Measuring variable-speed motor drive output voltage with a Fluke ScopeMeter 190 Series

Similar documents
Fluke MDA-510 and MDA-550 Motor Drive Analyzer

ScopeMeter Test Tool CSV files available for FlukeView software and Microsoft Excel Application Note

How adjustable speed drives affect power distribution

Making sense of electrical signals

Troubleshooting. process loops. All. Application Note. Loop calibrators. ProcessMeter

Fluke T5 Electrical Testers. Fluke T and T5-600 Voltage, Continuity and Current Testers

Fluke 170 Series True-rms Digital Multimeters

1587/1577 Insulation Multimeters

Fluke 83V and 87V Digital Multimeters

Overall vibration, severity levels and crest factor plus

Clamp Meter ABCs. Application Note. The transformer action

Use of infrared thermography in electronics

5790A Automated AC Measurement Standard

Oscilloscope Calibration Options for Fluke 5500A/5520A Multi-Product Calibrators Extended Specifications

Oscilloscope Calibration Options for 55XX Series Multi-Product Calibrators

Fluke Digital Multimeters Solutions for every need

Electrical Motor Power Measurement & Analysis

5080A Multi-Product Calibrator

Installation Tester and DMM Kits

So advanced, we had to create a new category

CHAPTER IV DESIGN AND ANALYSIS OF VARIOUS PWM TECHNIQUES FOR BUCK BOOST CONVERTER

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Industrial Electronics

Fluke and

Fluke 1587 FC/1577 Insulation Multimeters

Oscilloscopes for field applications

1507/1503. Insulation Testers. Technical Data. Features and benefits:

ECET Industrial Motor Control. Variable Frequency Drives. Electronic Motor Drives

The 7 secrets to better infrared image quality

FAMILIARISATION WITH P.E. COMPONENTS

ELG4139: Power Electronics Systems Objective To Realize and Design Various Power Supplies and Motor Drives!

With any other power quality analyzer you re just wasting energy.

Power Supplies in Accelerators

ELG3336: Power Electronics Systems Objective To Realize and Design Various Power Supplies and Motor Drives!

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

+/- (3 PERCENT +2) AC VOLTAGE, +/- (2 PERCENT +2) DC VOLTAGE, +/- (5 PERCENT +3) RESISTANCE. User Manual, Test Lead Wrap, TP2 Test Probes

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation

Fluke 370 FC Series True-rms Wireless AC/DC Clamp Meters

A New Method for the Calibration of the mv Ranges of an AC Measurement Standard

POWER ELECTRONICS LAB MANUAL

Clamp Meter ABC s APPLICATION NOTE. The transformer action. Choosing your clamp meter

Basic Electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras

225 Lock-in Amplifier

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

Reliable Power Meters Multipoint Power Recorder

An Evaluation of Artifact Calibration in the 5700A Multifunction Calibrator

Fluke 1660 Series Multifunction Installation Testers

Oscilloscope Calibration Options for Fluke 5500A/5520A Multi-Product Calibrators

Fundamentals of AC Power Measurements

Fluke Norma 4000/5000

Measure voltage without test leads. Product Highlights

Electronic Instrumentation & Automation. ET-7th semester. By : Rahul Sharma ET & TC Deptt. RCET, Bhilai

EE POWER ELECTRONICS UNIT IV INVERTERS

Oscilloscopes for field applications

AC VOLTAGE CONTROLLER (RMS VOLTAGE CONTROLLERS)

Complimentary Reference Material

Type of loads Active load torque: - Passive load torque :-

Use of Advanced Unipolar SPWM Technique for Higher Efficiency High Power Applications

UNIVERSITY QUESTIONS. Unit-1 Introduction to Power Electronics

As you can see, by varying the turn-on point, the amount of power getting to the bulb is adjustable, and hence the light output can be controlled.

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

Simple Methods for Detecting Zero Crossing

Insulation resistance testing. A complete solution for every application

Lecture 19 - Single-phase square-wave inverter

Electronics. RC Filter, DC Supply, and 555

Electrical measurements on adjustable speed drives Ten measurements that tell you a lot


Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads

PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY

6. Explain control characteristics of GTO, MCT, SITH with the help of waveforms and circuit diagrams.

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

PV System Components: Inverters and Charge Controllers. EE 495/695 Spring 2011

Electronic Circuits I Laboratory 03 Rectifiers

280 Series Waveform Generators A selection of universal waveform generators offering superior performance and excellent value

1650 Series Multifunction Installation Testers

Variable Frequency AC Source

APPENDIX D DISCUSSION OF ELECTRONIC INSTRUMENTS

1% Switchgear and Substations

Thornwood Drive Operating Manual: Six-SCR General Purpose Gate Firing Board FCOG6100 Revision R

5500A. Multi-Product Calibrator. Extended Specifications 2005

Figure 1 Typical Inverter Block Diagram

PHYS 3152 Methods of Experimental Physics I E2. Diodes and Transistors 1

Fluke 8845A/8846A Digital Multimeters Extended Specifications

GESS Industrial UPS System. Overview

Electricity and Electronics Constructor Kits

Modeling and Analysis of Common-Mode Voltages Generated in Medium Voltage PWM-CSI Drives

RF Generators. Requirements:

The future of installation testing is here. The Fluke 1650 Series Multifunction Testers

Alternating Current Page 1 30

The silicon controlled rectifier (SCR)

Table of Contents...2. About the Tutorial...6. Audience...6. Prerequisites...6. Copyright & Disclaimer EMI INTRODUCTION Voltmeter...

CHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS

An Introduction to Rectifier Circuits

Fluke 1623 and GEO Earth Ground Testers. Technical Data. Stakeless testing

Time Matters How Power Meters Measure Fast Signals

Fluke 712B and 714B Temperature Calibrators

Generator Advanced Concepts

Fluke Norma 4000/5000

5320A. Multifunction Electrical Tester Calibrator. Extended Specifications

Frequently Asked Questions (FAQs) MV1000 Drive

Drives 101 Lesson 5. Power Input Terminology for a VFD

Transcription:

APPLICATION NOTE Measuring variable-speed motor drive output with a Fluke ScopeMeter 190 Series Variable-speed motor drives, also known as frequency inverters, are spreading widely amongst industrial installations. During installation and service, measurements on the output s often give unexpected results. How is this possible, and what can be done to overcome this? Variable-speed motor drives Traditional electrical machinery connected directly to a single or three-phase power system have only a very limited range of speed control, if any at all. An external gearbox provides a solution but is bulky, noisy, expensive and subject to wear. The availability of new semi- conductor devices handling high s and large currents has opened the door for the design of so-called variable-speed motor drives or frequency inverters. These devices offer broad flexibility in speed control and match this to low electrical losses and a constant torque that can be independent of the actual rotational speed of the machine. As a result, the use of variable-speed motor drives is spreading widely amongst industrial installations where they offer many advantages including: The elimination of wear, because asynchronous machines are used, Effective control, and High energy efficiency. During installation and service, however, measurements on unexpected results. Here we explain how this is possible and what can be done to over- come it using Fluke 190 Series ScopeMeter Test Tools.

Generating variable-frequency output Several methods are available for generating the variable frequency output. The first designs were known as self-controlled or machine-synchronized thyristor power converters. These are still found today in high-power frequency inverters but for lower power applications better alternatives have become available. Thyristors (Silicon Controlled Rectifiers or SCRs) can be turned off only at zero crossing of the mains current, which is why the output of these converters isn t a continuous sine wave but always shows discontinuities (for instance as seen in figure 1). without filtering Figure 1: of SCR-based power converter. The unfiltered output clearly shows discontinuities. Here, changing the phase angle of the discontinuity effectively controls the output power, which can be used to change the machine speed while reducing mechanical power available. Unfortunately, these converters don t allow for random modulation of the output waveform; attempts to resolve this using extra circuitry have proven to be expensive yet have met with only limited success. Once so-called gate-controlled turn-off power semiconductors became available, a totally different approach to variable-speed motor control became possible. Such semiconductors can be turned off as well as on, which makes them suitable for chopping in a DC system. Figure 2 gives the basic structure of such drives. R S T Mains input Input rectifier + - DC buffer DC bus 1a 2a 3a Control unit 1b 2b 3b Pulsewidth modulator/chopper Figure 2: Basic structure of a variable-speed motor drive. 1a 1b 2a 2b 3a 3b M Inverter output The single- or three-phase mains input is connected to a series of rectifiers that feed an internal DC bus. Here the DC is buffered in a large- value storage capacitor, charged to a Ub: Ub = 2*U mains 1.41*U mains The DC is then applied to a series of double-sided switches that alternately connect each of the three machine connections to either the positive or the negative bus line. Furthermore, each branch of switches can be in the inactive (i.e. non-conductive) mode, effectively floating the machine connection to which it is connected. The switches are all controlled by a central Control Unit that generates the driving pulses to activate each of the 6 switches at the proper instant. The switching speed can be varied and this determines the output frequency. The order in which the three outputs are driven determines the rotational direction of the machine. The control unit is set up such that the output frequency can be varied over a broad range. And because the machine s rotational speed depends directly on the frequency of the supply, the speed of the machine can effectively be controlled. 2 Fluke Corporation Measuring variable-speed motor drive output with a Fluke ScopeMeter 190 Series

Figure 3 gives the resulting output s for each of the output lines. On each of the machine connections we see a positive impulse, a period where the connection is left unpowered, then a negative impulse, followed by yet another period where no driving is applied. In this simple case, the open output of each of the outputs is either +1/2 Ub or zero (floating), or 1/2 Ub, where Ub is the bus. Note that because all three outputs are connected the same way, the mean value for each of the output lines is at half the DC bus. If we applied the above waveform to a low-pass filter, the output would resemble a sine wave with the same fundamental frequency as the square wave which is dictated by the control circuitry (see figure 4). However, low-pass filters that can handle the energy levels encountered in motor drives would be bulky and expensive, so alternatives for these have been developed. Alternative to low-pass filtering The alternative to low-pass filters has come from another improvement in power electronics. In real systems, the positive and negative pulses are generally not created by generating a single pulse of the desired polarity. Instead all pulses are generated by repeatedly switching on and off the same solid-state switch at a much higher pulse rate using a varying on-off duty cycle (see figure 5). 1a on 3b on 2a on 1b on 3a on 2b on 0 60 120 180 240 300 360 60 degrees Figure 3: for each of the individual output lines. a on b on 0 60 120 180 240 300 360 60 degrees Figure 4: directly and through a low-pass filter. 1 2 3 after lowpass filtering The trick now is that the duty cycle is varied such that the cur- rent (but not the ) through the machine winding has a sine waveform. In effect, the induction of the machine windings then functions as the low-pass filter in which a current with a sine waveform flows as the result of a pulse-width modulated. In figure 5, the upper curve gives the output for one output line only in which the effect of duty-cycle variation is clearly seen; the lower curve gives the effective output per internal clock cycle T on a relative scale. T T T I/T = fixed internal frequency +1/2 U b -1/2 U b One cycle of output Figure 5: s for pulse-width-modulated motor drive (simplified). 3 Fluke Corporation Measuring variable-speed motor drive output with a Fluke ScopeMeter 190 Series

This indicates that the effective output has a sine waveform. However, the real output of the motor drive resembles much more closely the upper curve! In contrast to the SCR circuits mentioned earlier, the drive circuitry can now be used in switched mode all the time, and therefore energy losses in the semiconductor switches are minimal, giving high energy efficiency and low heat generation in the drive module. Voltage measurements Although the improvements in efficiency and the freedom in speed control with these motor drives are evident, there is a complication for the engineer responsible for installing or carrying out service work on these motor drives. The output of the motor drive is generated with the aim of producing a current with a sine waveform through an inductive load, but the applied has a completely different waveform. Measuring the output directly may therefore give unexpected results because, unlike the electrical machinery, the voltmeter will respond to the unfiltered output. This is due to the waveform as well as to the design characteristics of digital multimeters. These are generally designed to measure the amplitude of a sine wave at mains frequency, i.e. 50 or 60 Hz. In contrast, the output of the variable-speed drive is a square wave of high frequency, and its duty cycle changes continuously. On the other hand, the peak amplitude of the square wave is fixed. Finally there are two polarities to deal with. Most multimeters are designed to respond to the peak-, peak-peak- or mean applied, and these multimeters are then calibrated to read the effective amplitude of the sine wave. What s more, when used for AC- measurements, most multimeters have a double-phase rectifier at the input to ensure that s of either polarity contribute equally to the reading. If we look at the output as shown in figure 5, the average per cycle T (after rectification) is directly proportional to the duty cycle of the waveform and to the DC-bus, and is therefore constantly changing because the duty cycle is varied. Within a half-cycle of the resulting current, the mean will then be: U mean = d * U peak = d * ( 1/2 Ub ) where: d = duty cycle, which changes from 0 to 100 % and back. The result is a meter reading in volts that may deviate significantly from the value expected on the machine terminals (as seen, for example, on a display incorporated in the motor drive itself that reads the effective output calculated by the internal control electronics). As an illustration of the above, we ve tested a number of multimeters of different make and model, all under exactly the same conditions, using the same motor drive with the same settings. The measured results, given in table 1, range from 143 V up to 1000 V! Digital multimeter model 1 1001 V Reading (Vac) 2 154.2 V 3 157.6 V 4 170.1 V 5 187.1 V 6 193.6 V 7 204.3 V 8 215.3 V 9 237.93 V 10 254 V Fluke 41B Fluke 43B Fluke 190 Series 143V 143.3 V 144 V Table 1: AC- reading using various digital multimeters 4 Fluke Corporation Measuring variable-speed motor drive output with a Fluke ScopeMeter 190 Series

Making the right measurements The proper way to calculate the output for this particular situation is by taking into account the particular application of the motor drive. The drive power for electrical machinery is derived from the current through the machine windings, whereas the applied is basically needed only to make that current flow. Variable-speed motor drives make use of this fact by applying a high-frequency, non-continuous that results in a current with a sine waveform through the machine windings with a frequency governed by the control unit and the polarity of the switched. So if we want to know the effective output of the motor drive, we should take into account only the fundamental frequency component of the applied. This can be obtained by taking a large number of samples of the applied and building a detailed image of the waveform within the digital memory of the instrument, from which the amplitude of the fundamental frequency component can be calculated and displayed. This is exactly what is done in the last three test-instruments listed in table 1. This includes the Fluke 190B and 190C Series ScopeMeter Test Tools where all incoming s are digitized at a high sample rate and a digital image of the waveform is stored in memory for further analysis. The 190 Series ScopeMeter Test Tools are equipped with a dedicated measurement function labelled Vpwm-measurement targeting these applications. With this function, the 190 Series can analyze the digitized signal and calculate the fundamental frequency. This will have the same wave- form as the motor drive s output current. From this waveform, the effective value is then calculated and displayed as the Vpwm-reading. See the screen copy in figure 6, where both the peak-to-peak amplitude and the effective output of a motor drive are given in small boxes at the top of the screen. The effective output frequency of the displayed wave- form can easily be determined here: a single cycle takes approximately 6.3 divisions, the timebase setting is 5 ms, so a single cycle takes approximately 31.5 ms. The output frequency is then 1/31.5 ms = 32 Hz. Alternatively, the cursors may be used to mark a cycle of this output waveform. Conclusion Figure 6: Motor drive output measured using the Fluke 199C. Variable speed motor drives bring a lot of advantages to the machine builder and user. For the service engineer and the installer of the machine drives, a complication is in measuring the output s of the drives. Only test equipment that is specifically prepared for testing these output s will give reliable readings, in line with the (calculated) reading on the motor drive itself. The Fluke 190 Series ScopeMeter is particularly well suited for use during installation and service on these variable speed motor drives, and is equipped with all test functions you may need. Fluke. Keeping your world up and running. Fluke Corporation PO Box 9090, Everett, WA 98206 U.S.A. Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands Modification of this document is not permitted without written permission from Fluke Corporation. For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com 2005, 2016 Fluke Corporation. Specifications subject to change without notice. 9/2016 2543358b-en 5 Fluke Corporation Measuring variable-speed motor drive output with a Fluke ScopeMeter 190 Series