 12 VDC control, optically isolated inputs, 15 ma max. Frequency shutdown Hz Selectable up to 30 Hz deviation Overvoltage shutdown VAC Selectable 0 300 Pulse pickup input VAC 5 to 30 any non-monotonic waveshape LED output ma 10 nominal, short circuit proof Setup interface Alpha-numeric display, 4-character, red LED 4 pushbuttons up, down, enter, escape Communications port RS-485, 19,200 baud Enclosure EA 12, screw cover plate Ambient temperature F ( C) 0 to 140 ( 18 to 60) Connector ultiturn Type SC / S3102E22-19P ating connector S3106E22-19S Size (approximately) in (mm) 9.25 x 6.25 x 3.50 (235 x 159 x 99) Weight (approximately) lbs (kg) 10 (4.54) ounting position Optional 3

enerator speed controller block diagram: dimensions in inches (millimeters) SC 1-2X Up Down Enter Etc. P1 RS485 (+) (-) 1 2 3 Display Start*.O..C. (momentary) External Fault LED* External Run LED* (ote 2) 0v Stop* Proportional Solenoid K L P H J 0V FAIL RU I V RS 485 +V +5v icrocontroller J1 emory J 3 Testpoint 0 to 5V F 0v 3A 0v AC ~ E A B) C) D F agnetic Device (if used) + _ Battery 10 to 35VDC 2A Power Frame 120/240 VAC round 50/60Hz 50VA L 1 E P Control L 2 Fuse* L 1 Fuse* Feedforward a b R T 1 T 2 P S F a F a1 F e B B AC 2 Pulse AC 1 (ote 3) VAC A X 1 X 2 H S F S A 4 otes: 1) * Items are customer supplied 2) Install external LED or jumper to 0v. 3) Dual element, time delay fuse recommended for 240 VAC. 4) J 1 is shorted for 120 VAC Scaling. J 2 is open for 240 VAC Scaling

Unit dimensions, S and KPSE connectors: dimensions in inches (millimeters) RA 29 977/09.95 Ø 0.31 (7.9) 4 Places Circular Connector A B D agnetic pickup C Battery positive 8.00 (203) 8.75 (222.3) 9.50 (241) D E F Frame ground Battery negative (Chassis) 120/240 VAC H J Pump proportional solenoid Start Stop K (.O.) (.O.) 4.00 (101.5) 5.00 (127) 6.25 (159) L P Fault LED en. run LED 3.50 (89) 2.00 (50.8) Type Box receptacle ating connector 6.00 (152) 2.00 (50.8) 12 auge SC / S3102E22-19P S3106E22-19S ating connector is supplied. Circuit Board "1" RFI Filter Field Connector 11 A 10 * B 12 * C 13 * D 14 * E 15 * F 16 * 5 H 6 * J 2 * K 3 * L 1 * 7 * 4 * P * *= Capacitator to ground 5

6 annesmann Rexroth Corporation Rexroth Hydraulics Div., Industrial, 2315 City Line Road, Bethlehem, PA 18017-2131 Tel. (610) 694-8300 Fax: (610) 694-8467 Rexroth Hydraulics Div., obile, 1700 Old ansfield Road, Wooster, OH 44691-0394 Tel. (330) 263-3400 Fax: (330) 263-3333 All rights reserved Subject to revision Printed in U.S.A.