The Causes and Impact of EMI in Power Systems; Part 1. Chris Swartz

Similar documents
Understanding and Optimizing Electromagnetic Compatibility in Switchmode Power Supplies

QPI-AN1 GENERAL APPLICATION NOTE QPI FAMILY BUS SUPPLY QPI CONVERTER

Electromagnetic Compatibility

ROD ANTENNA TESTING Complete article download from: EMI TESTING. Basic RE102 test (2-30 MHz)

CHAPTER 2 EQUIVALENT CIRCUIT MODELING OF CONDUCTED EMI BASED ON NOISE SOURCES AND IMPEDANCES

Differential-Mode Emissions

Practical Design Considerations For The Reduction Of Conducted EMI; Part 2. Chris Swartz

CS101. Conducted Susceptibility CS101. CS101 Maximum Current. CS101 Limits. Basis For CS101 Limits. Comparison To MIL-STD Vdc or Less

CHAPTER 4 MEASUREMENT OF NOISE SOURCE IMPEDANCE

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS

Filter Considerations for the IBC

Test and Measurement for EMC

Trees, vegetation, buildings etc.

Understanding, measuring, and reducing output noise in DC/DC switching regulators

Application Note AN- 1094

INTRODUCTION TO CONDUCTED EMISSION

Specification for Conducted Emission Test

Controlling Input Ripple and Noise in Buck Converters

LISN UP Application Note

7. EMV Fachtagung. EMV-gerechtes Filterdesign. 23. April 2009, TU-Graz. Dr. Gunter Winkler (TU Graz) Dr. Bernd Deutschmann (Infineon Technologies AG)

Conducted emission pre compliance measurements

Conducted EMI Simulation of Switched Mode Power Supply

Power Electronics Technology

Minimizing Input Filter Requirements In Military Power Supply Designs

Model 3725/2M. Line Impedance Stabilization Network (LISN) User Manual

Reducing EMI in buck converters

High Performance ZVS Buck Regulator Removes Barriers To Increased Power Throughput In Wide Input Range Point-Of-Load Applications

ELECTRICAL FILTERS. (Command Control Communications Computer & Intelligence) E 3 LINE FILTERS EMI LEMP NEMP HEMP TEMPEST

V1.3. TBLC08 50mH AC-LISN TBLC08

OVP 2:1. Wide Range. Protection

2620 Modular Measurement and Control System

Conducted emission pre compliance measurements

Chambers Accessories Equipment 1 Equipment 2 Amplifiers Antennas Emission

The analysis and layout of a Switching Mode


AC/DC Power Supply Series APPLICATION NOTE

Mixed Mode EMI Noise Level Measurement in SMPS

Core Technology Group Application Note 6 AN-6

Probe Considerations for Low Voltage Measurements such as Ripple

Debugging EMI Using a Digital Oscilloscope. Dave Rishavy Product Manager - Oscilloscopes

IN-CIRCUIT RF IMPEDANCE MEASUREMENT FOR EMI FILTER DESIGN IN SWITCHED MODE POWER SUPPLIES

Single Switch Forward Converter

12. Output Ripple Attenuator Module (MicroRAM )

EMI Filter Design and Stability Assessment of DC Voltage Distribution based on Switching Converters.

Guide on Implementation of Requirements of the Common EPS

7. Transmitter Radiated Spurious Emissions and Conducted Spurious Emission

TOPSwitch Power Supply Design Techniques for EMI and Safety Application Note AN-15

MIW3000 Series EMI. 5-6W, Wide Input Range DIP, Single & Dual Output DC/DC Converters MINMAX. Block Diagram. Key Features

Chapter 1 Introduction

Analogue circuit design for RF immunity

Ileana-Diana Nicolae ICMET CRAIOVA UNIVERSITY OF CRAIOVA MAIN BUILDING FACULTY OF ELECTROTECHNICS

OUTLINE. Introduction. Introduction. Conducted Electromagnetic Interference in Smart Grids. Introduction. Introduction

MIL-STD 461F Results for M&A Technology Companion epad Computer

Measurement and Analysis for Switchmode Power Design

CHAPTER 6 EMI EMC MEASUREMENTS AND STANDARDS FOR TRACKED VEHICLES (MIL APPLICATION)

Chapter 12 Digital Circuit Radiation. Electromagnetic Compatibility Engineering. by Henry W. Ott

When input, output and feedback voltages are all symmetric bipolar signals with respect to ground, no biasing is required.

Electromagnetic Compatibility of Power Converters

Overview of EMC Regulations and Testing. Prof. Tzong-Lin Wu Department of Electrical Engineering National Taiwan University

Characterization of Conducted Electromagnetic Interference (EMI) Generated by Switch Mode Power Supply (SMPS)

EMI Noise Prediction for Electronic Ballasts

Essential Capabilities of EMI Receivers. Application Note

A Comparison Between MIL-STD and Commercial EMC Requirements Part 2. By Vincent W. Greb President, EMC Integrity, Inc.

Effectively Using the EM 6992 Near Field Probe Kit to Troubleshoot EMI Issues

Mitigation of Common mode Noise for PFC Boost Converter by Balancing Technique

Electro-Magnetic Interference and Electro-Magnetic Compatibility (EMI/EMC)

Common myths, fallacies and misconceptions in Electromagnetic Compatibility and their correction.

Tapped Inductor Bandpass Filter Design. High Speed Signal Path Applications 7/21/2009 v1.6

Technology in Balance

EMC in Power Electronics and PCB Design

RF Emissions Test Report To Determine Compliance With: FCC, Part 15 Rules and Regulations

Simulation Tool for Conducted EMI and Filter Design

Outcomes: Core Competencies for ECE145A/218A

Experiment 1: Instrument Familiarization (8/28/06)

Output Filtering & Electromagnetic Noise Reduction

FLTR100V20 Filter Module 75 Vdc Input Maximum, 20 A Maximum

Fixed Frequency Control vs Constant On-Time Control of Step-Down Converters

HigH Reliability emi FilteR

A Solution to Simplify 60A Multiphase Designs By John Lambert & Chris Bull, International Rectifier, USA

Keysight Technologies Essential Capabilities of EMI Receivers. Application Note

In particular, the filter module is compliant with the following requirements of MIL-STD-461C/D/E standards :

Testing and Verification Waveforms of a Small DRSSTC. Part 1. Steven Ward. 6/24/2009

Electromagnetic interference at the mains ports of an equipment

Experiment 1: Instrument Familiarization

Cool Power Technologies

Distributing Tomorrow s Technologies For Today s Designs Toll-Free:

While the Riso circuit is both simple to implement and design it has a big disadvantage in precision circuits. The voltage drop from Riso is

Emerging Standards for EMC Emissions & Immunity

E Typical Application and Component Selection AN 0179 Jan 25, 2017

Course Introduction Purpose Objectives Content Learning Time

The shunt capacitor is the critical element

Today most of engineers use oscilloscope as the preferred measurement tool of choice when it comes to debugging and analyzing switching power

50 μh Line Impedance Stabilisation Network (AC LISN)

ITG Electronics, Inc.

Designing Your EMI Filter

(typ.) (Range) Parameter Model Min. Typ. Max. Unit

Simulation Comparison of Resonant Reset Forward Converter with Auxiliary Winding Reset Forward Converter

American Power Design, Inc.

Application Note 323. Flex Power Modules. Input Filter Design - 3E POL Regulators

AN2447 Application note

Transcription:

The Causes and Impact of EMI in Power Systems; Part Chris Swartz

Agenda Welcome and thank you for attending. Today I hope I can provide a overall better understanding of the origin of conducted EMI in power systems. The topics we will cover in Part of our two part series will be: The definition of conducted EMI to include types, categories, coupling mechanisms and measurement standards for ITE type equipment I will discuss how conducted EMI is measured, test setups, measuring methods and the line impedance stabilization network The origin and characterization of differential mode EMI using a simulated Buck converter and a real world isolated DC-DC converter Common mode noise origins, paths and characterization using a simulation model of an isolated Full Bridge converter Finally, I hope to provide some tips on converter selection to help achieve lower EMI in your power system 2

What Is EMI? EMI stands for Electromagnetic Interference and it has been used to describe many different types of noise phenomena observed in modern power electronic systems in use today. The term interference is used somewhat loosely today. Interference means that one piece of equipments actual operation is disrupted by either another piece of equipment or an external signal source. Actual interference is not usually implied by the term EMI unless describing a prevention device, method or test. The two basic types of EMI are: Radiated EMI; measured in the far field using antennas Conducted EMI; measured at the power entry port using a line impedance stabilization network (LISN) There are two general categories of Conducted EMI (the focus of this seminar): Differential Mode Noise (sometimes referred to as Normal Mode) Common Mode Noise 3

How is EMI Coupled? There are four basic noise coupling mechanisms in electrical systems: Conductive; caused by direct contact with metal conductors ( ripple or grounding issues) Capacitive; caused by fast changing voltages applied to capacitance between conductors Inductive; caused by fast changing currents flowing in a loop (transformer action) Radiated; caused by far field electromagnetic coupling (antenna effect) Capacitive Radiated; Antenna Effect Conductive Inductive 4

What Are The Required Commercial Measurement Standards? There are conducted EMI standards for just about every kind of commercial electronics application and governing bodies that determine the test standards depending on the country where the equipment will be sold. Fortunately, most countries (including the US) have adopted the International Electro-technical Commission s (IEC) International Special Committee on Radio Interference (CISPR) standards for conducted EMI. Always check to see if other standards may apply for a particular country where the equipment may be sold for use. For Information Technology Equipment (IT or ITE) we are concerned with CISPR 22, which is the same standard as FCC Part 5 and the European EN55022. You may hear them used synonymously when referring to conducted EMI. Per CISPR 22, ITE equipment is divided into two (2) commercial classes: Class A Equipment Class A is industrial type equipment not intended for use in a domestic environment. Class B Equipment Class B equipment can be used in either industrial or domestic environments. 5

What Are The Required Military Measurement Standards? For most military power applications in the US and also many other NATO countries, the main standard to consider is MIL-STD-46 (latest revision). This standard covers not only conducted emissions and susceptibility but also radiated emissions and radiated susceptibility. For conducted emissions produced by power supplies: CE0 measured at the power leads using a LISN from 30 Hz to 0 khz CE02 measured at the power leads using a LISN from 0 khz to 0 MHz MIL-STD-46 documents which applications require CE0, where CE02 compliance is usually mandatory 6

How Is Conducted EMI Measured In Commercial Equipment? LISN Line Impedance Stabilization Network Copper Ground Plane Tied To Earth Ground 7

The Line Impedance Stabilization Network (Commercial Products) 50u L UUT_L Power Source R 39k 8u C6 250n C2 L_M V R7 5 R3 K R4 50 High frequency chokes L and L2 block high frequency noise from the power source C6 and R7 along with C and R8 form high frequency shunts to keep high frequency noise from the power source from entering measurement of the EUT (equipment under test) R2 39k R8 5 8u C LISN Line Impedance Stabilization Network 50u L2 R5 K 250n C3 R6 50 EARTH N_M UUT_N Unit under test power supplied here 8

:U2_UUT_L/:U2#UUT_L / Ohm The LISN Impedance Plot (Simulated) 00 0 Impedance-Ohms Impedance approximates 50 Ohms from 50kHz to 30MHz, the measurement standard for conducted EMI I 0 V2 L_IN UUT_L L_M LISN EARTH U2 V Impedance (Ohms) = V/I 50 R 00m N_IN N_M UUT_N AC V 0m m Frequency-Hz 00u 0 00 k 0k 00k M 0M 00M Frequency / Hertz 9

Measurement Requirements To Meet CISPR 22 The CISPR 22 standard requires that a unit meet the following conducted noise levels as measured between each conductor and earth ground using the specified measuring filters: Class A Class B This equation allows determination of the measured voltage for any level of conducted emission where V ref = uv. db V 20 log V unknown V ref For Class B at 500kHz, current measured at the LISN is: 99.5 uv / 50 Ohms = 4 ua! db V V unknown 0 20 V ref 0

The CE02 Limits For Military Products Based on peak measurements only. There are no quasipeak or average limits in CE02

Measurement Filters There are several measuring filter techniques that you should know about: Peak Detection This method is the fastest of all EMI scans. It also generates the highest amplitude results as well. An envelope detector is employed that can respond very quickly to amplitude changes in the envelope but without the ability to track the instantaneous value of the input signal. Quasi-Peak Detection This detection method is a form of weighted averaging that has a fast rise time constant but a slow fall time constant. Narrow duty cycle signals will measure a lower value than peak but as frequency or duty cycle increases, the measured value will start to approach peak detection. Quasi-Peak detection takes the longest of all EMI sweeps. Quasi-Peak Detection has higher limits to allow for an annoyance factor of the offending signal. Average This method is peak detection followed by a filter with a bandwidth that is lower than the resolution bandwidth. The result is that the higher frequency peaks get averaged to a lower value. Average detection is slower than peak but faster than quasi-peak. 2

Measurement Flow Start Peak Detector Is Peak < AVG limit? No Is Peak < QP limit? No Quasi-Peak Detector Yes Yes Average Detector Is QP < QP limit? Yes Yes Is AVG < AVG Limit? No Is QP < AVG limit? No Yes Pass!! Fail 3

Recap Covered testing.. Now discussing noise sources.. 4

Differential Mode Noise (A.K.A. Normal Mode) Differential mode noise is sometimes referred to as Normal Mode noise. There is a good reason for this. It results from an applied voltage differential ( of opposite polarity) between the noise source and the noise return. It can be caused by any or all (hopefully not!) of the four coupling methods previously discussed. Normal circuit operation is also differential in nature. Differential noise requires only two wires or a single wire and ground. Differential noise currents flow in opposite directions in input feeds or AC line and Neutral. Input voltage ripple, output voltage ripple are common examples of differential mode noise. Differential noise appears in all forms of power feeds both 2 wire feeds and three wire feeds. 5

Differential Mode Noise Ideal Buck Converter Consider the ideal buck converter shown below: This ripple current is responsible for the differential mode EMI that will be measured at the LISN. We are concerned about these ripple currents, as they are responsible for the ripple voltage measured at the node Vin. This ripple voltage is the source for the differential mode EMI that occurs at the fundamental as well as the much of the harmonic content. 6

Differential Mode Noise Ideal Buck Converter To generate the noise model, we modify the circuit as shown below: Add our LISN equivalent circuit 7

What If You Don t Know How The Design Works? Consider the circuit below, an isolated DC-DC Converter 48V-2V @ 300W U2 L_IN UUT_L U4 VIN+ Base_Plate VOUT+ 48 V L_M LISN EARTH N_M 00u C VOUT- VIN- 48V-2V ISOL DC-DC 300W 480m R N_IN UUT_N C3 4.7n C2 4.7n U3 CONVERTER SHIELD PLANE 8

What If You Don t Know How The Design Works? The data sheet called for C to be 00uF Electrolytic Capacitor and gave a part number for C U2 L_IN UUT_L U4 VIN+ Base_Plate VOUT+ 48 V L_M LISN EARTH N_M 00u C VOUT- VIN- 48V-2V ISOL DC-DC 300W 480m R N_IN UUT_N C3 4.7n C2 4.7n U3 CONVERTER SHIELD PLANE 9

What If You Don t Know How The Design Works? Step Remove C2, C3 Y capacitors to isolate common mode noise sources (more about that later) Step 2 Disconnect base plate and VOUT- from converter shield plane (common mode isolation) U2 L_IN UUT_L U4 VIN+ Base_Plate VOUT+ 48 V L_M LISN EARTH N_M 00u C VOUT- VIN- 48V-2V ISOL DC-DC 300W 480m R N_IN UUT_N U3 CONVERTER SHIELD PLANE 20

What If You Don t Know How The Design Works? Step 3 measure p/p AC ripple voltage across C carefully. If possible, measure the current with a current probe. In my case, adding the current probe was not possible. The manufacturer s datasheet listed a typical ESR of 00 mohms. U2 L_IN UUT_L U4 VIN+ Base_Plate VOUT+ 48 V L_M LISN EARTH N_M 00u C VOUT- VIN- 48V-2V ISOL DC-DC 300W 480m R N_IN UUT_N 3.62A p/p since 362mV p/p / 0. = 3.62A U3 CONVERTER SHIELD PLANE 2

What If You Don t Know How The Design Works? Step 4 Create your noise source model by replacing the current determined previously with a PWL or Current generator. Add the ESR in parallel with the current source and add your LISN model. 50u L 50 R3 LISN 362mV p/p 00m Resr I 3.62A p/p 50u L4 50 R4 Cin ESR 22

What If You Don t Know How The Design Works? Step 5 Take FFT of voltage of simulated LISN. 50u L 50 R3 LISN 99.3 dbuv peak 00m Resr I 3.62A p/p 50u L4 50 R4 Cin ESR 23

What If You Don t Know How The Design Works? Step 6 Take a scan of the power supply with a real LISN. Very close agreement observed. 50u L 50 R3 LISN 00m Resr I 3.62A p/p 50u L4 50 R4 Cin ESR 24

Ideal Buck Converter Other Considerations Know the start up input current and maximum dynamic step requirements These are critical requirements for selecting CIN and designing a proper input filter 25

Common Mode Noise Common mode noise always flows in the same direction in both input feeds (L and N) from an applied voltage between those common lines and earth ground (chassis, baseplate, test equipment etc.) It can be most difficult to determine the path since it can involve virtually any equipment connected to earth ground. Earth ground or a three wire system with an isolated ground is required. Non-isolated DC-DC Converters need not have much consideration for common mode noise. Test equipment can be very vulnerable based on the type of circuitry being measured. Isolated converters that connect output (-) to earth ground will have common mode + differential mode ripple at the output. Common mode noise can cause problems with non-isolated DC-DC converters if grounded test equipment has high common mode noise flowing between them. 26

27 Common Mode Noise Origin Isolated Full Bridge Topology 0p C8 0p C7 0p C6 0p C u R5 K R8 H 50m R6 C3 00u IC=46.8 Si9956DY Q4 LISN U2 EARTH UUT_L L_M N_M UUT_N L_IN N_IN P S S2 TX B+ E2 B- A- A+ A- 00p C8 00p C6 VOUT 0m R3 D 32ctq030h m R2 m R20 m R9 2u IC=0 L2 D2 32ctq030h 470u IC=9 C2 Si9956DY Q m R4 m R 200m R7 00p C7 00p C9 V E A+ V2 B+ B- u R RET 48 V3 u R2 Si9956DY Q2 Si9956DY Q3 D3 32ctq030h D4 32ctq030h D5 32ctq030h D6 32ctq030h C4 200p C5 200p 0p L 0p L3 BASEPLATE

28 Common Mode Noise Origin Isolated Full Bridge Topology 0p C8 0p C7 0p C6 0p C u R5 K R8 H 50m R6 C3 00u IC=46.8 Si9956DY Q4 LISN U2 EARTH UUT_L L_M N_M UUT_N L_IN N_IN P S S2 TX B+ E2 B- A- A+ A- 00p C8 00p C6 VOUT 0m R3 D 32ctq030h m R2 m R20 m R9 2u IC=0 L2 D2 32ctq030h 470u IC=9 C2 Si9956DY Q m R4 m R 200m R7 00p C7 00p C9 V E A+ V2 B+ B- u R RET 48 V3 u R2 Si9956DY Q2 Si9956DY Q3 D3 32ctq030h D4 32ctq030h D5 32ctq030h D6 32ctq030h C4 200p C5 200p 0p L 0p L3 BASEPLATE

S2 S P Common Mode Noise Origin Isolated Full Bridge Topology 20p 20p 48 V3 L_IN UUT_L U2 L_M LISN EARTH N_M 50m R6 C3 00u IC=46.8 A+ V R4 Si9956DY Q 00p C7 C7 20p C8 C 00p C8 Si9956DY Q4 R20 E2 B+ B- N_IN UUT_N A- B+ B- V2 R9 Si9956DY Q2 0m R3 00p C6 0p L C4 00p TX 20p C6 Si9956DY 00p C9 Q3 R2 A+ A- E If we do nothing, the return path must be through the mains and LISN! VOUT RET 200m R7 470u IC=9 C2 D4 D3 D 32ctq030h 32ctq030h 32ctq030h 2u IC=0 m L2 R D2 32ctq030h D5 32ctq030h D6 32ctq030h u u R u BASEPLATE R2 H R5 K R8 29

S2 S P Common Mode Noise Origin Isolated Full Bridge Topology 20p 20p 48 V3 L_IN LISN UUT_L L_M EARTH N_M U2 50m R6 C3 00u IC=46.8 A+ V R4 Si9956DY Q 00p C7 C7 20p C8 C 00p C8 Si9956DY Q4 R20 E2 B+ B- N_IN UUT_N The current that passes through the LISN is the common mode voltage measured from each line to ground divided by the LISN impedance. The common mode voltage is the source for the common mode portion of the EMI. A- B+ B- V2 VOUT RET u R2 R9 H 0m R3 Si9956DY 00p C6 Q2 200m 470u IC=9 R7 C2 u R u R5 K R8 0p C4 L 00p D4 D3 D 32ctq030h 32ctq030h 32ctq030h 2u IC=0 m L2 R TX D2 32ctq030h D5 D6 32ctq030h 32ctq030h BASEPLATE 20p C6 00p C9 Si9956DY Q3 R2 The actual measured EMI spectrum will consist of common mode + differential mode currents. There will be some cancellation that occurs and also some additions. E 30 A+ A-

Common Mode Noise Characterization Y capacitors are added to provide a lower impedance path for current to flow and to reduce the level of common mode voltage that appears between L-N and ground. Their effectiveness depends on the impedance of the common mode voltage source. Y capacitors U2 L_IN UUT_L U4 VIN+ Base_Plate VOUT+ 48 V L_M LISN EARTH N_M 00u C VOUT- VIN- 48V-2V ISOL DC-DC 300W 480m R N_IN UUT_N C2 C3 C4 U3 CONVERTER SHIELD PLANE 3

Common Mode Source Impedance The source impedance can be crudely estimated by adding an R-C between N-E and measuring the change in common mode voltage with increases in common mode current. A load line is then created to estimate the source impedance. This method should not be attempted on off-line power supplies or any supply that has hazardous voltages. The capacitor should have low ESR and be as large a value as possible. The results may be somewhat difficult to measure as there may be resonances and high frequency ringing that changes with resistor values used. In most cases, some external series impedance such as a dedicated common mode filter will be required. 32

Common Mode Source Impedance U2 VIN+ Base_Plate VOUT+ 48 V 00u C VOUT- VIN- 48V-2V ISOL DC-DC 300W 480m R C2 Measure current vs common mode voltage with various values of R2. R2 K CONVERTER SHIELD PLANE U3 33

S2 S P Add a Y Capacitor To Our Isolated Full Bridge Simulation 20p 20p 48 V3 L_IN UUT_L U2 L_M LISN EARTH N_M 50m R6 C3 00u IC=46.8 A+ V R4 Si9956DY Q 00p C7 C7 20p C8 C 00p C8 Si9956DY Q4 R20 E2 B+ B- N_IN UUT_N A- B+ B- V2 R9 Si9956DY Q2 0m R3 00p C6 0p L C4 00p TX 20p C6 Si9956DY 00p C9 Q3 R2 A+ A- E C5 4.7n u R2 VOUT RET H 200m R7 u R 470u IC=9 C2 u R5 K R8 D4 D3 D 32ctq030h 32ctq030h 32ctq030h 2u IC=0 m L2 R D2 32ctq030h D5 D6 32ctq030h 32ctq030h BASEPLATE With 4700pF capacitor added, our CM voltage dropped to 700mV p/p from 4V p/p. This means our source impedance is 6.5 Ohms. With that, it will still require an additional attenuation of 63dB to meet Class B! 34

Power Supply Selection Tips To Make EMI Compliance Easier As seen by our common mode EMI simulation, a rapidly changing voltage applied to a capacitance causes a high current slug into the base plate. Choosing a power supply that employs zero voltage switching can reduce this effect significantly due to resonant (slower) voltage changes. Be aware of power supplies that contain bipolar rectifier diodes that have snappy reverse recovery characteristics. For Buck regulators, look for circuits that avoid or minimize body diode conduction. MOSFET body diodes do not have desirable recovery characteristics. Snappy reverse recovery can cause high frequency broadband noise in the 5-30MHz region that can be difficult to solve. Body diode conduction reduces efficiency as well. High speed, hard switching can cause fast spikes and ringing at high frequency due to energy storage in parasitic inductances. Get a sample power supply and look at the waveforms. Clean waveforms = Lower EMI As power supplies get smaller and more efficient, there is less natural damping. Plan for filtering. 35

In Summary. The definition of conducted EMI including types, categories, coupling mechanisms and measurement standards was presented. There was a discussion of how EMI is measured, including test setups, limits, measuring filters and the line impedance stabilization network. The origin and characterization of differential mode EMI was presented using a simulated buck regulator and a real world example of a 300W isolated DC-DC converter. Finally, common mode noise origins, paths and characterization was presented using a simulation model of an isolated Full Bridge converter. Some tips were presented to help reduce EMI during the power supply selection process. 36

Part 2 Coming Attractions We will expand on input capacitor selection for a typical Buck regulator based on the characterization methods described here. We will also analyze some typical input filter configurations to show when input filter instability is present and how to avoid it. Various methods of common and differential mode filtering will be presented along with filter insertion loss measuring techniques. A method to reduce the overall size of the common mode filter will be presented. Finally, some real world examples from my case history files of solving filter problems including do s, don ts and troubleshooting techniques to solve EMI problems. 37

Acknowledgements The following material was used as references in the presentation of this seminar: Controlling Conducted Emissions By Design by John C. Fluke (an excellent book, highly recommended) Predict Differential Conducted EMI with a SPICE simulator Christophe Basso; April 2, 996 Making EMI Compliance Measurements Agilent Technologies Application Note CISPR 22 Fourth Edition Vicor Application Note AN-22 38

What Are The Required Commercial Measurement Standards? 39

What Are The Required Military Measurement Standards? 40

What Are The Required Military Measurement Standards? 4

How Is Conducted EMI Measured In Military Equipment? 42

The CISPR 22 Standards For Class A Commercial ITE Products 43

The CISPR 22 Standards For Class B Commercial ITE Products 44