GETTING STARTED GUIDE NI Port DeviceNet Module

Similar documents
NI 9881 GETTING STARTED GUIDE. 1-Port CANopen Module

High-Speed/Flexible Data-Rate CAN Characteristics 5 VDC

GETTING STARTED GUIDE NI Port, High-Speed CAN Module. Français Deutsch 日本語한국어简体中文. ni.com/manuals

OPERATING INSTRUCTIONS NI Port, Low-Speed/Fault Tolerant CAN Module

NI 9853 GETTING STARTED GUIDE. 2-Port, High-Speed CAN Module. This document explains how to connect to the NI Français Deutsch 日本語한국어简体中文

1- or 2-Port, High-Speed, Flexible Data Rate PXI CAN Interface Module

1- or 2-Port, Software-Selectable PXI CAN Interface Module

OPERATING INSTRUCTIONS NI Port DeviceNet Module

NI PXIe Contents. About These Specifications DEVICE SPECIFICATIONS. 3 GHz Ω Multiplexer (SP16T)

USRP Contents. Definitions SPECIFICATIONS. 50 MHz to 2.2 GHz Tunable RF Transceiver

USRP Contents. Definitions. Conditions SPECIFICATIONS. Software Defined Radio Reconfigurable Device

USRP Contents. Definitions SPECIFICATIONS. Software Defined Radio Reconfigurable Device

USRP Contents. Definitions. Conditions SPECIFICATIONS. Software Defined Radio Device

USRP Contents. Definitions. Conditions SPECIFICATIONS. Software Defined Radio Device

USRP Contents. Definitions SPECIFICATIONS. 10 MHz to 6 GHz Tunable RF Transceiver

NI-XNET CAN HS/FD Transceiver Cable

NI PXI Contents DEVICE SPECIFICATIONS. RF Attenuator

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9853E 2-Port, High-Speed CAN Module

GETTING STARTED GUIDE NI AI, ±5 V, 24 Bit, 51.2 ks/s/ch Simultaneous, AC/DC Coupling, IEPE AC Coupling

GETTING STARTED GUIDE NI AI, ±10 V, 24 Bit, 50 ks/s/ch Simultaneous

CDA Contents. Definitions SPECIFICATIONS. Clock Distribution Device

GETTING STARTED GUIDE NI C Series GPS Synchronization Module

GETTING STARTED GUIDE NI khz to 100 MHz, 50 Ω, AC Coupled RF Receiver Module

NI PXI Contents. About These Specifications DEVICE SPECIFICATIONS GHz Dual Transfer Switch 50 Ω Relay Module

PXI Contents. PXI-2585 Specifications. Topology DEVICE SPECIFICATIONS. 10-Channel Multiplexer

PXIe Contents SPECIFICATIONS. RF Amplifier

PXIe Contents SPECIFICATIONS. RF Preselector Module

Refer to the NI Switches Help at ni.com/manuals for detailed topology information.

PXI Contents SPECIFICATIONS. ±20 V, 40 W PXI Source Measure Unit

SA1500X. Operating Basics. Cautions DEVICE SPECIFICATIONS. High Impedance Active Probe

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous

PXI Contents. Definitions SPECIFICATIONS. ±100 V, 2 W Precision PXI Source Measure Unit. These specifications apply to the PXI-4132.

NI PXI/PXIe Contents DEVICE SPECIFICATIONS. 40 A Fault Insertion Unit

NI PXI/PXIe Contents DEVICE SPECIFICATIONS. 10 A Fault Insertion Unit

PXI Contents. PXI-2584 Specifications DEVICE SPECIFICATIONS. 300 V CAT II, 600 V CAT I Multiplexers

PXI Contents SPECIFICATIONS. 1.3 GHz RF Analog Signal Generator

NI roborio. Contents. Processor SPECIFICATIONS. RIO Device for Robotics

PXIe Contents SPECIFICATIONS. 3.3 GHz RF Analog Signal Generator

PXI Contents SPECIFICATIONS. 6.6 GHz RF Analog Signal Generator

100 MHz Bandwidth, 12-Bit PXI Waveform Generator

USRP Contents. Definitions SPECIFICATIONS. USRP Software Defined Radio Stand-Alone Device

NI PXI/PXIe Contents. About These Specifications DEVICE SPECIFICATIONS. Quad 2 1 Terminated Multiplexer

PXIe Contents. Definitions SPECIFICATIONS. 8.5 GHz Vector Network Analyzer

PXIe Contents. Definitions SPECIFICATIONS. 8.5 GHz Vector Network Analyzer

PXIe Contents SPECIFICATIONS. 250 khz to 20 GHz RF Analog Signal Generator

4-Channel, ±6 V, 500 ma Precision PXI Source Measure Unit

4-Channel, ±24 V, 150 ma PXI Source Measure Unit

4-Channel ±10 V, 100 ma, Precision PXI Source Measure Unit

16-Bit, 120 MS/s, 12 Channel DC/16 Channel AC Receiver Adapter Module

4-Channel ±10 V, 100 ma, Precision PXI Source Measure Unit

4-Channel, ±24 V, 150 ma Precision PXI Source Measure Unit

Related Information Refer to the NI Switches Help for detailed topology information.

Power Amplifier. Input Characteristics. SPECIFICATIONS NI PXIe-4610 Power Amplifier. Signal Range

NI USB Contents DEVICE SPECIFICATIONS. 50 MS/s Bus-Powered USB Oscilloscope

This document lists the specifications for the NI PXI The PXI-5900 is a differential amplifier.

Note Using the NI 5751/5751B in a manner not described in this document may impair the protection that the NI 5751/5751B provides.

NI 9216 DATASHEET. 8 RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100

NI 9207 DATASHEET. 16 AI, ±20 ma/±10 V, 24 Bit, 500 S/s Aggregate

NI 9220 DATASHEET. 16 AI, ±10 V, 16 Bit, 100 ks/s/ch Simultaneous. DSUB or push-in springterminal. 250 Vrms, CAT II, channelto-earth

PXIe Contents SPECIFICATIONS. 2-Channel, 60 V, 1 A PXI Programmable Power Supply. These specifications apply to the PXIe-4112.

8-Ch 24 V Sinking DI, 8-Ch 24 V Sourcing DO SIL3 Capable

Specifications are typical and valid from -40 C to +85 C unless otherwise noted. Galvanic isolation between channels and to chassis

R Series for USB Multifunction RIO with Kintex-7 70T FPGA. may impair the protection the NI USB-7855R provides.

PXIe, 6½-Digit, ±300 V, Onboard 1.8 MS/s Isolated Digitizer,PXI Digital Multimeter

GETTING STARTED GUIDE NI AI Differential/32 AI Single-Ended, ±200 mv to ±10 V, 16 Bit, 250 ks/s Aggregate, Fuel-Cell Measurements

R Series for USB Multifunction RIO with Kintex-7 70T FPGA

NI 9213 DATASHEET. 16 TC, ±78 mv, 24 Bit, 75 S/s Aggregate

100-SPST (latching), 50-DPST. Refer to the NI Switches Help at ni.com/manuals for detailed topology information.

PCI Express, 6½-Digit, ±300 V Digital Multimeter Device

PXIe Contents SPECIFICATIONS. ±60 V, 3 A System PXI Source Measure Unit. These specifications apply to the PXIe-4138.

Input Characteristics. Measurement Range. SPECIFICATIONS NI PXIe-4357

NI 9213 DATASHEET. 16 TC, ±78 mv, 24 Bit, 75 S/s Aggregate

NI 9770 DATASHEET. 30 khz to 100 MHz, 50 Ω, AC Coupled RF Receiver Module

Current ON state current ma minimum, 6 ma typical, 10 ma maximum OFF state current ma maximum

PXIe Contents SPECIFICATIONS. ±200 V, 1 A System PXI Source Measure Unit. These specifications apply to the PXIe-4136.

6½-Digit, ±300 V, 1.8 MS/s Isolated Digitizer Included, PCI Digital Multimeter Device

Related Information Refer to the NI Switches Help for detailed topology information.

NI Channel, TTL Digital Input/Output Module

OPERATING INSTRUCTIONS AND SPECIFICATIONS NI Port, RS485/RS422 Serial Module

NI PXI-2520 Specifications 80-Channel SPST Relay Module

NI 9219 DATASHEET. 100 S/s/channel, 4-Channel C Series Universal Analog Input Module

NI PXI-2521 Specifications 40-Channel DPST Relay Module

NI Channel SPST Electromechanical Relay Module

4-Slot, Extended Temperature, Ethernet CompactDAQ Chassis

8-Slot, Extended Temperature, Ethernet CompactDAQ Chassis

SCXI MHz Quad 8x1 50 Ω Multiplexer

PXIe Contents SPECIFICATIONS. ±60 V, 3 A Precision System PXI Source Measure Unit. These specifications apply to the PXIe-4139.

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9207E 16-Channel, ±20 ma/±10 V, 24-Bit Analog Input Module

NI PXI-2797 Specifications 40 GHz 6 1 Terminated 50 Ω Multiplexer

PXIe Contents SPECIFICATIONS. ±200 V, 1 A Precision System PXI Source Measure Unit. These specifications apply to the PXIe-4137.

NI 2865A 0.3 A Matrix Cards for NI SwitchBlock

mmwave Transceiver System

DATASHEET NI Channel, 250 V Sinking Digital Input Module

NI 9205 DATASHEET. 16 AI Differential/32 AI Single-Ended, ±200 mv to ±10 V, 16 Bit, 250 ks/s Aggregate

NI Channel, Universal Digital Input Module

R Series Reconfigurable I/O Module (AI, AO, DIO) for PXI Express, 6 AI, 18 AO, 48 DIO, 1 MS/s AIO, 512 MB DRAM, Kintex-7 325T FPGA

R Series for USB Multifunction RIO with Kintex-7 160T FPGA. ni.com/manuals

PCI Contents SPECIFICATIONS. 8-Channel, 12-Bit, 60 MHz PCI Oscilloscope Device

R Series Reconfigurable I/O Module (AI, AO, DIO) for PXI Express, 8 AI, 8 AO, 48 DIO, 500 ks/s AI, Kintex-7 160T FPGA

NI PXI-2555 Specifications

Transcription:

GETTING STARTED GUIDE NI 9882 1-Port DeviceNet Module

This document explains how to connect to the NI 9882. The NI 9882 module requires the latest NI-DeviceNet software to be installed. The latest version of the NI-DeviceNet software is at ni.com/downloads. Note Before you begin, complete the software and hardware installation procedures in your chassis documentation. Note The guidelines in this document are specific to the NI 9882. The other components in the system might not meet the same safety ratings. Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system. Safety Guidelines Operate the NI 9882 only as described in this document. Caution Do not operate the NI 9882 in a manner not specified in this document. Product misuse can result in a hazard. You can compromise the safety protection 2 ni.com NI 9882 Getting Started Guide

built into the product if the product is damaged in any way. If the product is damaged, return it to NI for repair. Safety Guidelines for Hazardous Locations The NI 9882 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx na IIC T4 and Ex na IIC T4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the NI 9882 in a potentially explosive environment. Not following these guidelines may result in serious injury or death. Caution Do not disconnect I/O-side wires or connectors unless power has been switched off or the area is known to be nonhazardous. Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous. Caution Substitution of components may impair suitability for Class I, Division 2. NI 9882 Getting Started Guide National Instruments 3

Caution For Division 2 and Zone 2 applications, install the system in an enclosure rated to at least IP54 as defined by IEC/EN 60079-15. Caution For Division 2 and Zone 2 applications, install a protection device between the external power supply and the Vsup pin. The device must prevent the Vsup-to-COM voltage from exceeding 50 V if there is a transient overvoltage condition. Caution For Zone 2 applications, install a protection device between the CAN signals and the NI 9882 CAN pins. The device must prevent the CAN Port-to-COM voltage from exceeding 55 V if there is a transient overvoltage condition. Special Conditions for Hazardous Locations Use in Europe and Internationally The NI 9882 has been evaluated as Ex na IIC T4 Gc equipment under DEMKO Certificate No. 07 ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI 9882 is marked II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 C Ta 70 C. If you are using the NI 9882 in Gas Group IIC hazardous locations, you must use the device in 4 ni.com NI 9882 Getting Started Guide

an NI chassis that has been evaluated as Ex nc IIC T4, Ex IIC T4, Ex na IIC T4, or Ex nl IIC T4 equipment. Caution You must make sure that transient disturbances do not exceed 140% of the rated voltage. Caution The system shall only be used in an area of not more than Pollution Degree 2, as defined in IEC 60664-1. Caution The system shall be mounted in an ATEX/IECEx-certified enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15. Caution The enclosure must have a door or cover accessible only by the use of a tool. Wiring the NI 9882 The NI 9882 has one 9-pin male D-Sub connector that provides connections to a CAN bus. The NI 9882 has pins for CAN_H and CAN_L, to which you connect the CAN bus signals. Connect these signals using twisted-pair cable. NI 9882 Getting Started Guide National Instruments 5

The port has two common pins (COM) that are internally connected to the module s isolated reference and serve as the reference ground for CAN_H and CAN_L. You can connect the CAN bus reference ground (sometimes referred to as CAN_V-) to one or both COM pins. The port also has an optional shield pin, SHLD, that you can connect to a shielded CAN cable. Connecting SHLD may improve signal integrity and EMC performance in a noisy environment. Caution You must use a UL listed ITE power supply marked LPS with the NI 9882. The NI 9882 requires an external power supply of +9 to +30 V to operate. Supply power to the NI 9882 V SUP pin. Note Power on V SUP is required for DeviceNet operation. The NI 9882 pinout is listed in Table 1. The NI 9882 features software-selectable bus termination for High-Speed CAN transceivers. On the NI 9882, you can enable 120 Ω termination resistors between CAN_H and CAN_L through an API call. Table 3 lists recommended termination resistor values. 6 ni.com NI 9882 Getting Started Guide

Table 1. Pin Assignments for the NI 9882 Connector Pin Signal 1 No Connection (NC) 2 CAN_L 3 COM 6 7 8 9 1 2 3 4 5 4 NC 5 SHLD 6 COM 7 CAN_H 8 NC 9 V SUP CAN Bus Topology and Termination A CAN bus consists of two or more CAN nodes cabled together. The CAN_H and CAN_L pins of each node are connected to the NI 9882 Getting Started Guide National Instruments 7

main CAN bus cable through a short connection known as a stub. The pair of signal wires, CAN_H and CAN_L, constitutes a transmission line. If the transmission line is not terminated, each signal change on the bus causes reflections that may cause communication errors. Because the CAN bus is bidirectional, both ends of the cable must be terminated. However, this requirement does not mean that every node on the bus should have a termination resistor; only the two nodes at the far end of the cable should have termination resistors. Figure 1 shows a simplified diagram of a CAN bus with multiple CAN nodes and proper termination resistor (R t ) locations. 8 ni.com NI 9882 Getting Started Guide

Figure 1. CAN Bus Topology and Termination Resistor Locations Bus Cable Length CAN_H CAN_H CAN Node R t R t CAN Node CAN_L CAN_L CAN_L CAN_H CAN_L CAN_H Stub Length CAN Node CAN Node Connecting a CAN Bus to the NI 9882 You can connect the NI 9882 port to any location on a CAN bus. Figure 2 shows one example of connecting the NI 9882 directly to one CAN node. NI 9882 Getting Started Guide National Instruments 9

Figure 2. Connecting the NI 9882 to a CAN Device (SHLD) (SHLD) CAN Device CAN_H R t CAN_L V sup CAN Cable (With Optional Shield) CAN_H R t CAN_L V sup C Series Module COM COM Cabling Requirements for the NI 9882 Cable Specifications Cables should meet the physical medium requirements specified in ISO 11898, shown in the following table. Belden cable (3084A) meets all these requirements and should be suitable for most applications. 10 ni.com NI 9882 Getting Started Guide

Table 2. ISO 11898 Specifications for Characteristics of a CAN_H and CAN_L Pair of Wires Characteristic Value Impedance 95 Ω min, 120 Ω nominal, 140 Ω max Length-related resistance Specific line delay 70 mω/m nominal 5 ns/m nominal Termination Resistors The termination resistors (Rt) should match the nominal impedance of the CAN cable and therefore comply with the values in the following table. NI 9882 Getting Started Guide National Instruments 11

Table 3. Termination Resistor Specification Characteristic Value Condition Termination resistor, R t 100 Ω min, Minimum power dissipation: 120 Ω nominal, 220 mw 130 Ω max Cable Lengths The cabling characteristics and desired bit transmission rates affect the allowable cable length. You can find detailed cable length recommendations in the ISO 11898, CiA DS 102, and DeviceNet specifications. ISO 11898 specifies 40 m total cable length with a maximum stub length of 0.3 m for a bit rate of 1 Mb/s. The ISO 11898 specification says that significantly longer cable lengths may be allowed at lower bit rates, but you should analyze each node for signal integrity problems. 12 ni.com NI 9882 Getting Started Guide

Number of CAN Nodes The maximum number of nodes depends on the electrical characteristics of the nodes on the network. If all nodes meet the ISO 11898 requirements, you can connect at least 30 nodes to the bus. You can connect higher numbers of nodes if the nodes electrical characteristics do not degrade signal quality below ISO 11898 signal level specifications. The NI 9882 electrical characteristics allow at least 110 CAN ports on a network. NI 9882 Hardware Overview The NI 9882 has one full-featured CAN port that is isolated from the other modules in the system. The port has a Bosch DCAN CAN controller that is CAN 2.0B-compatible and fully supports both 11-bit and 29-bit identifiers. The port also has an NXP PCA82C251T High-Speed CAN transceiver that is fully compatible with the ISO 11898 standard and supports baud rates up to 1 Mbps. NI 9882 Getting Started Guide National Instruments 13

+ _ Figure 3. NI 9882 Hardware Overview V sup COM Ext Pwr Supply Required CAN Controller Rx Tx Rx Tx CAN Transceiver CAN_H CAN_L NI 9882 Specifications The following specifications are typical for the range -40 C to 70 C unless otherwise noted. High-Speed CAN Characteristics Transceiver Max baud rate NXP PCA82C251T 1 Mbps 14 ni.com NI 9882 Getting Started Guide

CAN_H, CAN_L bus lines voltage CAN Supply voltage range (V SUP ) MTBF -27 to +40 VDC +9 to +30 VDC Contact NI for Bellcore MTBF or MIL-HDBK-217F specifications. Power Requirements Power consumption from chassis Active mode 1 W max Sleep mode 2.55 mw max Thermal dissipation (at 70 C) Active mode 1.25 W max Sleep mode 250 mw max NI 9882 Getting Started Guide National Instruments 15

Physical Characteristics To clean the module, wipe it with a dry towel. Weight Approx. 144 g (5.0 oz) Safety Connect only voltages that are within the following limits: Maximum Voltage 1 Port-to-COM Isolation Port-to-earth ground Continuous Withstand -27 to +40 VDC max, Measurement Category I 60 VDC, Measurement Category I 500 V rms, verified by a 5 s dielectric withstand test 1 The maximum voltage that can be applied or output between any port or V SUP terminal and a COM terminal without creating a safety hazard. 16 ni.com NI 9882 Getting Started Guide

Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics. Caution Do not connect the NI 9882 to signals or use for measurements within Measurement Categories II, III, or IV. Safety and Hazardous Locations Standards This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use: IEC 61010-1, EN 61010-1 UL 61010-1, CSA 61010-1 EN 60079-0:2012, EN 60079-15:2010 IEC 60079-0: Ed 6, IEC 60079-15; Ed 4 UL 60079-0; Ed 5, UL 60079-15; Ed 3 CSA 60079-0:2011, CSA 60079-15:2012 NI 9882 Getting Started Guide National Instruments 17

Note For UL and other safety certifications, refer to the product label or the Online Product Certification section. Hazardous Locations U.S. (UL) Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2, AEx na IIC T4 Canada (C-UL) Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2, Ex na IIC T4 Europe (DEMKO) Ex na IIC T4 Gc Electromagnetic Compatibility This product meets the requirements of the following EMC standards for sensitive electrical equipment for measurement, control, and laboratory use: EN 61326 (IEC 61326): Class A emissions; Industrial immunity EN 55011 (CISPR 11): Group 1, Class A emissions AS/NZS CISPR 11: Group 1, Class A emissions 18 ni.com NI 9882 Getting Started Guide

FCC 47 CFR Part 15B: Class A emissions ICES-001: Class A emissions Note For the standards applied to assess the EMC of this product, refer to the Online Product Certification section. Note For EMC compliance, operate this device with shielded cables. CE Compliance This product meets the essential requirements of applicable European Directives, as follows: 2014/35/EU; Low-Voltage Directive (safety) 2014/30/EU; Electromagnetic Compatibility Directive (EMC) 94/9/EC; Potentially Explosive Atmospheres (ATEX) Online Product Certification Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for this product, visit ni.com/ NI 9882 Getting Started Guide National Instruments 19

certification, search by model number or product line, and click the appropriate link in the Certification column. Shock and Vibration To meet these specifications, you must panel mount the system. Operating vibration Random (IEC 60068-2-64) Sinusoidal (IEC 60068-2-6) Operating shock (IEC 60068-2-27) 5 g rms, 10 Hz to 500 Hz 5 g, 10 Hz to 500 Hz 30 g, 11 ms half sine; 50 g, 3 ms half sine; 18 shocks at 6 orientations 20 ni.com NI 9882 Getting Started Guide

Environmental Refer to the manual for the chassis you are using for more information about meeting these specifications. Operating temperature -40 C to 70 C (IEC 60068-2-1, IEC 60068-2-2) Storage temperature -40 C to 85 C (IEC 60068-2-1, IEC 60068-2-2) Ingress protection Operating humidity (IEC 60068-2-78) Storage humidity (IEC 60068-2-78) Pollution Degree 2 Maximum altitude Indoor use only. IP40 10% RH to 90% RH, noncondensing 5% RH to 95% RH, noncondensing 2,000 m NI 9882 Getting Started Guide National Instruments 21

Environmental Management NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers. For additional environmental information, refer to the Minimize Our Environmental Impact web page at ni.com/environment. This page contains the environmental regulations and directives with which NI complies, as well as other environmental information not included in this document. Waste Electrical and Electronic Equipment (WEEE) EU Customers At the end of the product life cycle, all NI products must be disposed of according to local laws and regulations. For more information about how to recycle NI products in your region, visit ni.com/ environment/weee. 22 ni.com NI 9882 Getting Started Guide

电子信息产品污染控制管理办法 ( 中国 RoHS) 中国客户 National Instruments 符合中国电子信息产品中限制使用某些有害物质指令 (RoHS) 关于 National Instruments 中国 RoHS 合规性信息, 请登录 ni.com/environment/rohs_china (For information about China RoHS compliance, go to ni.com/environment/rohs_china.) Worldwide Support and Services The NI website is your complete resource for technical support. At ni.com/support, you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers. Visit ni.com/services for NI Factory Installation Services, repairs, extended warranty, and other services. Visit ni.com/register to register your NI product. Product registration facilitates technical support and ensures that you receive important information updates from NI. NI 9882 Getting Started Guide National Instruments 23

A Declaration of Conformity (DoC) is our claim of compliance with the Council of the European Communities using the manufacturer s declaration of conformity. This system affords the user protection for electromagnetic compatibility (EMC) and product safety. You can obtain the DoC for your product by visiting ni.com/certification. If your product supports calibration, you can obtain the calibration certificate for your product at ni.com/calibration. NI corporate headquarters is located at 11500 North Mopac Expressway, Austin, Texas, 78759-3504. NI also has offices located around the world. For telephone support in the United States, create your service request at ni.com/support or dial 1 866 ASK MYNI (275 6964). For telephone support outside the United States, visit the Worldwide Offices section of ni.com/niglobal to access the branch office websites, which provide up-to-date contact information, support phone numbers, email addresses, and current events. 24 ni.com NI 9882 Getting Started Guide

Refer to the NI Trademarks and Logo Guidelines at ni.com/trademarks for information on NI trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering NI products/technology, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your media, or the National Instruments Patent Notice at ni.com/patents. You can find information about end-user license agreements (EULAs) and third-party legal notices in the readme file for your NI product. Refer to the Export Compliance Information at ni.com/legal/export-compliance for the NI global trade compliance policy and how to obtain relevant HTS codes, ECCNs, and other import/ export data. NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR ANY ERRORS. U.S. Government Customers: The data contained in this manual was developed at private expense and is subject to the applicable limited rights and restricted data rights as set forth in FAR 52.227-14, DFAR 252.227-7014, and DFAR 252.227-7015. 2010 2016 National Instruments. All rights reserved. 373253E-01 Mar16