Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder. Installation Instructions Revised 9/2/2016

Similar documents
Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems Overview Revised 9/2/2016

COMPACT DECK. Compact Deck SOUTHERN FOREST PRODUCTS ASSOCIATION SOUTHEASTERN LUMBER MANUFACTURERS ASSOCIATION

Lateral Support. Decks over 24 above grade require lateral support* *Exceptions to be discussed later

TRELLIS. Trellis SOUTHERN FOREST PRODUCTS ASSOCIATION SOUTHEASTERN LUMBER MANUFACTURERS ASSOCIATION

PRESCRIPTIVE RESIDENTIAL DECK CONSTRUCTION GUIDE. Based on the 2015 International Residential Code

FREDERICK COUNTY USBC/IRC 2015

SDWH TIMBER-HEX Screw

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

DECKS. Stairway illumination Positive attachment of ledger Lateral load connection required board (R507.2) required (R ) (R311.7.

Load Tables, Technical Data and Installation Instructions

STORAGE SHED. Storage Shed SOUTHERN FOREST PRODUCTS ASSOCIATION SOUTHEASTERN LUMBER MANUFACTURERS ASSOCIATION

Prescriptive Residential Wood Deck Construction Guide Based on the 2006 International Residential Code

Typical Deck Details Based on the City of Nixa Residential Deck Ordinance

Typical Deck Details

Page 1 of 70

24" max from each end of the ledger. See detail 6A & 6B, typ. both ends IRC R Ledger R507.2

eb^sv=qfj_bo UNIVERSITY OF WISCONSIN - STOUT COLLEGE OF SCIENCE TECHNOLOGY ENGINEERING & MATHEMATICS Architectural Technology AEC 233

Typical Deck Details

DIVISION 6 WOOD AND PLASTICS

THE ENGINEERED WOOD ASSOCIATION

REVISION CHANGES: REV. NO. REV. DATE

City of Virginia Beach, Virginia Typical Deck Details

Originally Issued: 09/26/2012 Revised: 10/15/2018 Valid Through: 09/30/2019

Deck Evaluation Checklist

Lateral Tension System

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013.

Deck Design Guide. One and Two Family Residential Dwellings

FASTENERS BUILDING DEPARTMENT

Pulaski County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code

Maryland Building Officials Association Typical Deck Details

SECTION CARPENTRY

When is a Building Permit Required? Deck Details: What Must be Submitted with a Building Permit Application?

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: SCREW PRODUCTS, INC.

10x12 FOUNDATION GUIDE 10x12 TRICO AND FLORA SHEDS

Main Floor Revisions: 38' 0" Rm1 H3 50' 0" Bk1 B1 Rm2 B5 (26)-2 H2 B2 H3 (3)-3 B3 (11)-4 Bk1 B1 (5)-5 Rm4 Bk1 Rm3 Bk1 24' 0" 6' 0" 20' 0" START FRAMIN

A. Rough carpentry includes but is not limited to the following:

ICC-ES Evaluation Report

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Typical Deck Details

ICC-ES Evaluation Report

How to Build Good Decks..

SECTION ROUGH CARPENTRY

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A

APA Performance Rated Rim Boards

COMPATIBILITY OF FASTENERS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Residential Decks. Typical Deck Details DECKING REQUIREMENTS

TRASH CAN & FIREWOOD STORAGE UNIT

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II


Product Catalog. Since 1980 The Natural Choice for Preservative-Treated Wood

ONE AND TWO FAMILY DWELLINGS Uncovered Decks July, 2007

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years.

3.1 General Provisions

SECTION ROUGH CARPENTRY

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

Originally Issued: 06/28/2012 Revised: 06/21/2017 Valid Through: 06/30/ Design

Attach Trusses and Rafters Faster

Featuring TJ Rim Board and TimberStrand LSL

Joint Evaluation Report

UL Construction No. 254

COMPACT DECK. Compact Deck Project Plan #850 Sheet 1 of Riverside Dr., Suite 212 Metairie, LA SouthernPine.com SouthernPineDecks.

APPLICATION FOR A BUILDING PERMIT

REPORT HOLDER: ISAIAH INDUSTRIES, INC. EVALUATION SUBJECT:

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK:

ROOFING City of Grand Rapids Building Safety Division

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: MiTek USA, INC.

Pressure-Treated Wood: The Next Generation

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.

THE BR BRICK BRACKET

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year.

4) Verify that the size of the supporting member can accommodate the connector s specified fasteners.

TRUS JOIST RIM BOARD. Featuring TJ Rim Board and TimberStrand LSL. Multiple thicknesses, grades, and products to cover all your rim board needs

ROOF-CEILING CONSTRUCTION

ROOF-CEILING CONSTRUCTION

ESR-1254 * DELETED BY CITY OF LOS ANGELES. Reissued April 1, 2006 This report is subject to re-examination in one year.

DBP Technical Data Series Rev. 0 Jan. 1, Pre Assembled Door Canopies

Hex Cap Screws Coarse & Fine Thread

Engineering Services Program

GLOSSARY OF TERMS SECTION 8

A. Product Data: For each type of process and factory-fabricated product indicated.

SECTION TRAFFIC SIGNAGE

PRE-ENGINEERED HORSE STALL SYSTEMS 4884 HSD STANDARD SLIDING DOOR. & Assembly. Installation Instructions

eco-shake INSTALLATION INSTRUCTION

IRC 2012 Code Compliant Wood Framed Residential details. Miss Installed Connectors with code references and remedies, discussion.

COMPOSITE SIDING INSTALLATION GUIDE

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Ohlson Project Property Owner: Kathy Ohlson Property Address: Deer Lake Rd. Derwood MD 20855

PRODUCT DESCRIPTION. This evaluation report includes aluminum clad wood skylights based on the following tested configurations:

GROUND-LEVEL DECK. Ground-Level Deck Riverside Dr., Suite 212 Metairie, LA SouthernPine.com SouthernPineDecks.com

Fastener Schedule. a, b, c. FASTENER Roof 3-8d (2 1 / ) / ) 3-10d. 3-10d ( ) 3-16d box nails. (3 1 2 toe nails on one side

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

Use the Design Properties (100% Load Duration) Table from Page 3 for questions 1-7

Trusted ICC ES PASLODE, Evaluation. report, or as to any. ICC-ES Evaluation

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL SHINGLES SECTION: METAL ROOF TILES REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Pryda Timber Connectors

Transcription:

Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder Installation Instructions Revised 9/2/2016

SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical information, disseminating industry news, and facilitating networking opportunities for manufacturers of roof trusses, wall panels and floor trusses. SBCA endeavors to expand component manufacturers market share and enhance the professionalism of the component manufacturing industry. Copyright 2016 Structural Building Components Association.

Minimum Ledger Requirements 2x10 or 2x12 lumber Specific gravity > 0.43 Identified by the grade mark of, or certificate of inspection issued by, an approved lumber grading or inspection bureau or agency.

Minimum Ledger Requirements Made of PPT (Preservative Pressure Treated) or code approved decay-resistant lumber Pressure treatment must be an approved process in accordance with American Wood Protection Association standards.

Step 1: Review Connection Details Determine fastener spacing based on the following conditions: Joist span (up to 18 ) Applicable loading (40 psf or 60 psf) Connection type (side) Fastener type (bolt or lag screw)

Step 1: Review Connection Details Vertical Load Connection Detail

Step 1: Review Connection Details Lateral Load Connection Detail Ledger Attached at Truss Side

Step 2: Install Over Structural Sheathing Install ledger directly over wood structural sheathing fastened to the wall per IRC Chapter 6. Maximum thickness of sheathing is 15/32"

Step 2: Install Over Structural Sheathing Attach ledger through wood structural sheathing into one of the following: 2-ply 2x4 truss end vertical 4x4 vertical web Key-block

Step 2: Install Over Structural Sheathing Attach ledger with: ½" x 6" lag screws or ½"-diameter Standard Hex bolts with washers and nuts Lag screws and bolts must meet the requirements of ANSI/ASME Standard B18.2.1

Step 2: Install Over Structural Sheathing Maximum one fastener per truss member or key-block. Install fasteners through the centerline of the truss member or key-block Position fasteners to avoid interfering with bottom and top chord joints and connector plates.

Step 3: Fastener Specification Lag screws and bolts must be installed according to 2015 NDS requirements. A "test" installation is recommended before drilling the lead holes, to ensure that the lead holes are neither too small nor too large.

Step 3: Fastener Specification ½" x 6" lag screws: Lead holes for the threaded portion must be 5/16". Clearance holes must be ½" and the same depth of penetration as the length of unthreaded shank. ½ diameter bolts: Holes must be a minimum of 17/32" to a maximum of 9/16".

Step 3: Fastener Specification All fasteners used with PPT wood must be hotdip zinc-coated including: Galvanized steel Stainless steel Silicon bronze Copper

Step 3: Fastener Specification Fasteners must meet ASTM A153, Class D, for fasteners 3/8" diameter and smaller or Class C for fasteners with diameters over 3/8". Lag screws, bolts, nuts and washers are permitted to be mechanically deposited zinccoated steel with coating weights in accordance with ASTM B695, Class 55, minimum.

Step 4: Hardware Specification All hardware (e.g., joist hangers, hold-down device, etc.) must be galvanized or stainless steel. Hardware hot-dipped prior to fabrication must meet ASTM A653, G-185 coating. Hardware hot-dipped post fabrication must meet ASTM A123.

Step 4: Hardware Specification Additional requirements include: Fasteners and hardware exposed to saltwater or located within 300' of a saltwater shoreline must be stainless steel grade 304 or 316. Fasteners and hardware must be of the same corrosion-resistant material. Other coated or non-ferrous fasteners or hardware must be approved by the authority having jurisdiction.

Step 5: Flashing Installation Install flashing at top of ledger for water tightness. Flashing must be corrosionresistant metal of minimum nominal 0.019" thickness or an approved non-metallic material. Do not use aluminum flashing in direct contact with lumber treated with preservatives containing copper, such as ACQ, Copper Azole or ACZA.

Step 6: Blocking Two-ply 2x4 truss end verticals, 4x4 truss vertical webs, and keyblocks connected to ledger with lag screws or bolts must have a specific gravity, G 0.42 (includes DF, HF, SP and SPF).

Step 6: Blocking Construct keyblocks with minimum 2x4 No. 2 or better lumber. Install key-blocks at required locations. Cut to fit tight.

Step 7: Connect Joist to Lateral Load Connection Apply minimum 2x_ SPF block of same depth as deck joists to one side of each vertical web or key-block to which the hold-down is attached.

Step 7: Connect Joist to Lateral Load Connection Cut block to fit tight between exterior sheathing and side of first interior floor truss. Carefully notch block for tight fit around top chord of ladder frame.

Step 7: Connect Joist to Lateral Load Connection Attach block to side of web or key-block and to floor sheathing with 10d nails @ 3 o.c.

Step 7: Connect Joist to Lateral Load Connection Apply Hold-Down capable of resisting 750 lbs minimum. Install hold-downs at four (4) locations, evenly distributed along ledger with one (1) hold-down within 2 of each end of ledger.

Step 7: Connect Joist to Lateral Load Connection Attach hold-down to vertical truss web or keyblocks with lag screw Minimum 3-1/2 penetration into web/keyblock and to deck joist per manufacturer s specifications.

Step 7: Connect Joist to Lateral Load Connection Install lag screw through center of web or keyblock so as not to damage or disturb connector plates.

References SRR 1408-01 - Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems