S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Similar documents
Distribution Transformers

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Howard Smart Transformer Specification Guide

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Substation transformers

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

SECTION TRANSFORMERS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Intelligent Distribution Transformer. Fine tune your distribution system to its most efficient operation for any given time of the day or year

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

TECHNICAL SPECIFICATION

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

General Electricity Company of Libya

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

7. INSPECTION AND TEST PROCEDURES

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Section 2 Outdoor Voltage Transformers

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

Liquid-Filled Transformers

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

CONTINUING EDUC ATION

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

CITY OF TACOMA Transmission & Distribution

American Electrical Institute

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Distribution/Substation Transformer

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

METER - INSTALLATION Pad Mount Transformer

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Article 250 Grounding & Bonding

The Variable Threshold Neutral Isolator (VTNI)

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Specialty Switches. Inertia Engineering & Machine Works, Inc Hardaway Road, Stockton CA 95215

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Back to the Basics Current Transformer (CT) Testing

DISTRIBUTION TRANSFORMER kv

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

Reference Number PPS 05 - (RIC Standard: EP SP)

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

35 kv Class M.O.V.E. DirectConnect elbow arrester

POTENTIAL TRANSFORMER

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

DISTRIBUTION TRANSFORMER 11 / kv

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Tab 8 Surge Arresters

Substation Design Volume VII

Insulation Co-ordination For HVDC Station

Regional Technical Seminar TAP CHANGERS

Distribution transformers Part 2 Ground mounted transformers not closecoupled

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

TECHNICAL INFORMATION

Steps for Selecting the Proper Transformer

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

MC CHANGER CABINET INSTALLATION INSTRUCTIONS

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Short-Circuit Current Calculations

Component Requirement Specification for SGI 500XT Isolation Transformer

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

HPS Universal BUCK-BOOST TRANSFORMERS

Reactor and inductor are names used interchangeably for this circuit device.

MATERIAL COMBINATION NUMBER 2: Corrosive environment requiring harder, wear-resistant seating faces and resistance to dezincification.

OIL-IMMERSED ARC-SUPPRESSION COILS

Power Processor - Series 700F 10KVA to 150KVA

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

Transcription:

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical characteristics of Single- Phase, Single Bushing, Oil-Filled (certified non-pcb), Overhead Distribution Transformers. 1.2 All characteristics, definitions, and terminology, except as specifically covered in this specification shall be in accordance with the latest revision of the following ANSI standards. C57.12.00 - IEEE Standard General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformers. C57.12.20 - Overhead-Type Distribution Transformers, 500 KVA and Smaller: High Voltage, 34500 Volts and Below: Low Voltage, 7970/13800Y Volts and Below. C57.12.90 - IEEE Standard Test Code for Liquid- Immersed Distribution, Power, and Regulating Transformers and IEEE Guide for Short- Circuit Testing of Distribution and Power Transformers. C57.12.91 - Guide for Loading Mineral-Oil-Immersed Overhead and Pad- Mounted Transformers rated 500 kva and less with 55 C or 65 C average winding rise. 1.3 In addition to the above requirements, the transformers shall also meet the requirements of the Rural Utility Service (RUS-formerly REA) Specification D-10 and Department of Energy (DOE) 10 CFR Part 431 Efficiency Compliance. 2.0 RATINGS 2.1 The transformer shall be designed in accordance with this specification and shall have one of the following kva ratings: 10, 15, 25, 37.5, 50, 75, 100, 167 L:\Material Standards Committee\1bushing conv transformer 1

<The applicable kva rating(s) shall be specified on Attachment A.> 2.2 The primary voltage and the basic insulation level (BIL) shall be 95 kv for 12,470 Grd. Y/7200 volts,125 kv for 24,940 Grd.Y/14,400 volts and 95 X 125 kv for 12,470 Grd. Y/7200 X 24,940 Grd. Y/14,400 volts (dual voltage primary). <The primary voltage shall be specified on Attachment A>. 2.2.1 Dual voltage transformer shall have dual voltage primary windings connected to an externally operable, dual voltage selector switch for de-energized operation only. Two operations (minimum) shall be required to change switch position. Unit to be shipped with voltage selector switch in highest voltage position. 2.3 The secondary voltage shall be 120/240 volts. The basic insulation level (BIL) of the secondary shall be 30 kv. All secondary windings for 10, 15 and 25 kva ratings shall be interlaced. 2.4 If specified on Attachment A, the transformer shall be furnished with full capacity high-voltage taps. The tap changer shall be clearly labeled to reflect that the transformer must be de-energized before operating the tap changer. If taps are required on dual voltage units, the taps shall be on the higher voltage (series) position only. The unit shall have one of the following tap configurations: Two - 2½% taps above and below rated voltage Four - 2½% taps below rated voltage 3.0 HIGH VOLTAGE BUSHINGS AND TERMINALS 3.1 The high-voltage bushings provided shall be wet process porcelain in accordance with Table 6 of ANSI C57.12.20. The high voltage bushing shall be located 180 from the secondary neutral bushing. 3.2 The bushing terminals provided shall be tin plated eyebolt type to accommodate both copper and aluminum conductors. The size of these terminals shall be in accordance with Table 10 of ANSI C57.12.20. 3.3 The bushing terminals shall be equipped with one of the following: PVC Birdguards Handwheel birdguards L:\Material Standards Committee\1bushing conv transformer 2

No birdguards <The applicable terminal configuration shall be specified on Attachment A.> 4.0 LOW VOLTAGE BUSHINGS AND TERMINALS 4.1 The low-voltage bushings provided shall be in accordance with Table 6 of ANSI C57.12.20. 4.2 The bushing terminals provided shall be tin plated, eyebolt type to accommodate both aluminum and copper conductors. The size of the terminals shall be in accordance with Table 12 of ANSI C57.12.20. 4.3 The internal secondary leads shall be permanently embossed with the letters A, B, C, and D per ANSI C57.12.00 and C57.12.20. This marking can be used as a means to locate such leads with respect to one another for internal reconnection. 4.4 The neutral bushing shall be connected to the tank by means of an adequately sized copper ground strap. Tank-end connection of the ground strap shall be made using a silicon-bronze or 300 series stainless steel bolt. 5.0 PROTECTION 5.1 The overvoltage protection shall be provided by a polymer housed, tank mounted, MOV surge arrester with ground lead isolator. Arrester shall be 10 ka (heavy duty) minimum duty cycle. Furnish 10 kv Class for 95 kv BIL and 18 kv class for 125 kv BIL. Arrester shall have an insulating PVC birdguard and shall be connected to the high voltage bushing with an insulated wire suitable for outdoor exposure. Mounting bolts on arrester bracket shall be made using a silicon-bronze or 300 series stainless steel bolt. <The lightning arrester housing shall be specified on Attachment A.> 6.0 TANK 6.1 The tank shall include a pressure relief device, located on the tank above the 140 C top-oil level between the hanger bracket in segment four and the primary bushing, as a means to relieve pressure in excess of pressure resulting from normal operation. The venting and sealing characteristics shall be as follows: 1. Cracking Pressure - 10 psig ± 2 psig L:\Material Standards Committee\1bushing conv transformer 3

2. Resealing Pressure - 6 psig minimum 3. Zero leakage from reseal pressure to -8 psig 4. Flow at 15 psig - 40 SCFM minimum The pressure relief device shall have a pull ring for manually reducing pressure to atmospheric level using a standard hook-stick and shall be capable of withstanding a static pull force of 25 pounds for one minute without permanent deformation. 6.2 The tank coating shall meet all requirements in ANSI C57.12.31 (Gray color). 6.3 The tank provided shall have a recessed tank bottom which offers protection when sliding over rough surfaces. 6.4 The tank shall have an internal mark which indicates the proper oil level per Section 6.2.3 of ANSI C57.12.20. 6.5 The tank shall be provided with a mild steel cover ring or center bolt design cover and a stainless steel bolt and washer with a stainless steel or silicon bronze nut. 6.6 The tank shall be complete with an anodized aluminum or stainless steel laser engraved nameplate. This nameplate shall meet ANSI Standard C57.12.00 for Nameplate B. The nameplate shall be visible when facing the secondary terminals and mounted on the lower hanger bracket in segment two. 6.7 The tank shall include arrester mounting pads, two complete grounding terminals mounted on the lower portion of the tank below the secondary terminals and adjacent to the hanger bracket, two sets of hanger brackets located on opposite sides of the tank and 90 from the secondary bushings, and lifting lugs. 6.8 The kva rating shall be durably marked in numerals not less than 2 ½ inches high on both sides of tank, one located under the secondary bushings and the other located opposite. L:\Material Standards Committee\1bushing conv transformer 4

7.0 SHIPPING 7.1 Unit shall be banded, blocked or bolted to a suitable wooden pallet with 2½ inch clearance for shipment. 7.2 A temporary bar code label shall be attached to the exterior of the transformer in accordance with ANSI C57.12.35. 7.3 The customer shall be notified at least 24 hours in advance of shipment as specified on Attachment A. Shipper shall give total number of units to be shipped and the weight of the heaviest unit(s). 8.0 TESTING AND LOSSES 8.1 All units shall be tested for no-load (20 C) losses, load (85 C) losses, percent impedance (85 C), and excitation current (100% voltage). Each unit shall be subjected to a full wave voltage impulse and leak test. The manufacturer shall provide certification upon request for all design and other tests listed in Table 17 of ANSI C57.12.00 including verification that the design has passed Short Circuit Criteria per ANSI C57.12.00 and ANSI C57.12.90. 8.2 The manufacturer shall provide and send electronically and by mail (if requested by Purchaser on Attachment A) Certified Test Reports (CTR) in IEEE 1388 format. The CTR shall guarantee the average no-load and load losses. No individual unit shall be shipped that exceeds guaranteed losses by more than 10% no load and/or 6% total loss. If actual average losses exceed the guaranteed value, the penalty will be as specified on Attachment A. 8.3 The CTR shall also report the following DOE efficiency values: 1. Standard Efficiency Level as specified in DOE Chart, Table I.1 2. Absolute Minimum Efficiency for any one unit calculated using DOE formula n=1. 3. Minimum Average Efficiency for number of units in the basic model as calculated using DOE s formula. 4. Number of units (n) in the basic model 5. Tested or calculated DOE Efficiency for each unit L:\Material Standards Committee\1bushing conv transformer 5

6. Average of the Tested DOE Efficiency for number of units in the basic model. 8.4 The radio influence voltage shall not exceed 100 micro-volts at 1000 khz when measured at 110% of rated voltage. RCD 4/22/02 (Original) Any exceptions to these specifications must be stated by the manufacturer when submitting the proposal. L:\Material Standards Committee\1bushing conv transformer 6

Attachment "A" Single Phase, Single Bushing Overhead Distribution Transformer Electric Cooperative Dated I. Rating (kva) [Quantity of each]: 10 15 25 37.5 50 75 100 167 II. Primary Voltage (volts): 12,470 Grd Y/ 7200 24,940 Grd Y/14,400 12,470 Grd Y/7200 X 24,940 Grd Y/14,400 III. Primary taps: None Two-2 1/2% above and below Four below IV. HV Bushing Terminals No Birdguards PVC Birdguards Handwheel Birdguards V. Loss Formula (Based on Present Worth): Total Owning Cost (TOC) = (1.5 X initial unit cost) + ( $8.00 X NL losses) + ( $2.00 X Load losses). Units within a +3% window of lowest TOC will be considered equal. VI. Penalty for Exceeding Guaranteed Losses: Total Penalty = [$ X (Average NL losses furnished - NL losses guaranteed) + $ X (Average Load losses furnished Load losses guaranteed)] X Total number of Units. This will apply for all units in each line item of the purchase order with no credits back to manufacturer. VII. The Certified Test Reports (CTR) shall be sent: At time of shipment monthly quarterly other By mail to VIII. Shipping: Notify at phone # at least 24 hours before shipment. Receiving hours are Monday through Friday. Ship to, SC. office in IX. Other Special requirements: L:\Material Standards Committee\1bushing conv transformer 7