SHUNT ACTIVE POWER FILTER

Similar documents
CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

To Study The MATLAB Simulation Of A Single Phase STATCOM And Transmission Line

Chapter 2 Shunt Active Power Filter

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Power Quality improvement of a three phase four wire system using UPQC

Improving Passive Filter Compensation Performance With Active Techniques

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

The unified power quality conditioner: the integration of series and shunt-active filters

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

shunt (parallel series

Enhancement of Power Quality Using Advanced Series Active Power Filters

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

UPQC (Unified Power Quality Conditioner)

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Power Quality enhancement of a distribution line with DSTATCOM

A Novel Power Factor Correction Rectifier for Enhancing Power Quality

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Active Harmonic Filter (AF3)

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Literature Review for Shunt Active Power Filters

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

CHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Literature Review. Chapter 2

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

2020 P a g e. Figure.2: Line diagram of series active power filter.

Design and Simulation of Passive Filter

CHAPTER 3 H BRIDGE BASED DVR SYSTEM

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

Power Quality Improvement using Shunt Passive Filter

CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Power Quality Improvement using Active shunt Power filter using PI Controller

CHAPTER 1 INTRODUCTION

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

CHAPTER 4 HARMONICS AND POWER FACTOR

Modeling and Simulation of Matrix Converter Using Space Vector PWM Technique

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Modeling and Simulation of STATCOM

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Mitigation of harmonics using shunt active filter Mrs.Chhaya S Bandgar 1, Ms.Shamal B Patil 2

PF and THD Measurement for Power Electronic Converter

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Conventional Paper-II-2013

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Simulation Study of PWM Techniques for Voltage Source Converters

Understanding Input Harmonics and Techniques to Mitigate Them

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Field Programmable Gate Array (FPGA) Based Pulse Width Modulation for Single Phase Hybrid Active Power Filters U. Krishna Reddy 1 Ch.

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

ISSN Vol.03,Issue.07, August-2015, Pages:

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

11. Define the term pinch off voltage of MOSFET. (May/June 2012)

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

CHAPTER 3 SINGLE SOURCE MULTILEVEL INVERTER

A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Multilevel Inverter Based Statcom For Power System Load Balancing System

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

6. Explain control characteristics of GTO, MCT, SITH with the help of waveforms and circuit diagrams.

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Novelty Technique for Power factor Improvement by a Single phase Rectifier

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Harmonic control devices

CHAPTER 4 FULL WAVE RECTIFIER. AC DC Conversion

Power Factor Correction of LED Drivers with Third Port Energy Storage

Active Rectifier in Microgrid

Transcription:

75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF) for threephase systems to ensure low mains current harmonics and high energy efficiency by reducing reactive power consumption, as well as maintaining a constant output DC-bus voltage. Discussed the performance characteristics of SAPF topology with the synchronous logic control algorithm that is based on the angle between the mains and the reference sine wave to control the power factor and to inject a current where each harmonic current has the same amplitude as that of the load current but in opposition of phase. However, this PWM technique greatly simplifies the calculation process and is easier to implement with digital processors. Designed and developed a three-phase SAPF system that is built and tested with the inputs and output with load. The proposed PWM technique can be used in all applications such as Inverters, Filters, UPSs, etc. The Simulation and experimental prototype performance results of a three-phase SAPF with a power output of 3 kva is presented to validate the proposed control strategy and the results obtained. 4.1 Introduction In the traditional approach, in order to suppress harmonics in power systems, passive power factor correction techniques with line chokes and bulk capacitors are used but they are neither convenient nor economical; they need bulky components and are not adaptive to changing needs. However, the remarkable progress made in the field of the power electronic devices made the systems design for harmonics compensator, named as Active Power Filters

76 (APFs) is a reality. These APFs eliminate the components of power that do not contribute to the net transfer of energy from the source to the load. New systems and appliances can be built with the unity power factor and low current harmonics front end rectifiers but large number of systems that are already in operation need a special attention. Active power filters can be divided in two classes: series type and shunt type active filters, as defined in [31], from the system point of view. The combination usage of shunt active and passive filters has already been in use to compensate large-rated loads input current harmonics. Active Power Filters also help in meeting the IEEE 519-92, IEC-555 and European EN 61000-3-2/IEC 61000-3-4 standards for allowable harmonic contents of mains. To prevail over the above drawbacks of the large number of systems that are already in the field and in operation, power quality improvement filters are included as an inherent part of the total power network system that produces high efficiency, reduced size and regulated output. Various types of solutions to Power Quality problems with Active Power Filters are shown in table 4.1. Table 4.1: - Active Power Filter Solutions to Power Quality Problems. Active Power Filter Solutions to Power Quality Problems Active Filter Connection Load on AC Supply AC Supply to Load Shunt -Current Harmonic Filtering. -Reactive current compensation. -Current unbalance. Nil -Voltage Flicker. Series -Current Harmonic Filtering. -Reactive current compensation. -Current unbalance. -Voltage Flicker. -Voltage unbalance. -Voltage sag/swell. -Voltage unbalance. -Voltage distortion. -Voltage interruption. -Voltage flicker. -Voltage glitches.

77 An active harmonic power conditioner/compensator/filter is a device that uses at least one static converter to meet the harmonic compensation function. This generic term thus actually covers a wide range of systems, distinguished by: The number of converters used and their association mode, Their type (voltage source, current source), The global control modes (current or voltage compensation), Possible association with passive components (or even passive filters). (a) (b) Figure 4.1: - Active Power Filter (a) shunt-type and (b) series type. Figure 4.2: - Series/Parallel type hybrid filter.

78 The only common feature of these active systems is that they all generate voltages and/or currents that are in opposition (Phase) to the harmonics generated by non-linear loads. Figure 4.1(a) shows the simplest one that is normally known as Shunt (or Parallel ) type topology. The Series type active harmonic conditioner shown in Figure 4.1(b) is rarely used. It works by blocking the upstream harmonic voltage sources to provide better power to a sensitive load on a troubled power network. However, in practice, this upstream technique is of little interest since: The quality of the energy at the point of common coupling is satisfactory, Insertion of an equipment in series mode is not that easy because of the issues like withstanding short-circuit current, It is more useful to look at the actual causes of voltage distortion (harmonic currents) within the network. Out of the numerous Hybrid alternatives the Series/Parallel type solutions have shown in figure 4.2 the one that combines active and passive filtering is a very effective one for harmonic cancellation that comes close to the high power converters. Provided that the equipment is capable of injecting a current at any given time with the same amplitude as that of the load current but exactly in opposition of phase, at that point of contact (coupling) the current supplied by the mains is guaranteed to be purely sinusoidal as per the Kirchoff s law. The control strategy is to apply a current reference that is equal to all the harmonics content of the current absorbed by non-linear load, then the current produced by the converter is in phase opposition to the load and cancels all the harmonics at the point of common coupling (PCC) as shown in figure 4.3, which is also known as Shunt Active Power Filter (SAPF). This also comes under the classification of Flexible AC Transmission Systems (FACTS) which is defined by the IEEE as "a power electronic based system and other static equipment that provide control of one or more AC transmission system parameters to enhance

79 controllability and increase power transfer capability." The combination of non linear load currents plus active power filter currents forms a linear load current to the mains power supply. SAPF also supplies the reactive component of the load to make the source current to be in phase with the voltage. The SAPF thus forms a current source independent of mains supply impedance as clarified in [14, 29, 31, 35], and the control algorithm as in [2], with the following characteristics: Band-width is sufficient to remove most of the harmonic components from the load current, Response time is such that the harmonic compensation is effective in steady state as well as in transient state, Has enough power to meet all harmonic components. However, all the harmonics generated by the load are not necessarily compensated in total and permanently. Provided that these three main objectives are simultaneously met, the SAPF forms an excellent source solution as it is self-adaptive and there is no risk of interaction with power network impedances. The aim of SAPF is not to re-phase the mains fundamental voltage and current components but to make sure the current is linear. So, the insertion of SAPF has no effect on the displacement power factor. Apart from controlling the harmonics in the source currents, close to unity power factor ensures that the source is not loaded reactively. Here a four quadrant, three-phase, six-switch and common link DC bus converter topology used. Figure 4.4 shows a block diagram of the parallel active filter connection. It consists of a dc link inverter and filter section. The filter inductor is used to convert the voltage source inverter output to a current source capable of injecting harmonic currents to the load. The configuration exhibited in Figure 4.5 uses load current feedback. The system is capable of using utility source voltage and current signals wherein the source harmonic currents are minimized.

80 (a) Figure 4.3: - Equivalent circuit of Shunt Active Power Filter, (a) Single line diagram and principle of compensation (filtering) (b) Three Phase (b) Figure 4.4: - Shows the basic structure of Three-Phase Shunt Active Power Filter. Figure 4.5: - Three-Phase and neutral configuration of Shunt active power filter.

81 The SAPF topology is implemented with six power switches (three legs) as shown in figure 4.5. Shunt active power filter (SAPF) is similar to a PWM unity power factor rectifier by construction but differ it by a centre tap on the main filter capacitors / batteries which in turn is connected to the neutral. The control logic types studied as in [3, 19] made improvements by calculating the load current harmonics in real time by comparing with the fundamental, which are applied as reference to the inverter control logic in order to cancel the harmonics and to get a sinusoidal form for the mains supply current. SAPFs are gaining widespread popularity and have received special attention in high-power high-voltage applications for large capacity power applications as listed in Table 4.2 because of their excellent performance and better line side power quality. This data is collected from the various device manufacturers data sheets and also various application notes and presentations. Table 4.2: - Commercial applications of Shunt Active Power Filters Objective Rating Switching Devices Applications Harmonic compensation below100kva IGBT Diode or thyristor rectifiers and cyclo- with or without reactive MOSFET converters for industry power compensation IGCT GTO Flicker compensation 100VA ~10 MVA IGBT Arc furnaces Voltage regulation above10mva GTO Sinkansen (the Japanese bullet trains) Designed and developed a three-phase SAPF system that was built and tested with the inputs and output. The results confirm the theoretical analysis. The SAPF was designed to run over a wide line-to-line supply voltage range of 160 to 520 Vrms, and 3 kva nominal power output. For an output Dc link voltage of 900 Vdc, the input phase current was approximately 5.0 Arms.

82 Experimental prototype system results of three-phase, twelve switches, PWM SAPF that was designed to deliver an output of 3 kva power are presented. Details on the formulated problem design example are presented in section 4.2, including description of a power section implementation with six power switches and six freewheeling diodes and two filter/storage capacitors. Details of the SAPF analysis are described in Sections 4.3 including Input current Analysis. Simulation details are presented in section 4.4. Simulation results are presented in section 4.5 with nominal input while delivering total of 3 kva harmonic compensation. Details on the experimental performance, such as the input currents and respective harmonics, DC link bus voltage and input voltages are given in Section 4.6. The overall SAPF system performances with the synchronous logic control implementation are concluded in Section 4.7. 4.2 Design (Example) The design and implementation of a shunt active power filter (SAPF) with reduced dc link voltages as detailed in [35] was studied. Following Flowchart of the generalized design methodology for SAPF is given in Figure 4.5 (a) and design example is used as an improvement to the above reference: 1. Choose a suitable PWM switching pattern for the Inverter three phases. Enough lead and lag angle range accommodated in order to keep the output dc link voltage constant even under high input voltage fluctuations conditions. 2. Select the switching frequency of the SAPF bridge converter switches (MOSFET, IGBT or GTO) based on voltage, current and power for the specified kva rating. The selected switching frequency is 50 khz to compensate for higher harmonics of 29 th order. So

83 MOSFETs are selected. 3. Select the Free-wheeling diodes for SAPF converter based on the voltage, current and power for the specified load kva. Fast Recovery Diodes are selected. 4. Calculate the input filter inductance based on voltage and the kva rating. 5. Calculate the DC bus link capacitance based on voltage and the kva rating of converter. 6. Calculate the input main inductance value for the specified output kva (current) rating, Lowest input voltage rating and selected constant switching frequency. Flowchart of the generalized design methodology for SAPF: I. Determine the required output power rating (Po), input voltage (Vin) and required efficiency (η) of the system II. Select a suitable sinusoidal switching pattern for the Inverter threephases III. Determine the required lead and lag angles to keep the harmonic content low even under high mains voltage and full output load conditions IV. Select the suitable Bi-Directional switches (Transistors and Diodes) based on the type (MOSFET or IGBT), voltage and current based on the voltage, current and power for the specified load kva V. Calculate the input filter inductance based on the voltage and kva rating, and desired per unit impedance VI. Calculate the DC bus link capacitance based on voltage and the kva rating of converter VII. Calculate input main coupling inductance based on the specified output kva (current), lowest input voltage and selected switching frequency VIII. Verify input current harmonics at various R, RL (fixed) and RL (variable) loads IX. Verify system efficiency at various output power levels with R, RL (fixed) and RL (variable) loads X. Finalize the design I II III IV V VI VII N VIII Y N IX Y X Fig. 4.5 (a). Flowchart of the generalized design methodology for SAPF

84 In this section, the design prototype example of a SAPF is presented which is having the following specifications: Table 4.3: - Active Power Filter Specifications (4.8 Arms) Type APF urs (Nominal) Vrms 3.0 kw 3 x 400 ± 15%, 47 to 53 Hz Power Factor 0.95 THD of ir 10 % Modulation type Switching (modulation) frequency Rated VA @ 400 Vac ir Short term over load current in A ac Sine PWM 50kHz 3.0 kva 5.0 Aac 200% of ir for 0.5 sec. over 60 sec cycle time. Estimated efficiency η 90 Operating Temp. C 0 to +40; +40 to + 50 with derating

85 4.3 Shunt Active Power Filter Analysis The proposed three-phase high-quality Shunt Active Power Filter (SAPF) is shown in figure 4.5. The four wires SAPF consists six power switches (three legs), six power diodes, two capacitors in the DC side and three line inductances in the ac side. Figure 4.6 illustrates the phasor diagrams for power exchanges at the Point of Common Coupling (PCC), converter output current and voltage are shown in all four quadrants of the PQ plane. Figure 4.6: - Phasor diagram for power exchanges in four quadrant operations. A. Sinusoidal PWMs for Shunt Active Power Filters The implementation of a SAPF with synchronous logic based phase angle control algorithm based PWM is carried out by the same principle as that of a converter. Figure 4.7(a) shows a reference control wave with frequency F o and a carrier wave with frequency Fs i.e.,

86 switching frequency. The magnitude of the carrier wave has to be always kept greater than the reference wave for better harmonics control. The carrier wave generates the gate drive pulses as shown in Figure 4.7(b) for the power switches sr1 and sr1 of the SAPF converter R phase that generates voltage. And for the other two phases S and T, the reference sinusoidal waves are displaced by an angle 2Π/3 and 4Π/3 respectively. Figure 4.7(a): Source Current (Red), Control wave (Green) and Carrier wave (Blue) for R-phase of the Three- Phase H-Bridge SAPF Converter. Figure 4.7(b): Gate drive pulses for R-phase of the Three-Phase H-Bridge SAPF Converter.

87 4.4 System Simulation The H-Bridge SAPF converter SIMULINK simulation gives DC link voltage of 900 Vdc and average bridge rectifier DC voltage of 600 Vdc for SAPF converter, at nominal voltage conditions. The mains current harmonics are much lower than the levels of the statutory requirements. At various non-linear or/and reactive loads, it is possible to keep the mains current harmonics low and power factor close to unity for input over voltage situations also. In order to verify the input current harmonics of SAPF at different load levels while keeping constant DC link voltage, simulations as shown in figures 4.8(a) and (b) have been performed. Tabulated results by changing the loads on the output with R, RL (PF-fixed), and RL (PF-variable) variable type. The control strategy has enough lag and lead angles δ to keep the Dc link voltage stable, while keeping the mains current free of harmonics. 4.4.1 Simulation of SAPF with Synchronous Logic: The model shown below in figure 4.8(a) gives the Simulation circuit of SAPF and figure 4.8(b) shows Synchronous Logic based Phase angle control scheme. Each leg has two power switches and two power diodes are connected in parallel. IGBT s are taken as the power switches. The output voltage and current is taken as the output on the scope. 4.4.1.1 Model Parameters These parameters are based on the per unit impedances for the given power level and output ratings/specifications. Source: Voltage (Phase) 230 Vac, Frequency 50 Hz, Resistance- 0.1 Ω, Inductance - 1.0 mh Bridge Rectifier: Output voltage 600 Vdc, Capacitance - 1000 µf, Load- R 200 Ω and L - 0.01 mh Converter: Coupling Inductance - 1.0 mh, DC link Voltage 900 Vdc, Switching Frequency 50 khz

88 Figure 4.8(a): - Simulation circuit of Shunt Active Power Filter (SIMULINK). Figure 4.8(b): - Shunt Active Power Filter Control Scheme (SIMULINK).

89 4.5 System Simulation Results Simulation studies were carried out to validate the Synchronous Logic based control algorithm SIMULINK model to generate gate drive PWM for SAPF. SAPF CONVERTER SYSTEM The simulation results of SAPF system are shown below in figure 4.9 with Resistive (R) Load. The three phase reference voltages unr, uns, unt are calculated from the frequency and amplitude of the source voltages as shown in figure 4.9(a). The control waveforms are calculated from the load current waveforms and compared with the carrier waveforms to get the drive signals of the power switches. Figure 4.9(b) shows the Load current, Source current and converter current, 4.9(c) shows DC Capacitor link voltage, and 4.9(d) shows Bridge Rectifier load (dc) current and voltage. The simulation and results are with Resistive (R) Load. The input current is, inr = 5.47 A (corresponding to 1 kw each phase) at 230 Vac input voltage. Only harmonics 5 th, 7 th, 11 th, 13 th, 17 th, 19 th, 23 rd, 25 th and 29 th are considered. Third and its multiples are negligible to consider. 4.5.1 Mains (Source) Voltage and Current The mains (source) supply voltages and currents of R-Phase, Three-Phase, Four-wire, SAPF are shown in figure 4.10(a) and figure 4.10(b) respectively.

90 (a) (b) (c) (d) Figure 4.9: SAPF converter; (a) Voltages (unr, uns, unt) from source voltages, (b) Load current, Source current and converter current, (c) DC Capacitor link voltage, (d) Bridge Rectifier load (dc) current and voltage.

91 (a) (b) Figure 4.10: Source waveforms of Three-Phase, Four wire, SAPF R-Phase; (a) Three Phase Voltages (b) Currents. 4.5.2 Source Current Harmonics Suitable harmonic computation technique for active power filters as detailed in [45] was studied. The source current harmonics of R-Phase, Three-Phase, Four wire, SAPF are shown in figure 10(c). 0.300 0.250 0.200 0.150 0.100 0.050 100W 200W 400W 600W 800W 1000W 0.000 5th 7th 11th 13th 17th 19th 23rd 25th 29th Figure 4.10(c): Simulation results source current harmonics of R-Phase Three-Phase Four wire SAPF.

92 Table 4.4: SAPF Simulation Input current and voltage at different Resistive loads. Table 4.5: SAPF Simulation Input current harmonics at different Resistive loads.

93 4.6 Experimental Results In order to verify the SAPF concept, a prototype of a three-phase four wire Shunt Active Power filter with proposed synchronous logic based phase angle control with source voltage and load current sensing was built with following specifications: Maximum output of 5A per Phase current harmonic compensation. Source: Voltage (L-N) 230 V, Frequency 50 Hz, Inductance - 1.0 mh Bridge Rectifier: Output voltage 600 Vdc, Capacitance - 1000 µf, Load- R 120 Ω and L - 0.01 mh Converter: Coupling Inductance - 1.0 mh, DC link Voltage 900 Vdc, Switching Frequency 50 khz The real-lab prototype for the three phase with neutral SAPF system configuration is shown in figure 4.5 is shown in figures, 4.11(a), Logic section and Power sections, 4.11(b), complete assembly of SAPF. The power supply, some line filters and output load sections are not shown due to space constraints. Component values are based on the kva rating, per unit impedance, switching frequency and output rating. The experimental condition is as follows: three-phase Source inductance is 1.0 mh; SAPF converter coupling inductance is 1.0 mh; Bridge rectifier output inductance, 0.01 mh and capacitance, 1000 µf. Six main bidirectional switches in parallel with six ultra fast recovery diodes used to build three-phase full bridge SAPF converter. SAPF converter phases unr, uns and unt are implemented with MOSFETs as shown in figure 4.5. The Bridge rectifier output load resistance is 120 ohms. The switching frequency is 50 khz. Figure 4.12 shows the experimental waveforms. Three Phase Input Current waveforms (Ch1 Ch4) inr, ins, int and in when a resistive load of 3 kw applied on output of bridge rectifier.

94 Figure 4.11(a): Real-Lab prototype set up of the three-phase four wire SAPF Logic and Power sections. Figure 4.11(b): Real-Lab prototype set up of the three-phase four wire SAPF Converter. Ch1: 3A, Ch2: 3A, Ch3: 3A, Ch4: 3A; Scale: 5 ms; Trigger: Line Figure 4.12: Three Phase Source Current waveforms (Ch1 Ch4) inr, ins, int and in at 230 V when total Resistive Load of 3 kw applied on Bridge Rectifier Output.

95 Readings have been taken in order to verify the utility mains current harmonics at different load levels. Recorded readings of source current harmonics; bridge rectifier output voltages and efficiency, by changing the loads on the output with R, RL(fixed PF) and RL (variable PF) type and presented in figures 4.13(a), 4.14(a), 4.15(a); 4.13(b), 4.14(b), 4.15(b) and 4.16 respectively. The measured power factor was 0.97 when the DC-Link voltage was 900 Vdc. Bridge rectifier output voltage is 600 Vdc (+300 and -300 referenced to center point) and currents are multiplied by 50 to make them easily readable. Only harmonics 5 th, 7 th, 11 th, 13 th, 17 th, 19 th, 23 rd, 25 th and 29 th are considered. Third and its multiples are negligible to consider. The values of the displacement power factor (DPF), power factor (PF), and current total harmonic distortion (THD), respectively for the load and power supply source are presented in Table 4.4. The values of THD are for the phase and neutral currents. The values of DPF and PF are presented to each of the phases. Table 4.6: SAPF DPF, PF and currents THD values at Load and source with crest factor loads. It is confirmed after comparing the results that the SAPF compensates the PF and the harmonic currents, turning them into near unity and near zero respectively at source supply. The source current spectrum, rectifier output voltages and current are shown in Figure 4.13 with resistive (R) Load. The input current is, inr = 5.0 A at 232 Vac input voltage. The efficiency at rated power is 82%.

96 Table 4.7: SAPF Input current and voltage at different Resistive loads. Table 4.8: SAPF Input current harmonics at different Resistive loads.

97 0.400 0.350 0.300 0.250 0.200 0.150 0.100 0.050 100W 200W 400W 600W 800W 1000W 0.000 5th 7th 11th 13th 17th 19th 23rd 25th 29th (a) 400 300 200 100 0-100 -200-300 I-R-Load V2 -R V1 - R -400 (b) Figure 4.13: - SAPF with Resistive Load, (a) Source current harmonics at different load levels, (b) Bridge Rectifier output Voltage and Current with 3 kw load. Figure 4.14 shows the source current spectrum, rectifier output voltages and current with Resistive and Inductive (RL) Load with a fixed power factor. The input current is, inr = 5.14 A at 231 Vac input voltage. The efficiency at rated power is 80%.

98 Table 4.9: SAPF Input current and voltage at different RL loads (Fixed-PF). Table 4.10: SAPF Input current harmonics at different RL loads (Fixed-PF).

99 0.450 0.400 0.350 100W 200W 0.300 0.250 0.200 400W 600W 0.150 800W 0.100 0.050 1000W 0.000 5th 7th 11th 13th 17th 19th 23rd 25th 29th (a) 400 300 200 100 0 I-RL-(PF-Fixed) V1 - RL-(PF-Fixed) -100 V2 - RL-(PF-Fixed) -200-300 -400 (b) Figure 4.14: - SAPF with Resistive and Inductive (RL) Load with a fixed rated power factor, (a) Source current harmonics at different load levels, (b) Bridge Rectifier output Voltage and Current with 3 kw load. Figure 4.15 shows the source current spectrum, rectifier output voltages and current with Resistive and Inductive (RL) Load with variable power factor. The input current is, inr = 5.08 A at 231 Vac input voltage. The efficiency at rated power is 81%.

100 Table 4.11: SAPF Input current and voltage at different RL loads (Variable-PF). Table 4.12: SAPF Input current harmonics at different RL loads (Variable-PF).

0.400 0.350 0.300 0.250 0.200 0.150 0.100 0.050 0.000 400 300 200 100 0-100 -200-300 -400 5th 7th 11th 13th 101 17th 19th 23rd 100W 200W 400W 600W 800W 25th I-RL-(PF-Variable) 1000W V1 - RL-(PF-Variable) V2 - RL-(PF-Variable) 29th Figure 4.15: - SAPF with Resistive and Inductive (RL) Load with variable power factor, (a) Source current harmonics at different load levels, (b) Bridge Rectifier output Voltage and Current with 3 kw load. (a) (b) 90 80 70 60 50 40 30 20 10 0 ƞ R Load ƞ RL Fixed ƞ RL Variable 100 200 400 600 800 1000 Figure 4.16: - Efficiencies of SAPF with various load levels.

102 The efficiencies shown in figure 4.16 are with Resistive, Resistive and Inductive (RL) Load with fixed power factor and RL with variable power factor from unity to rated. Measurements were recorded by changing the loads on the output of the setup. The efficiency varied based on the type of load and also percentage of the load from 58% to 82%. 4.7 Summary More reactive power and more current harmonics means more losses, lower efficiency, more electric energy to be produced and correspondingly more environmental pollution and particularly more carbon dioxide put in to the atmosphere. Cancellation of harmonics and reduction of reactive power in the mains represents not only an economic sense but also a direct solution for sustainable development. A number of possible SAPF were presented. It was demonstrated that both voltage and current harmonics can be cancelled as well as the reactive component of the load current by using proper control logic. The phase angle control was based on specialized logic developed for converter applications, providing a simple and cost effective solution. The proposed three-phase, four wire, six switch H-Bridge, SAPF converter was investigated and simulated; source current distortion that usually generated by diode bridge rectifier and capacitive filter was controlled. A new three-phase synchronous logic based phase angle control is introduced and simulations show that it can produce very low DC link voltage ripple and very low source current harmonics with unity power factor. The resulting input current harmonics were below the limits of IEC 61000-3-4 standard for various load levels. Experimental SAPF converter of 1 kva per phase, with six switches H-Bridge was built to

103 verify the concept. Near unity power factor was measured in all three phases. The source is having lower current harmonics but more number of conducting devices (Converter and Rectifier) resulted in lower efficiency. The proposed controller is implemented by sensing source voltages, load currents and DC link voltage. The SAPF converter controller is very simple and reliable. The input inductance size and value is reduced when compared to the passive filter circuit. The experimental results confirm the prototype circuit s behavior.