Grounding Recommendations for On Site Power Systems

Similar documents
Upgrading Your Electrical Distribution System To Resistance Grounding

Grounding for Power Quality

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

This document covers common questions concerning the design of an effectively grounded system.

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

ECE 528 Understanding Power Quality

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

EPG. by Chris C. Kleronomos

American Electrical Institute

CONTINUING EDUC ATION

Article 250 Grounding & Bonding

Wiring of the Main Distribution Panelboard

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Grounding Complications

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Grounding and Bonding

Webinar: An Effective Arc Flash Safety Program

Industrial and Commercial Power Systems Topic 7 EARTHING

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Wisconsin Contractors Institute Continuing Education

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Grounding and Bonding of Service Equipment

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

ET 40 - Electrician Theory Examination Marking Schedule

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

high RESISTANCE GROUNDING SYSTEM the power to protect SLEUTH Instruction Manual C-408EM

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

TECHNICAL INFORMATION

Ground Fault Location. Turbo Sleuth. Instruction Manual

Electrical Wiring: Commercial, Seventh Canadian Edition

Utility Interconnection and System Protection

Alternator winding pitch and power system design

Industrial Electrician Level 3

Summary of the Impacts of Grounding on System Protection

Effective System Grounding

2 Grounding of power supply system neutral

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

TN, TT & IT Earthing Arrangements

Paralleling Dissimilar Generators: Part 2 Compatible Alternators

System Protection and Control Subcommittee

NEC 2014 Code Changes

POWER SERVICE DETAILS

Our Brands. Where we are?

Three Phase Transformers

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings

Tower Grounding Training For Telecommunications Networks

Installation Manual DOC R1 Date: 05/27/99. Plug-in Meter Installation Manual

Continued from Part 1 Rules 1 25.

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Ground Fault Protection

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

ET 51 - Electrician Theory Examination Marking Schedule

Education & Training

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

Electrical Arc Hazards

Module Title: Electrical Installation II Laboratory Sheet:

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

How to maximize reliability using an alternative distribution system for critical loads

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR

Grounding System Theory and Practice

Ground Fault Protection

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

SINGLE-PHASE VSV SWITCH

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Los A LA-UR Los Alamos National Laboratory Los Alamos, New Mexico 87545

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

MV network design & devices selection EXERCISE BOOK

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013

Transformer Protection Principles

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Microprocessor Control Board Set Up Procedures (OR PLC)

Generator Protection GENERATOR CONTROL AND PROTECTION

Designing For a Critical Load using a Spot Network

COURSE PLANNER. Subject: TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS ( ) B.E. Fourth Year (8 th Sem) Branch Electrical Engineering

Article 225: Outside Branch Circuits And Feeders

ARC FLASH HAZARD ANALYSIS AND MITIGATION

IRRIGATION 810-3R RECEIVER GUIDE

Grounding and Lightning arrestors

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Transcription:

Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved

Course Objectives Participants will be able to: Explain grounding best practices and code requirements for system and equipment grounding methods. Define requirements for proper ground fault sensing to help design and install ground fault systems that work correctly. Define when a 3 pole vs 4 pole transfer switch should be used so that neutral and ground current loops are eliminated and ground fault detection systems work correctly. Identify key factors of paralleled systems that need to be considered so that ground fault detection systems will work properly.

Equipment Grounding vs System Grounding Equipment grounding Establish (connect) a conductive path between normally non-current carrying metal parts of equipment AND between these parts and the grounding electrode System grounding Deliberate connection between a circuit conductor of a power source and ground (earth) Both are part of the path for ground fault current to return to the source Metal Enclosures Neutral System Ground Equipment Ground Grounding Electrode

Equipment Grounding ATS Generator Set Equipment Grounding Conductor (EGC) Connects normally non current-carrying metal parts of equipment together and to the System grounded conductor (neutral) or Grounding electrode conductor (GEC) Provides path for ground fault current EGC Neutral Grounding electrode: a conducting object through which a direct connection to earth is established such as building steel or a ground rod GEC Grounding Electrode

Why Ground Equipment? Safety Minimizes hazards of touching live equipment Minimizes voltages on equipment during fault conditions Provide a path for fault current to return to the source Earth is not an acceptable path for fault current to return to the source

Impediments to Effective Equipment Grounding Painted surfaces Use ground braid or cable across anti-vibration mounts or painted metal surfaces Corroded or damaged ground connections, wires or cables Loose ground connections Missing star type washers

B System Grounding IEEE Std 142-2007 (Green Book) System grounding is the intentional connection to ground of a phase or neutral conductor for the purpose of: a) Controlling the voltage with respect to earth or ground within predictable limits and b) Providing for a flow of current that will allow detection of an unwanted connection between system conductors and ground the control of voltage to ground limits the voltage stress on the insulation of conductors the control of voltage also allows reduction of shock hazards C N A V A-G = 277 V V B-G = 277 V V C-G = 277 V V N-G = 0 V G C N A B Full Ground Fault on Phase B V A-G = 480 V V B-G = 0 V V C-G = 480 V V N-G = 277 V

Solidly Grounded System Most common grounding method for low voltage generator sets Enables ground fault detection and thus activation of ground fault protection equipment High level of ground fault current Limits excess voltage on ungrounded phases during ground fault

Resistance Grounded System Commonly used with medium voltage generator sets Limits ground fault current level Two types of resistance grounded system: Low Resistance Grounding Fault current usually limited to 300-500 amps Easily detectable with conventional CT s Sufficient to trip circuit breakers High Resistance Grounding Fault current usually limited to 5-10 amps Maintain continuity of power during a fault allowing controlled shutdown Z

Establishing a Neutral on an Ungrounded System M M Z Z Zigzag or wye-delta transformers may be used to obtain a neutral for ungrounded systems Either solidly grounded or resistance grounded High impedance to balanced normal phase currents Low impedance to zero sequence (fault) currents

Separately Derived Systems NEC Definition - A premises wiring system whose power is derived from a source of electric energy or equipment other than a service. Such systems have no direct electrical connection including a solidly connected grounded circuit conductor, to supply conductors originating in another system. Ground NEC Section 250.30(A)(1) requires separately derived systems to have a system bonding jumper connected between the generator frame and the grounded circuit conductor (neutral) Neutral Bonding Jumper

Separately Derived System Service Entrance 4P ATS Generator Set EGC GEC To Loads (3-phase/4W with GND) GEC No direct electrical connection between sources 3 Phase, 4 Wire System 4 Pole Transfer Switch Generator neutral is solidly grounded and bonded

Non-Separately Derived System Service Entrance 3P ATS Generator Set Common neutral for entire system 3-phase, 4 wire system 3 Pole Transfer Switch Neutral is not grounded at the generator To Loads (3-phase/4W with GND)

Ground Fault Protection and Indication NEC 230.95 (CEC 14-102) requires Ground Fault Protection (GFP) at the service disconnect (utility breaker) for systems with: Solidly grounded wye More than 150 volts to ground (277/480 or 347/600VAC) Over current device rating of 1000A or More (CEC 120/208VAC & 2000A) Ground Fault Indication (GFI), not protection, is required at the emergency source (NEC 700.6 (D))

How Do We Sense Ground Fault? GFR GFR GFR L1 L2 L3 L1 N L2 L3 L1 N L2 L3 N Residual Most common method for breakers CTs on each phase and neutral Vector sum of current through all CT s must be 0 (< threshold) Zero sequence Single CT around all three phases and neutral Same concept as residual method Source ground return Single CT in the neutral to ground bond Method used by our genset control GFR: Ground Fault Relay

Ground Fault Sensing in LV Emergency Standby Systems Most common method is to use GFP in breaker at the service disconnect Two rules for proper GF sensing: Rule #1: There must be only one neutral/ground connection on any neutral bus at one time Rule #2: Ground fault sensors must be downstream from the bonding connection These two rules drive the requirement that 4 pole transfer switches must be used when ground fault sensing is required or may be required in the future. IEEE Std 446-1995 (Orange Book) 7.9.1 for most emergency and standby power systems with ground-fault systems, switching of the grounded circuit conductor by the transfer switch is the recommended practice.

Sensing a Ground Fault Service Entrance ATS Generator Set To Loads (3-phase/4W with GND)

Two Bonding Jumpers Service Entrance ATS Generator Set To Loads (3-phase/4W with GND) Parallel path for ground fault current on the neutral GFP does not sense all fault current Solution: remove the bond on the generator set

Single Bonding Jumper ATS Generator Set To Loads (3-phase/4W with GND) Removing the generator set neutral bond solves the problem in the previous slide There is only one path for earth fault current to return to the source

3-Pole ATS Connected to Emergency Side Service Entrance ATS Generator Set To Loads (3-phase/4W with GND) Ground fault returns on neutral Possible nuisance trip during exercise Solution: ground the neutral on the source side of sensor

Function of 4-Pole Transfer Switches Service Entrance ATS Generator Set Fourth pole opens the path on neutral Allows accurate GFP sensing on both sides The neutral is grounded in only one place at a time Ground fault sensor is downstream of the bonding connection

Grounding Case Study Nine containerized generator sets on metal platform Containers bonded to platform Platform connected to underground ground ring Each generator is grounded through an NGR located inside the container

Grounding Case Study Should the NGR be bonded to the platform? (Yes/No) Gen 1 Platform is the fault current return path Gen 9 Load Bank Z Z Metal Platform Underground Ground Ring

Grounding Case Study Gen 1 Gen 9 Load Bank Z Z Metal Platform Underground Ground Ring Ground ring is the fault current return path

Grounding Case Study System ground consists of neutral conductors, NGRs and ground ring System ground is intended to carry current don t rely on metal structures Equipment ground consists of containers, platform, cabinets, etc. and ground ring Ground ring is common to both equipment and system ground Establish a low impedance path for fault current to return to the source Path should be through ground ring, not across platform, cabinet, railing Minimize touch potential

Grounding of Paralleled Generator Sets G1 G2 G1 G2 Z Z GFR GFR GFR 4 wire systems typically have a single ground in the switchgear Generators in 3 wire systems are typically separately grounded Medium or high voltage generators are often resistance grounded

Ground Fault Sensing with Paralleled Systems Utility G1 G2 G3 :Y 4-Pole Breaker Neutral To Loads (3-phase/4W)

Recommendations All equipment that can be energized must be grounded Ground fault current must have a defined path to return to the sources Remember the two big rules for ground fault sensing in emergency standby systems: There can be only one neutral-to-ground bond in the system The sensor for the ground-fault signal devices shall be located downstream of the neutral bonding point Specify 4-Pole ATS if: GFP on Normal/GF indication on emergency is required Any 3-phase 4-wire with line-to-ground voltage above150v when future expansion to the facility is expected Paralleled sources may require complex ground fault schemes Modified Differential GFP can differentiate between fault current and normal neutral current in systems with multiple sources and grounds Multiple grounds, 4 wire solid neutral systems and utility paralleling applications may require MDGFP

Thank You! Please share your feedback by completing the Power Seminar evaluation form. 2017 Cummins All Rights Reserved