HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL

Similar documents
Model 4800 O P E R AT I O N M A N U A L L O A D C E L L S U M M I N G T R A N S M I T T E R

MODEL AT-10 ANALOG TRANSMITTER

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

Series APD4059. For Load Cells/Pressure Transducer Transmitters. Field Rangeable, with Calibration Resistor. Standard Features.

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

MODEL UBP-10 UNIVERSAL IN-LINE TRANSDUCER AMPLIFIER BI-POLAR SUPPLY, 0-10 VOLT OUTPUT

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5


INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS

WEIGHING SYSTEM CALIBRATION USING A LOAD CELL SIMULATOR

INSTALLATION & OPERATING MANUAL. AT 08 Analog Transmitter

Non-Submersible Industrial Pressure Transducer

Installation and Operating Manual

TECHNICAL MANUAL. SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100

MINCO PRODUCTS, INC Commerce Lane, Minneapolis, Minnesota U.S.A. Telephone: (763) FAX: (763)

DRG-SC Series Signal Conditioners

TECHNICAL MANUAL. SERIES AP5103 DIN-Rail DC Strain Gage Conditioner ISO 9001/AS9100

User's Manual: Series 250T AC Current Input (External Sensor) Two-Wire Transmitters

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

670K9 SORtrax Level Transmitter

Isolated, Frequency Input 5B45 / 5B46 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

APPLICATION NOTE 695 New ICs Revolutionize The Sensor Interface

CSG110 Strain Gauge Universal Amplifier

LCT100. Load Cell Tester User s Guide (v1711) Anyload Transducer Co. Ltd Website:

MZB SERIES. Intrinsically Safe Shunt Diode Safety Barriers. Phone: Fax: Web: -

AD-8100 & AD-8200 Servo Amplifiers

12/4/ X3 Bridge Amplifier. Resistive bridge amplifier with integrated excitation and power conditioning. Logos Electromechanical

ISOLATED 4-20 ma TRANSMITTERS

FC Series Signal Conditioners

TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A

Installation, Operation and Maintenance Manual

250T Loop-Powered (2-wire) Transmitter 250T. Input. Isolation. 350T DC-Powered (3-wire) Transmitter 350T. Input. Isolation

SB.5.1 MODEL STRAIN GAGE CONDITIONER INSTRUCTION MANUAL. Instrument Series

MICROTC LINEAR THERMOCOUPLE AMPLIFIER OPERATOR S MANUAL

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806

Isolated, Linearized Thermocouple Input 5B47 FEATURES APPLICATIONS PRODUCT OVERVIEW

Making Basic Strain Measurements

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module

Installation, Operation and Maintenance Manual

SENSOTEC, INC Arlingate Lane Columbus, Ohio Phone (614) Facsimile (614) Toll Free Free (800)

Load Cell Accessories and Services

TRANSDUCER IN-LINE AMPLIFIER

Model TS. Transducer Simulator User s Guide. Sensotec Sensors

SEM104 SERIES. SEM104P Pt100 Temperature Transmitter. SEM104TC Thermocouple Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

Exercise 2: Temperature Measurement

The Harvard Research Carrier Signal Conditioner User s Manual

Uni-Mux XQL Multi-Channel Data Acquisition Module

MODEL PAXLPV PAX LITE PROCESS VOLT METER

IOM. Model 1050 Strain Gage Transmitter Installation & Operation Manual. (Cage Code #1MU21)

CAH CARD. user leaflet. 1 of 15. Copyright Issue 12.1 January 2015

Pro-Weigh 84/SS/FLP Lo Pro 90 / SS Installation Guide. Version 1.0

Stand Alone Rudder Angle Indicator System

ICA1 & ICA2 S and H Versions Strain Gauge or Load Cell Embedded Analogue Amplifier

Current Probes. User Manual

HUMITRAN-RHT & RH RELATIVE HUMIDITY/TEMPERATURE TRANSMITTER RELATIVE HUMIDITY TRANSMITTER

RENATO DESIRÒ PARABIAGO (MI) Via Sant Anna, 51 Tel Fax

DLVP A OPERATOR S MANUAL

User s Manual for Integrator Short Pulse ISP16 10JUN2016

ARD154. DIN rail mountable amplifier for strain gage sensors. User s guide. User s guide ARD CONNECTING 4-WIRE SENSORS

Materials (other materials see WIKA diaphragm seal program) Model S-10

GE Fanuc IC695ALG312. Rx3i PacSystem

Model LD-LPIX EXPLOSION-PROOF LOOP POWERED INDICATOR

2-wire level transmitter

Princo MagneLevel Model LML

Signal Conditioning Amplifier

Part Numbers. SNAP-AIARMS-i SNAP-AIARMS-i-FM* SNAP-AIVRMS-i SNAP-AIVRMS-i-FM* SNAP-AIMA-i. SNAP-AIMA-iSRC SNAP-AIMA-iSRC-FM* SNAP-AIMA2-i

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Thermocouple Conditioner and Setpoint Controller AD596*/AD597*

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

ZT-4 Tonnage Load Module By Toledo Integrated Systems User s Manual

SB.5.1 MODEL STRAIN GAGE CONDITIONER INSTRUCTION MANUAL. Instrument Series

BA507C & BA508C loop-powered 3½ digit panel mounting indicators

Model C STRAIN GAGE LOAD CELL. Installation and Operating Manual

SENSOTEC UNIVERSAL INLINE TRANSDUCER AMPLIFIER BIPOLAR VOLTAGE MODEL. $!}~ f?(' 7. ()ept 1200 CHESAPEAKE AVE" COLUMBUS OHIO (614)

LAUREL ELECTRONICS, INC.

Signal Conditioning Amplifier

Load cell system fault finding guide (Application Note: Number AN1)

USB-2404-UI Specifications

MODEL: M2DYS SEN TRONIC AG

Exercise 3: Voltage in a Series Resistive Circuit

MODEL PAXLCL PAX LITE CURRENT LOOP METER

KING-GAGE KING. ES2 Liquid Level Transmitter. Installation and Operation Instructions ma Liquid Level Transmitter EX-1834

Isolated Linearized 4-Wire RTD Input 5B35 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Model 176 and 178 DC Amplifiers

Signal Conditioning Amplifier

Model TL Linearized Platinum Resistance Thermometer Temperature Transmitter Instruction Manual

About Laurel Electronics & FLW, Inc.

LOAD CELL TROUBLESHOOTING

DO NOT USE UNIT POWER

ENGINE GOVERNING SYSTEMS LSM200 SERIES LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

269 Troubleshooting Guide 11/4/98 1

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition

What causes the Out-of-Balance Current in the coax and why does it Radiate?

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC.

LCA-460 Strain Amplifier Signal Conditioner Modules for Strain Gages, Load Cells, and Transducers

Torque Sensor Accessories and Services

OPERATING INSTRUCTIONS

Process Calibrator. TechChek 820

REQUIRED SKILLS AND KNOWLEDGE UEENEEE104A. Topic and Description NIDA Lesson CARD #

Transcription:

Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Corporate Headquarters 9440 Carroll Park Drive San Diego, CA 92121 Phone: (858) 278-2900 FAX: (858) 278-6700 Web-Site: http://www.hardysolutions.com Hardy Process Solutions Doc. Number: 0596-0138-01 Rev F Copyright 1999 to 2013 Hardy Process Solutions All Rights Reserved. Printed in the U.S.A. (941028)

1-2

Table of Contents Table of Contents Overview 1 Specifications 2 Physical Dimensions 2 Power Requirement 2 Load Cell Excitation 2 Zero Offset Range 2 Sensitivity 2 Linearity 2 Operating Temperature Range 2 Temperature Coefficient 3 Signal Current Ripple 3 Power Supply Rejection 3 Approvals HI 2204LT 3 Installation 3 Junction Box with Strain Gage Summing Board 3 Input - Strain Gage Transducer 4 Output/Power Loop 4 Earth Ground and Signal Return 5 Precautions on Grounding 6 Isolation 7 Calibration 7 Calibration Controls 8 Coarse (Zero) 8 Fine (Zero) 8 Span 8 Calibration Procedures 8 Example 9 Trouble Shooting Procedures 10 Malfunction: No Output 10 Malfunction: No Change in Input 10 Malfunction: Output Drifts 10 i

HI 2204 LT ii

Overview The model HI 2204LT Loop Powered Level Weight Transmitter furnishes power to strain gage transducers, measures the return voltage, and adjusts the 4-20 milli amp loop current to be proportional to the transducer signal. The HI 2204LT is not Factory Mutual approved and should not be used in a hazardous environment. The HI 2204LT can be used to transmit any strain gage signal with a bridge resistance of more than 88 ohms. This allows transmission of pressure, load, weight, force and torque signals including up to four 350 ohm, full bridge, load cells. The HI 2204LT powers itself and the attached strain gage transducers from the 4-20 ma loop power. This allows sensitive strain gage signals to be transmitted over long distances without the expense of installing additional power to remote locations. A common, low-cost power supply can be placed anywhere in the 4-20 ma loop. As the power supply provides loop power, the HI 2204LT controls the current flow (4-20 ma) representing the strain gage signal and receiving devices can be placed anywhere along the loop to monitor current flow. Typical receiving devices include: Chart Records Panel Meters Bar Graphs Programmable Controllers Computers Relay Set Point Modules Most receiving devices may be characterized as a load resistor allowing the 4-20 ma signal to cause a proportional voltage drop across it. Multiple receivers may be placed on the loop provided the loop power supply can drive the combined loads. this can be calculated by adding the voltage requirements of the HI 2204LT (14 VDC) to that of each receiving device (loop resistance x 20 ma). 1

The transmitter applies power to each transducer in pulses a few milliseconds long at a rate of 90 pulses per second. The transmitter measures the voltage across the output terminals of the transducer with each power pulse, and it converts the average into a smooth current that varies with the transducer signal. This method of powering the transducer allows the transmitter to power up to four load cells. Though each load cell requires more than 4 ma excitation, the transmitter itself draws no more than 4 ma average current at zero weight load, and no more than 20 ma average current at full scale. The transmitter is potted and sealed to withstand typical industrial environments. It is small enough to be mounted on a load cell summing board inside of a standard 5 x 7 x 3.5 NEMA 4 enclosure. Specifications Physical Dimensions Power Requirement Load Cell Excitation Zero Offset Range Length: 4.50 Inches (114.3 mm) Width: 2.15 Inches (54.6 mm) Height: 1.30 Inches 33.02 mm) Weight: 8 oz. (.227 Kgs) Minimum: 15 VDC Maximum: 50 VDC Zero Scale: 4 ma Full Scale: 20 ma 5 V (pulsed) Coarse: 2 mv/v fine: 0.04 mv/v Sensitivity 3 mv/v (Continuously Adjustable from 1 mv/v to 3 mv/v) Linearity Operating Temperature Range 0.08% of full scale 0 o C to +60 o C (+32 o F to +140 o F) 2

Temperature Coefficient Signal Current Ripple Power Supply Rejection Approvals HI 2204LT Installation Junction Box with Strain Gage Summing Board 0.025% per degree Celsius 20 mv p-p at 20 ma into 500 ohms 0.015% (max) 20 to 30 V 0.10% (max) 15 to 50 V CE The Loop Powered Level Weight Transmitter is usually installed close to the strain gage(s) to minimize the expense of special wiring, such as load cell cable. Wiring positions are indicated on the top surface next to each terminal strip. The transmitter is available in a NEMA 4 junction box.(see Fig. 1) FIG. 1 HI 2204 (-A3 OR -A5) IN NEMA 4 JUNC- TION BOX/TOP VIEW The HI 2204LT-A3 and HI 2204LT-A5 Loop Powered Level Weight Transmitter comes mounted on a load cell summing board within a NEMA 4 junction box. The load cell summing board is designed to allow balancing pots to be installed if required. (See Fig. 2) 3

FIG. 2 TRANSMITTER INSTALLED ON LOAD CELL SUMMING BOARD (-A3 OR -A5 OPTION) Input - Strain Gage Transducer Output/Power Loop Strain Gage signals are typically very low in voltage causing them to be susceptible to noise. It is a good practice to isolate strain gage signals from high voltage (110 VAC) lines. It is highly recommended that the transducer signal wire be routed in its own conduit. The transducer cable should have a shield which can be earth grounded near the transmitter. The loop power connection provides power to the HI 2204LT and provides the 4-20 ma signal. The transmitter must have from 15 VDC to 50 VDC across its LOOP terminals at up to 20 ma (full scale output). since all devices in the output/power loop are in series minimum power supply voltage, at 20 ma, must equal the total voltage drop across all of the other devices in the loop, plus 15 VDC for the HI 2204LT. The transmitter output loop can be wired with any two conductor shielded cable. The two inner conductors are connected to the output of the transmitter at the two terminals marked LOOP. (See Fig. 3 & 4) Note which wire is connected to each terminal to maintain correct polarity within the loop. 4

FIG. 3 OUTPUT LOOP TERMINALS Receiver #1 Receiver #2 - + Loop Powered Level Weight Transmitter 4mA-20mA Receiver #3 + - Power Supply FIG. 4 OUTPUT/POWER LOOP WIRING NOTE: Earth Ground and Signal Return Be sure to shield the tie point for CE compliance. Earth Ground is used here to indicate a point actually connected to a path into the Earth s ground. The 5

term signal return is used to indicate a return path for signals to the negative side of the power supply, or in the case of the output/loop, signal return means the more negative side of the voltage being measured. (See Figs. 4 & 5) 110 VAC 110 VAC Relays Set Point RCVR + + Loop Powered Level + Isolator Weight Transmitter + + DC Power Supply + RCVR 110 VAC 110 VAC FIG. 5 TYPICAL SYSTEM WIRING WITH ISOLATION NOTE: Be sure to shield the tie point for CE compliance. Receivers may be inserted into the minus or the plus power supply/transmitter path, or both. It is not necessary that one of the transmitter output leads be connected directly to ground. Appropriate grounding and shielding helps to protect the signals from noise. However, it may be necessary to try various ground/shield configurations to find the best one for a particular installation. Figures 4 & 5 are examples only. The transducer cable shield should be connected to either the earth ground or the signal return, on the input side of the transmitter to protect against noise, but not to both. The recommended configuration consists of the transducer cable shield connected to the output/power cable shield and to the signal return. Precautions on Grounding 1. Do not connect the signal return to the earth ground at more than one point in the output/ power loop. 6

2. Any receiver or electronic device inserted in the output/power loop must be designed so that the connections to the loop are isolated from ground. NOTE: Only the one point where the loop is already grounded can accept a grounded lead. 3. Do not connect the earth ground to the signal return in the transmitter input circuit. 4. Do not connect any of the transducer signal wires to the earth ground. Isolation Calibration The AC power sources for this instrument must be separate and isolated from the power supplied to any switches, relays, solenoids, or motors which can introduce excessive noise into the instrument s circuits. Load cells and load cell signal wires are not typically grounded, and they are not typically connected to their shields or to the load cell case. If the recommendations given in the grounding and shielding section are followed, there will be no need for isolation in the transmitter/load-cell circuit. In fact, in the load cell circuit, isolation adds to the cost and inaccuracy and is not recommended. It is generally not necessary to provide isolation in the output loop. However, when ground-loop problems do occur, a Loop isolator designed to handle the 4 ma to 20 ma Loop Powered Level Weight Transmitter signal may be installed. (See Fig. 5) The HI 2204LT Loop Powered Level Weight Transmitter is calibrated at the factory for 4 ma current output with zero millivolts input and 20 ma output for 15 mv input (based on a 3mV/V input source and 5 V excitation). In most cases, the transmitter will require a very simple recalibration to the system in which it is installed. The calibration procedure provided is designed to be used either in new installations or for recalibration of existing systems, and will work with 3 mv/v or 2 mv/v load cells. Be sure to read all calibrations instructions before attempting to calibrate the instrument. 7

Calibration Controls Coarse (Zero) Fine (Zero) Span The Coarse Control is used to remove large deadloads or offsets such as the weight of the scale s platform, container or any other constant weight on the load cells which is part of the weighing equipment itself. This control can subtract as much as 65% of full scale from the transmitter s output. This control is a fine offset adjustment. Its range is sufficient to fine tune the COARSE adjustment. The Span Control adjust the gain of the transmitter. It determines how many millivolts (of transducer signal) per volt (of transducer excitation) will be represented by the 4 ma to 20 ma output range. The gain can be adjusted from 3 mv input per volt of excitation to as high as 0.8 mv input per volt of excitation. This broad range of sensitivity allows for the wide variation in transducer range that remains after deadload compensation is subtracted by the COARSE Zero adjustment. Calibration Procedures The measuring instruments used in the following procedure must be designed so that test leads are isolated from ground. These are either floating and/or isolated and/or differential types. Insertion of any measuring device, or voltage dropping resistor for a measuring device in the output/ powers loop requires that the power supply voltage be high enough to supply the extra voltage (See Input- Strain Gage Transducer). The following is an example using load cells in a weighing application. Step 1. Step 2. Remove any weight from the scale. Allow deadload to remain. If deadload is counterbalanced, also allow counterbalancing to remain. Install a milli ammeter, in series, into the output/power loop of the transmitter. If a voltmeter is to be used for measurements, 8

Step 3. HI 2204LT and a resistor for calibration is not already installed in the system, install a 100 ohm, +- 0.1%, 1/4 W resistor, in series, into the output/power loop of the transmitter. Voltmeter readings are show in parentheses. If a voltmeter is used, attach the voltmeter across the 100 ohm resistor. Step 4. Adjust the transmitter FINE control for a 4 ma (1/4 V) reading on the meter. If necessary, center the FINE control, and adjust COARSE control first. Step 5. Step 6. Place a know weight on the scale. If possible, use a full scale weight for best results. Adjust the SPAN for 20 ma (2V) for fullscale. Divide: Calibration Weight/Full- Scale Weight = (F)raction of full scale. Multiply: (F) (16 ma) = 1, the current caused by the calibration weight. Add: 1 + 4 ma = Calibration Current, 1c Adjust the SPAN to produce the Calibration Current, 1c, in the output/power loop. Example Calibration Weight = 750 pounds Full Scale Capacity = 1000 pounds Adjust SPAN for: (750/1000) (16 ma) + 4 ma = 1c (0.75) (16 ma) + 4 ma = 1c 12 ma + 4 ma = 1c 16 ma = 1c Step 7. Remove the calibration weight and recheck that the zero reading is still 4 ma (0.4 V). Adjust the FINE control if necessary. 9

Step 8. Step 9. Step 10. Place the calibration weight back on the scale and recheck that the calibration reading is still correct. Adjust the SPAN control if necessary. Repeat steps 7 & 8 until no further adjustment is necessary to keep both measurements within the system tolerances. Calibration is complete. Trouble Shooting Procedures Malfunction: No Output Malfunction: No Change in Input Malfunction: Output Drifts This section is intended to provide assistance in solving minor system problems. Checks to be made: 1. Check voltage at + & - loop connections. You should get a reading of 15 VDC to 50 VDC. 2. Verify load cell connections. 3. Using an Oscilloscope, verify that you have a pulsed 5 VDC between terminals labeled - & + excitation. Checks to be made: 1. Load Cell signal output below original setting. If the signal level returned by the Load Cells is below the previous deadload setting, measure approximately 2.3 ma between the loop + & - terminals. 2. Load Cell signal output above original setting. If the signal level returned by the load cell is above the previous Span setting, measure approximately 23 ma between the loop + & - terminals. Checks to be made: 1. Verify load cell connections. 2. Verify Power Supply output and confirm that it is outputting a constant voltage. 10