ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

Similar documents
Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

A NOVEL METHOD FOR ENERGIZING TRANSFORMERS FOR REDUCING INRUSH CURRENTS

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

MATHEMATICAL MODELING OF POWER TRANSFORMERS

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

ANEW, simple and low cost scheme to reduce transformer

Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator

Autotransformer Inadvertent Energization Through Circuit Breakers Gradient Capacitors

A Study on Ferroresonance Mitigation Techniques for Power Transformer

FERRORESONANCE SIMULATION STUDIES USING EMTP

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Discrimination between Inrush and Fault Current in Power Transformer by using Fuzzy Logic

Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm

2. Current interruption transients

Ferroresonance Experience in UK: Simulations and Measurements

Transformer Inrush and Voltage Sag P28 Studies. August 2017

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Chapter 33. Alternating Current Circuits

Tab 2 Voltage Stresses Switching Transients

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Dynamic Phasors for Small Signal Stability Analysis

Demagnetization of Power Transformers Following a DC Resistance Testing

Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Spring 2000 EE361: MIDTERM EXAM 1

TRANSFORMER CONTROL (AC-56a)

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Transient Performance for a Series- Compensation in a High Voltage Transmission System

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

TECHNICAL BULLETIN 004a Ferroresonance

ESTIMATION OF RESIDUAL FLUX FOR THE CONTROLLED SWITCHING OF TRANSFORMER

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Abstract- At the time of transformer energization, a high current will be drawn by the transformer. The mentioned current

Simultaneous AC-DC Transmission Scheme Under Unbalanced Load Condition

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

Pre-insertion Resistor of Switching Shunt Capacitor Banks

Identification of network models parameters for simulating transients

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

Parameter Study of Ferro-Resonance with Harmonic Balance Method

The power transformer

Innovative Science and Technology Publications

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

In power system, transients have bad impact on its

Conventional Paper-II-2011 Part-1A

EXPERIMENT 4: RC, RL and RD CIRCUITs

Power Quality Improvement in Distribution System Using D-STATCOM

Properties of Inductor and Applications

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

II. DIFFERENTIAL PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION

DC current interruption tests with HV mechanical DC circuit breaker

Solving Customer Power Quality Problems Due to Voltage Magnification

CH 1. Large coil. Small coil. red. Function generator GND CH 2. black GND

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

RC circuit. Recall the series RC circuit.

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

CAPACITORS are commonly found in distribution

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

Modeling and electromagnetic transients study of two 1800MVA phase shifting transformers in the Italian transmission network

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Alternating current circuits- Series RLC circuits

Chapter 31 Alternating Current

Chapter 2-1 Transformers

Exercise 9: inductor-resistor-capacitor (LRC) circuits

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Long lasting transients in power filter circuits

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

AC Circuits INTRODUCTION DISCUSSION OF PRINCIPLES. Resistance in an AC Circuit

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

SINGLE-STAGE HIGH-POWER-FACTOR SELF-OSCILLATING ELECTRONIC BALLAST FOR FLUORESCENT LAMPS WITH SOFT START

Development and performance analysis of a saturated core high temperature superconducting fault current limiter

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

Power Quality enhancement of a distribution line with DSTATCOM

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

EXPERIMENT 4: RC, RL and RD CIRCUITs

Transformer Protection

Analysis of Modern Digital Differential Protection for Power Transformer

POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM

Transcription:

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir 1 Tabriz University, Faculty of Engineering, Department of Electrical & Computer Engineering, Tabriz, Iran 2 Azarbyjan Regional Electric Power Company Keywords: Inrush Current, Transformer, Analytical, Switching Time, EMTP, ATP ABSTRACT This paper presents some techniques for reduction of transformer inrush current. The equation of inrush current is obtained and then by using these methods, transformer inrush current is reduced, then after comparing the result of each method, the best choice is determined. Results which have been obtained from EMTP simulation confirm these subjects. I. INTRODUCTION Energization of unloaded transformers results magnetizing inrush current (IC) with high amplitude. These currents have many unfavorable effects, including operation failure of transformer differential protection, deterioration of the insulation and mechanical support structure of windings and reduced power quality of the system [1]. Without controlled switching the energization may occur at any time on the voltage wave producing high IC peak, when the transformer core is driven into saturation. Power transformers, as one of the vital components of electric power systems, require the protective relays with very high dependability, security, and speed of operation. But the magnetizing IC, which is often generated when the transformer is energized, can cause the false tripping of the differential relay therefore reduction of IC is necessary [2]. Some methods have been to reduce IC. Pre-insertion of series resistors and synchronous closing of circuit breakers are examples of the available mitigation techniques [3]. A neutral resistor based scheme for mitigating inrush currents was proposed in some papers [4-5]. II.TRANSFORMER MODEL In this section, we describe transformer original model and equation for calculate maximal of IC. The transformer behavior during first phase energization can be modeled through the simplified equivalent electric circuit shown figure 1. Figure 1. Transformer single phase model As shown in figure 1, r p and L p present primary resistance and leakage reactance. L m represents the nonlinear inductance of the iron core as function of the magnetizing current. Secondary side resistance r sp and leakage reactance L sp as referred to primary side are also shown. v p and v s represent the primary and secondary phase to ground terminal voltage respectively. From the figure 1: v p =v m sin(ωt+ө )=i φ r p +N 1 dφ L /dt (1) Where θ is the phase of primary voltage at t =, i φ is magnetize current, φ L is core flux and N 1 is number of turn in primary side. Therefore we have: v m =sin(ωt+ө )=(N 1 φ L.r p /L 1 )+N 1 φ L /dt (2) where L1 is primary inductance. After solve Eqn.2 for φ L : r p t L1 ( cos ) e cos( t ) φ = φ θ ± φ φ ω + θ (3) t m r m where φ m is the max of φ L and φ r is residual flux. At θ =π/2 in Eqn. 3 we have: r p t L1 φ =± φ e + φ sin ωt (4) t r m

In this case transient flux exists with φ r magnitude and time constant equal τ=l 1 /r p, the max of magnetizing current obtain as below: i φ m 2φm + φr 2.22Ai = (5) µ A t A. EFFECT OF CLEARING RESIDUAL FLUX If transformer is energized without any methods for reduction IC in circuit which shown in figure 2 then IC will be as follow which shown in figure 3. Where A i is area of core, A t is the area of the core with winding and µ is air permeability. The primary transient current obtains from below when transformer is connected to load. r p p 1 t t L l 1 sp i1 ( t) = iφ e + I e (6) 2 r Where I is the nominal current. Since lsp<l 1, then transient current produced with load current is damped very fast, in this case IR is equal 4-6 pu. From the equation we see that the magnitude of the magnetizing IC is in the range of the short circuit current and may by occurs serve dynamical stress in the transformer windings [6]. The IC amplitude usually does not exceed the fault current withstand capability of the transformer, however the duration of these stresses are significantly longer than occurrence is more frequent than of the short circuit which is cleared by the relay protection within some tens of ms. The amplitude of the magnetizing current depends mainly on two factors: the residual flux in the magnetic core and the transient flux produced by the integral of the sinusoidal supply voltage. When energizing a transformer at zero crossing of the sinusoidal voltage the prospective magnetizing current and the flux have their maximal values, and delay by 9 electrical degrees. Transient flux starts from the residual flux and reaches its highest amplitude a half period later. At that point the flux saturates the core and a high amplitude IC current appears because the inductance of the magnetic core is very small in that region. In follow describe some methods to reduction IC. III.METHODS OF REDUCTION OF IC For analyze transformer inrush current suppose circuit shown in figure 2. Figure 3. Inrush current without any control According to the above described in part II, the magnitude of residual flux in the transformer is the main parameters to change magnitude of inrush current, when circuit breakers are opened transformer is insolated from network, residual flux remains in transformer and when transformer is energized IC will be increased. For clear this effect, capacitor are inserted in primary side of transformer, which reduce residual flux then IC are obtain in this case are shown in figure 4. Figure 4. Inrush current with clearing residual flux From the above figure, we can see that the IC is reduced. Figure 2. ATPDraw circuit for network B.EFFECT OF PRE-INSERTION RESISTOR In order to reduce IC, in circuit that shown in figure 2 at first C 3 is closed, which series with resistor, after 1 ms the main switch (C 1 ) is closed and bypassed other switch and resistor. In this case IC is shown in figure 5.

From this, can see that the IC is effectively reduced, there for one of good methods to reduce inrush current is pre-insertion resistor. In this circuit auxiliary load is energized therefore, at first transformer inrush current is reduced. 12 8 4-4 -8-12..2.4.6.8 1. (file trans3.pl4; x-var t) c:x1a-x11a c:x1b-x11b c:x1c-x11c Figure 5. Inrush current with pre-insertion resistor C.EFFECT PER-INSERTION RESISTOR & CLEARING RESIDUAL FLUX In previous parts see that pre-insertion resistor and clearing residual flux are effective in reduction IC, there for in this part both method together used. The results from this simulation are shown in figure 6. 1 Figure 7. ATPDraw circuit for network with auxiliary load When this load are disconnected another again inrush current are exist, which results of simulation are shown in figure 8. 12 9 6 3 62-3 24-14 -52-9..2.4.6.8 1. (file trans3.pl4; x-var t) c:x1a-x11a c:x1b-x11b c:x1c-x11c Figure 6. Inrush current with clearing residual flux & pre-insertion resistor From figure 6, can see that apply both methods insertion pre-resistor and capacitor for clearing residual flux more effectively reduce IC. D. EFFECT ENERGIZING OTHER LOADS One of the methods that can reduce IC is energization another load simultaneous with transformer. For this goal, proposed another circuit which is shown in figure 7. -6..3.6.9 1.2 1.5 (file trans4.pl4; x-var t) c:x1a-x11a c:x1b-x11b c:x1c-x11c Figure 8. Inrush current when auxiliary load is used E.EFFECT ENERGIZATION AUXILIARY LOAD & CLEARING RESIDUAL FLUX In order to find best method to reduce the IC, in this part both methods energization auxiliary load and clearing residual flux are used, which results simulation are shown in figure 9. 8 5 2-1 -4-7..3.6.9 1.2 1.5 (file trans4.pl4; t) c:x1a-x11a c:x1b-x11b c:x1c-x11c x-var Figure 9. Transformer inrush current, when auxiliary load and clearing residual flux are used

From figure 9 can see that combination these two methods cause more reduction of IC. F.EFFECT OF ENERGIZATION AUXILIARLY LOAD & CLEARING RESIDUAL FLUX& INSERTION PRE-RESISTOR At following we use each three methods together to reduce IC. Results of this simulation are shown in figure 1. 7 From above can see that IC is eliminated. Therefore with combination this methods, we can find best case to reduce IC with lower cost. H.ASYNCHRONOUS SWITCHING In this part we use asynchronous method switching for switch C 1 without C 3 in circuit which is shown in figure 2. Best time of switching for C 1 is shown in table2, which at these moments supply voltage in each phase is maximum therefore residual flux is suitable. 44 18-8 Table 2. Best time of switching for C 1 Phase A B C Time of closing.8 sec.86 sec.83 sec Using switching time table 2, inrush current is shown in figure 12. -34-6..3.6.9 1.2 1.5 (file trans4.pl4; x-var t) c:x1a-x11a c:x1b-x11b c:x1c-x11c Figure 1. Inrush current, with each three methods From the above figure, we can see that use these three method with together cause more reduce IC, but IC is great still therefore must be find solve to reduce more IC. G. BEST TIME OF SWITCHING In this part try to find best time of closing and opening the switches and this schedule is used in manner F. Best time of opening and closing are shown in table 1. Table1. Best time of switching Switch TIME OF CLOSE TIME OF OPEN C1.775 sec - C2.7 sec.52 sec C3.71 sec.15 sec Figure 12. Transformer current when switching is asynchronous Therefore with use asynchronous switching only, inrush current is eliminated. In following no load transformer IC is shown in figure 13, when transformer is energized without any control method. For comparison, when asynchronous switching method is used, the IC is shown in figure 14. Therefore IC is very small by using asynchronous method. With use above switching time in manner part F, inrush current will be reduced, results from simulation are shown in figure 11. 12 8 Inrush Current (A) 3 4 2 1-4 -1-8 -2-3..3.6.9 1.2 1.5 (file trans4.pl4; x-var t) c:x1a-x11a c:x1b-x11b c:x1c-x11c Figure 11. Inrush current when both, method is used in F part and best time of switching is used -12..5 1. 1.5 2. 2.5 3. (file Noname.pl4; x-var t) c:x5a-x6a c:x5b-x6b c:x5c-x6c Figure 13. No load transformer IC without any control method

4 3 2 1-1 -2 Inrush Current (A ) -3..5 1. 1.5 2. 2.5 3. (file Nonam e.pl4; x-var t) c:x5a-x6a c:x5b-x6b c:x5c-x6c figure 14. No load transformer IC with asynchronous method IV. CONCLUSION The residual flux plays a significant role in the development of the magnetizing inrush current; it is observed that residual flux can be reduced by putting phase-to-ground capacitor at transformer terminals. It is also observed that pre-insertion resistor can reduce inrush current and the combination of all methods gives best results. Finally saw asynchronous switching can eliminate inrush current but the method is expensive because all circuit breakers must be exchanged. Numerical comparison results are shown in table 3. In table 3 it can be seen that the method G is the best because IC is almost eliminated. But in this situation trade off between cost of circuit breaker and cost of resistor and IC value is necessary. If loss of preinsertion resistor and resonance invention probability has in mind, then asynchronous method is the best method. APPENDIX Transformer information: F=5 Hz, S=5 MVA, V h =132 kv, V l =11 kv, I base =23 A Table 3. Comparison results of methods Method Positive max Negative min current (pu) current (pu) Normal 5.96-5.24 A. With pre-resistor 5.5-4.91 B. With capacitor 4.95-4.2 C. Capacitor& preresistor 4.19-3.82 D. Auxiliary load 4.78-2.39 E. Auxiliary load & capacitor 3.2-2.72 F. Auxiliary load & capacitor & preresistor 2.89-2.48 G. Best time of switching 1.8-1.1 H. Asynchronous 1-1 REFERENCES 1. L.Prikler, G.Banfai, G.Ban and P.Becker, Reducing the Magnetizing Inrush current by means of Controlled Energization and de-energization of Large Power Transformer, International Conference on Power System Transients, IPST 23. 2. G. Baoming, A. T. Almeida, Z. Qionglin and W. Xiangheng, An Equivalent Instantaneous Inductance-Based Technique for Discrimination Between Inrush Current and Internal Faults in Power Transformers, IEEE Trans. on Power Delivery, Vol. 2, No. 4, October 25. 3. Cigre working group A3.7,Controlled switching of HVDC circuit breakers; Benefits and economic aspects, Cigre, Paris, 24. 4. Y. Cui, S.G. Abdulsalam, S. Chen, and W. Xu, A Sequential Phase Energization Method for transformer inrush current reduction, Part I: Simulation and Experimental Results, IEEE Trans. on Power Delivery, Vol. 2, pp. 943-949, April 25. 5. W. Xu, S.G. Abdulsalam, S.Chen, and X. Liu, A Sequential Phase Energization Method for transformer inrush current reduction, Part II: Theoretical Analysis and Design Guide, IEEE Trans. on Power Delivery, Vol. 2, pp. 95-957, April 25. 6. M. Steurer, K. Frohlich, The impact of inrush currents on the mechanical stress of high voltage power transformer coils, IEEE PWRD, Vol. 17, No. 1, pp. 155-16, Jan. 22.