USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK

Similar documents
Ultra-High-Speed Relaying for Transmission Lines

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

NEW DESIGN OF GROUND FAULT PROTECTION

Transmission Protection Overview

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Phase Comparison Relaying

AORC Technical meeting 2014

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Synchronism Check Equipment

Distance Element Performance Under Conditions of CT Saturation

High Voltage DC Transmission 2

Digital Fault Recorder Deployment at HVDC Converter Stations

System Protection Schemes in Power Network based on New Principles

Effects and Mitigation of Post-Fault Commutation Failures in Line-Commutated HVDC Transmission System

Wide Area Monitoring with Phasor Measurement Data

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID

Distance Relay Response to Transformer Energization: Problems and Solutions

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

Application Example Document ID: SA Rev. - September 24, 2004

In Class Examples (ICE)

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Testing Power Sources for Stability

Wind and Solar (PV) Sub harmonic Interactions with Power Systems

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Conventional Paper-II-2011 Part-1A

U I. HVDC Control. LCC Reactive power characteristics

POWER SYSTEM II LAB MANUAL

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Using a Multiple Analog Input Distance Relay as a DFR

Dynamic Phasors for Small Signal Stability Analysis

FAULT CLASSIFICATION FOR DISTANCE PROTECTION

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Problems connected with Commissioning of Power Transformers

Superimposed Quantities: Their True Nature and Application in Relays

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

COPYRIGHTED MATERIAL. Index

Experiences on using gapless waveform data & synchronized harmonic phasors

Pinhook 500kV Transformer Neutral CT Saturation

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

ELEMENTS OF FACTS CONTROLLERS

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks

PROTECTION SIGNALLING

Relaying 101. by: Tom Ernst GE Grid Solutions

Impedance protection on power transformer.

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Fundamental Concepts of Dynamic Reactive Compensation. Outline

Chapter 10: Compensation of Power Transmission Systems

Assessment of Saturable Reactor Replacement Options

Power System Stability. Course Notes PART-1

Babak Enayati National Grid Thursday, April 17

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Agenda Notes for 4 th Meeting of Sub Group in respect of Preparation of Reliability Standards for Protection System and Communication System

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

An Ellipse Technique Based Relay For Extra High Voltage Transmission Lines Protection

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

A Novel Fuzzy Neural Network Based Distance Relaying Scheme

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

DC current interruption tests with HV mechanical DC circuit breaker

EASUN REYROLLE LIMITED

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

1

ATYPICAL high-power gate-turn-off (GTO) currentsource

A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines

Defining and Measuring the Performance of Line Protective Relays

AORC Technical meeting 2014

Directional Elements in L-PRO 4000

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

ELECTRICAL POWER ENGINEERING

SIPROTEC 5 Application Note

Standard Development Timeline

Mho. MiCOMho P443. A Guide How To Draw and Test P443 Distance Characteristics using Omicron

Testing Numerical Transformer Differential Relays

ZERO-SETTING POWER-SWING BLOCKING PROTECTION

High speed bus transfer function block description Operation Manual

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

PRECISION SIMULATION OF PWM CONTROLLERS

Directional STANDARDS: Overcurrent Relaying

Wind Power Facility Technical Requirements CHANGE HISTORY

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Generator Protection GENERATOR CONTROL AND PROTECTION

Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers

Voltage and Current Waveforms Enhancement using Harmonic Filters

Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay

Wavelet Based Fault Detection, Classification in Transmission System with TCSC Controllers

Transcription:

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK P Horton, S Swain patricia.horton@ge.com, simon.swain@ge.com UK INTRODUCTION Superimposed techniques also called Delta or Incremental techniques have been used for more than 30 years in protective relays. Directionality for distance relays has been implemented in different ways and has/is widely used. Directional Comparison relays were popular in the 80s and 90s and sometimes they were called Directional Wave relays meaning the relays detect the origin direction of travelling waves. Some of those relays use to quote operating time as little as 2-5 ms. As well as directionality, phase selection based on superimposed quantities has been used for similar amount of time. The principle has the advantage of calculate very fast fault direction and phase selection as well as an increased sensitivity due to the removal of prefault conditions. By measuring the step changes in currents, it is possible to detect power swings without the need to measure rate of change of impedance, which can be restrictive according to the selected impedance characteristic. Using superimposed principle also allows performing source impedance calculations which subsequently provides an estimate of fault level which has been used near HVDC links which impose temporally high fault level capability. The paper will cover the use of superimposed (delta) principle in protections such as distance and delta directional comparison. It will describe the use of the delta technique in fault direction, phase selection, power swing detection and its application in short circuit calculation for AC/DC links. PRINCIPLE OF SUPERIMPOSED ( DELTA ) TECHNIQUE Subtracting a value of the signal, before a change (due to a disturbance or fault) from its corresponding value after the change will produce a signal that represents the change. In the case of a change occurring in a periodic signal such as a sinusoid, the corresponding value before the change is the value measured exactly one or more cycles earlier. Figure 1 shows an example of a change in a sinusoidal wave and the effect of subtracting values separated in time by one cycle. A Change signal produced in this way are known as superimposed component. When a fault occurs on a power system, changes occur in the current and voltage signals which produce superimposed components as shown in Figure 2. Before the fault, when no changes occur, these superimposed components are zero.

Figure 1 Superimposed component Figure 2 Superimposed voltage and current DIRECTIONAL DETERMINATION PRINCIPLE The forward and reverse fault direction determination can well be explained by an example. Consider a protected line section AB, a fault occurs external to the protected circuit, both forward and reverse directional measurements are demonstrated using the same fault. The difference between unfaulted and faulted circuit is an equivalent circuit in which all signals are superimposed components. This shows that the superimposed components of current and voltages can be considered to be produced by an equivalent source of superimposed voltage at the fault point. The fault is represented by closing of the switch S which connects the superimposed voltage source E, whose magnitude is the change in voltage at the fault point. This causes a superimposed current I to flow in the superimposed circuit.. In Figure 3 the superimposed components flowing for an external fault is shown. Consideration of this equivalent circuit for the relay at A shows that the superimposed signals Vr and Ir are related by the equation, I r V Z r Equation 1 Where, Z is the impedance (Zsa) of the source behind the relay location. Similarly for the relay at B this relationship is, I r V Z r Equation 2

Figure 3 Superimposed components External fault Where, Z is the impedance (Zsa +Zl) of the source plus the line in front of the relay location. It should be noted that the positive direction of current for the relay at A is towards B and the positive direction of current for the relay at B is towards A. This means that, for forward faults (location A), the quantities Ir and Vr / Z are of opposite polarity and for reverse faults (location B) quantities Ir and Vr / Z are of same polarity. Compensation for the phase angle of impedance Z will then allow directional decisions to be made based on the relative polarity of the two superimposed signals. Figure 4 shows typical Delta I and Delta V for a phase A to ground fault with relay A seeing the fault in the forward direction and relay B seeing the fault in the reverse direction.

Figure 4 Typical superimposed signals. For the implementation of the delta directional principle with superimposed values calculated with the two previous cycles, under healthy system conditions, the prefault values are those measured two cycles earlier, but, when a fault is detected, by a Delta current greater than setting, the prefault values are retained for the duration of the fault. Under developing fault conditions or following the clearance of a fault on a parallel line it is sometimes necessary for the directional element to change from forward to reverse operation (or vice-versa). Any such change is monitored by Fault Detector elements which are overreaching forward and reverse distance elements. A further consequence of monitoring any change in the direction of operation using the Fault Detectors is that it prevents spurious operation on the non-power frequency signals which occur following faults on series compensated systems. After the normal measuring period, the Superimposed Signals consist of any remaining non-power frequency components of the current and voltage. Such operation is prevented because the reverse Fault Detector does not operate for the forward fault and there is therefore no agreement between the Directional count and the Fault Detector decision. Some cases have shown the delta directional principle being more secure for directional determination. The following case is an example of that: Figure 5 shows a case of an ABN solid fault behind the relay location. This is a parallel line with heavy load flowing out from the Relay location. Fault and prefault vectors shows how a -30 conventional memory directional line sees the fault in the forward direction while delta directional sees the fault in the reverse direction. Also note that a conventional -30 cross polarization directional line also would see the fault in the forward direction.

Figure 5 Directionality case PHASE SELECTION Similar to directional determination, superimposed components can also be used to detect phase determination. One way this has been achieved is by comparing the magnitudes of the three phase-tophase superimposed currents. A single phase-to-ground fault produces the same superimposed current on two of these signals and zero on the third. This is shown in figure 6 where Delta AB and Delta CA are a higher while Delta BC is lower indicating AN as the faulted loop as long as there is not a pole dead. A phase-to-phase or double phase-to-ground fault produces one signal which is larger than the other two. This is shown in figure 7 where Delta AB is higher and Delta CA and Delta BC are lower indicating AB as the faulted loop. A three-phase fault produces three superimposed currents which are the same size.

Figure 6 Superimposed current A-G Fault Figure 7 Superimposed current A-B Fault

The following table shows the phase selection criteria achieved by comparing the magnitudes of the three phase-to-phase superimposed currents against a threshold. This threshold is dynamic. For instance the superimposed current threshold is automatically increased from its default level (5%In if all current phases are less than rated current) to a percentage of the highest phase current to prevent sporadic operation during high levels of sub-synchronous frequencies ( which can be present in networks with series compensated lines). The threshold also varies during conditions such as power swing. Ph-Ph Delta I / Loop selected A B C AB BC CA I AB Valid yes yes no yes no no I BC Valid no yes yes no yes no I CA Valid yes no yes no no yes When phase selection is used with a distance relay, mix techniques with impedance loops are used to deal with slow clearance faults, evolving faults and cross country faults. With superimposed currents calculated with the two previous cycles, operation of the distance elements, is controlled by the Superimposed Current Phase Selector. Only impedance elements associated with the fault type selected by the phase selector can operate during a period of two cycles following the phase selection. If no such element operates, all elements are enabled for the following 5 cycles, before the phase selector returns to its quiescent state. Operation of an enabled distance element during the two-cycle, or five-cycle period, causes the phase selector state to be maintained until the distance element resets. An exception to this is when the phase selector changes decision while an element is operated. In this case, the selected elements are reset and the two cycle period restarts with the new selection. Note that any existing trip decision is not reset under this condition. After the first cycle following a selection, the phase selector is only permitted to change to a selection involving additional phases. DETECTION OF POWER SWINGS The company s author has used for more than 20 years a unique power swing detection that uses a superimposed current ( I) detector similar to the phase selection principle described above. Power swing is used in conjunction with the superimposed phase selection described earlier. For each phase loop (A-B, B-C, C-A), the actual measured current is compared with the measured current from exactly two cycles earlier to generate superimposed currents. Superimposed currents appear during both fault conditions, and power swings. For faults superimposed components will not be present beyond two cycles (i.e. there is only a step change in current) During power swing conditions however, superimposed components persist beyond two cycles (i.e. a continuous change in current detected). We can use this fact to differentiate between faults and power swings. During a power swing (in the absence of a fault), the phase selector will indicate a three-phase selection, or a phase-phase selection if one pole is dead. Two phase selector elements PH1 and PH2 are used for detecting power swings and faults during power swings. At fault inception, PH1 detects a superimposed current greater than 5%In on one or more loops. At this point, PH1 signals that PH2 must memorise the two cycles prior to this point, in order to retain a snapshot of the load condition prior to the fault. Thus, during the fault PH1 is calculating the superimposed current over the same continuously updating 2 cycle window of samples, whereas PH2 is always comparing the fault current to the prefault memorised load. This is the reason why after 2 cycles of fault current: PH1 resets, as 2 cycles into the fault the selector is comparing fault current to fault current, which results in little or no delta. PH2 remains picked-up, as it is still measuring delta with reference to the stored memory.

This is shown in figure 8 Figure 7 Superimposed current A-B Fault It is the length of time for which the superimposed current persists that is used to distinguish between a fault and a power swing. A power swing is deemed to be in progress if a three phase selection, or a phase to phase selection when one pole is open, produced in this way is retained for more than three cycles. This is shown in figure 8 at the time t2. At this time the phase selector threshold is increased. A fault is detected during a swing when the phase selector operates, based on its increased threshold. Therefore, any operation of the phase selector causes PSB unblocking and allows a trip. For example, a fault causes the delta current measured to increase above twice that stored during the swing. This is a step change in delta I rather than the expected gradual transition in a power swing. Figures 8 and 9 shows the phase selector timings used to detect power swing and faults during power swing. Figure 8. Phase selector timing for power swing condition

Figure 9: Phase selector timing for fault during a power swing OPERATING TIMES FOR DELTA BASED RELAYS The following curves show operating tripping times for relays protecting a typical line of 10<70 ohms impedance (1 Amp input CT) and at 60 Hz. Times are quote with high speed high break contact outputs Figure 10. Directional Comparison relays based on Delta principle. Times are quote depending on SIR at each end of the line.

Figure 11. Distance relay where phase selection and Directional decision are based on Delta principle. Comparators are standard. SOURCE IMPEDANCE DETERMINATION In the Directional Determination principle described earlier, it was described how the source impedance behind an IED location can be calculated using the superimpose values of voltage and current. Zeq = - ( Vr / Ir ) Where, Zeq is the short circuit impedance ( Zsource ) behind the IED location. With the calculation of the source impedance behind the IED, estimation of the short circuit level is possible given a suitable event in the grid. Estimation of the short circuit is in some locations of the grid has been used for different purposes. One of them is in the case of a HVDC station connected to the DC line. If a HVDC converter particularly LCC- line commutated converter is connected to a weak AC grid relative to the DC power, i.e. the AC system is seen as a high impedance at the AC/DC connection, problems with power frequency stability and voltage can occur. The weaker the AC grid is, the greater the AC/DC interactions. Even a small DC link connected at a point of high AC system impedance can have an adverse and considerable effect on the local network, even if the local network may be a part of a larger AC system. This is well documented in [5]. The terminology used is called Short Circuit Ratio (SCR) which is defined as the ratio of the connected grid SCL to the size of the converter. For example, the SCL of the grid is 1000MVA and the size of the converter is 200MW then the SCR is 1000/200 = 5. The guide [5] mention: A High SCR AC/DC System is categorized by an SCR value greater than 3 A Low SCR AC/DC System is categorized by an SCR value between 2 and 3 A Very low SCR AC/DC System is categorized by an SCR value lower than 2

Depending on the SCR of the system, different actions have to be taken. In case of very low SCR ac system, actions towards the strengthening of the system has to be taken. By having an estimation of the AC source impedance at a determined location, is possible to avoid running generators when they are not needed, add or remove synchronous compensators and filters. If the required short circuit power is not met i.e. the SCR is not met, the operator can dispatch more generators or connect synchronous compensators. An application was created for a large European TSO which has AC/DC links, where the short circuit capacity is calculated at the terminal of the converter. For this purpose, Phasor Measurement Units (PMUs) were installed specifically for this short circuit calculation. These PMUs measure the voltage and current of shunt reactors and capacitors connected at the AC converter terminal. Events are triggered by switching a shunt element on or off. The switch is deliberately when it is required to update the short circuit level value. These has helped a large European TSO the use of less conventional generation near the AC/DC link. There are some other ongoing studies using the same principle to predict fault level in distributed generators (DG) systems where there is a potential increase of fault levels due to the contribution of the connected DGs. The fault current can possibly exceed the opening capacity of the related breakers, due to the contribution of fault currents by DGs. The aim of the study is to avoid the refurbishment of circuit breakers in active distribution networks. USE OF THE TECHNIQUES IN DIFFERENT PROTECTION APPLICATIONS Superimposed (Delta) techniques have been used extensively and successfully for more than 30 years by the company s author in multiple relay protection applications: Directional determination has been used to achieve directionality of Distance relays, Directional comparison relays and most recently in in the fault level prediction in active distribution networks. Reliability of phase selection technique based on superimposed technique has allowed its use in Distance, Aided Directional Earth Faults (DEF) and Directional comparison relays. Power swing technique has provided a way to detect very fast oscillations which are otherwise difficult to detect with conventional rate of change of impedance method. Most recently, with these delta techniques have been used to determine the short circuit level to take actions in a HVDC link at the point of connection with the AC grid. CONCLUSION Superimposed components (delta) based principle has been used in commercially available relays from the author s company and have been successfully protecting the transmission lines for more than three decades. Delta directional technique have been complimented by delta based phase selection and delta current based power swing technique, to provide fast and secure operations for most faults in the power system. This is achieved even when protecting complex power systems and compensated transmission lines. Most recently this principle is being used to assist smart grid in functions such as fault level calculation in AC/DC links at the convertor stations. REFERENCES [1] MiCOM P40 Agile P543/P545 (with Distance) Technical Manual. Software Version: 82 Publication Reference: P54x1Z-TM-EN-1 [2] MiCOM P40 Agile P441, P442, P444 Technical Manual Platform Software Version: 61 & 70 Publication Reference: P44x/EN M/H96

[2] Type LFDC Digital Directional Comparison Protection Relay. GEC Measurements. Service manual R5923 [3] LFZR. High-Speed Numerical Distance Relays. Service manual R5923LFZR/EN M/B11 [4] K.S.Prakash et.al, IEEE Transactions on Power Delivery, Vol.4, October 1989, Amplitude comparator based algorithm for directional comparison protection of transmission lines. [5] Guide for planning DC Links terminating at AC System locations having low short-circuit capacities CIGRE-IEEE Joint task force. CIGRE Working group 14-07, IEEE Working Group 15.05.05. Biographies: Patricia Horton received her Bsc. Electrical Engineering (1990) from "Universidad Nacional de Colombia", Her early roles include design and commissioning of protection and control circuits for a 1000 MVA hydro electrical project, fault analysis and grading of transmission and subtransmision networks in Colombian utility. She joined GEC-Alsthom T&D in 1999 where she has undertaken several roles such as Support Engineer in Real Time Digital Simulator testing mainly transmission products. Most recently she works as a Product Manager of Distance relays in GE Grid Solutions United Kingdom. Simon Swain received his 1st Class BENG (Hons) Electrical/Electronic Engineering (2004) from Staffordshire University, UK. He joined GEC-Alsthom T&D in 1995 where he has undertaken many roles such as Technician Apprentice, Component Engineer, Product Support Engineer. In more recent years he took on the Lead role of the Transmission Distance and Differential Team as a Senior Application Software Engineer developing Algorithms for existing product lines. Most recently he works as Technical Lead, supervising 10 Engineers in the Development of Transmission Distance/Feeder Application developments within GE Grid Solutions United Kingdom developing the next generation Products.