DEIF A/S. Description of options. Option H1 Serial communication CAN open. Description of options. Functional description. Tables.

Similar documents
DEIF A/S. Description of options. Option H1, CAN open communication Basic Gen-set Controller. Description of option. Functional description

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description

Option H2, Modbus communication Automatic Gen-set Controller H SW version 2.33.X

DEIF A/S. Application note. Generators parallel with mains Multi-line 2 version 2. Application description. Power import control. Power export control

DEIF A/S. Application Notes. MDR-2 test procedures. Test of current measurement. Test of differential current measurement.

Option D1 Voltage/var/cos phi control Description of option Functional description

DESIGNER S REFERENCE HANDBOOK

Designer s Reference Handbook. Paralleling and Protection Unit/GS Multi-line I SW version 2.4X.X. Display unit and menu structure

PARAMETER LIST PARAMETER LIST

DEIF A/S. Application Notes. Basic Gen-set Controller. Single generator set. Automatic mains failure. Parallel with mains (grid)

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

Installation Instructions and Reference Handbook. Installation instructions

Remote Maintenance Box, RMB

Installation and start up instructions. Synchroniser type FAS-115DG uni-line H (UK) Synchronisation of generator to busbar

Generator Paralleling Controller, GPC-3 TCM-2 replacement Paralleling and Protection Unit, PPU-3

Installation and start up instructions. Synchroniser type FAS-113DG uni-line F (UK) Synchronisation of generator to busbar

DATA SHEET. Paralleling relays, HAS-111DG ANSI code 25

MBus Interface for Energy and Power meters AEM and APM

Option T2 Digital AVR: DEIF DVC Leroy Somer D510C Description of option Functional description

MULTI-LINE 2 DESCRIPTION OF OPTIONS. Option N Ethernet/IP. Document no.: B

CANopen Programmer s Manual Part Number Version 1.0 October All rights reserved

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups

Installation and start up instructions. Detection of vector shift. Detection of over- and underfrequency. Generator disconnection on mains failure

Installation and start up instructions. Paralleling relay type HAS-111DG uni-line G (UK) Synchronisation of generator to busbar

DEIF A/S. User s manual. Read synchroscope type RSQ-3. Precision LED synchronoscope. High immunity to harmonic distortion F (UK)

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification

C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS REFERENCE GUIDE

Automatic synchronising relay

Energy Management Energy Meter Type EM340

DATA SHEET AC current single function transducer TAC-311DG/TAC-321DG

INSTALLATION INSTRUCTIONS QUICK START GUIDE. Multi-transducer, MTR-3. Document no.: B SW version 3.0X.X or later

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE

Centrale de mesure Power Meter PM500 Merlin Gerin

SUPPLY NETWORK ANALYZER CVM-96 SERIES

Operating Guide October 2006

Function. Adjustment. Extra functions included. Modes. Housing

MODBUS RS485 SERIAL PROTOCOL

AQUAVAR CPC. Modbus Communications (Software Version 204 and later)* INSTRUCTION MANUAL ADAQCPC R1

TAS APFC Controller / Load Managers with MOD-BUS Interface

SELCO T-Line Generator Control, Protection and Monitoring

DATA SHEET Reverse power relays, RMP-121D ANSI code 32

Programming Guide CANopen VLT Midi Drive FC 280

MPS PROFIBUS-DP INTERFACE

DIRIS Ap RS485 JBUS/MODBUS COM. Systèmes de Coupure et de Protection Industrial Switching and Protection Systems ON 1

Contents. Introduction and description Package contents Device identification PM Options... 80

Metasys Integrator ESAM E as VND device Application

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN

Data Sheet. RISH Master Record %THD

DEIF A/S. TAS-311DG Selectable AC transducer J (UK) Installation and start up instructions

Energy Management Energy Analyzer Type EM111

CiA Draft Standard Proposal 402. CANopen. Device Profile Drives and Motion Control. This draft standard proposal is not recommended for implementation

MFR 3 Multi Function Relay

ALPTEC POWER FACTOR CONTROLLER

easygen-2000 Series Genset Control

E50 MODBUS POINT MAP

CANopen Programmer s Manual

DATA SHEET Differential current relays, RMC-131D ANSI code 87

USER MANUAL ZC-24DI. Via Austria, PADOVA ITALY. Tel Fax

ULTRA RAPID POWER QUALITY ANALYZER

CANopen Programmer s Manual

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

CAN-bus project. Using the CANbus Toolset software and the SELECONTROL MAS automation system. Master s Thesis. CAN-bus

PARAMETER LIST MICROFUSION

ZHUHAI PILOT TECHNOLOGY CO., LTD.

USER S MANUAL Multi-instrument, MIQ96-3

User's guide RD4. Position measurement & control

DATA SHEET. CIO multi-inputs. CAN bus-based I/O module

Energy Management Energy Meter Type EM112

Energy Management Energy Meter Type EM111

AG FB-CAN. Absolute encoder viva CAN. Product Manual E-V0204.doc

A TEMPOSONICS R

COMMUNICATION MODBUS PROTOCOL MFD44 NEMO-D4Le

Protection relays and controllers. Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB

PLA 33. Power line analyzer. User and service manual. version 2.4

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

Digital Multifunction Instrument - Rish Master 3440

SIPROTEC Feeder Automation Controller 7SC80

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

BMS BMU Vehicle Communications Protocol

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

Capacitor protection relay

Applied Motion Products CANopen Manual

Contents. FC 300 CANopen

Energy Management Energy Analyzer Type EM112

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

Universal MEMS Inclination Sensor with Analog Output. Output /Excitation U6 U8 I1

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

Universal-Transducer Multi-E11-MU

Metasys Integrator Power Measurement Ltd. Application

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

Modbus communication module for TCX2: AEX-MOD

SonoMeter 31 Energy Meters

Electronic Circuit Breaker ECONOMY REMOTE

JBus/Modbus Communication Card

REACTIVE ENERGY REGULATOR

ELECTRICAL VARIABLE ANALYZER RELAY EVAR

POSICHRON position sensor in a stainless steel pressure tube. Protection class IP68/IP69K

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Transcription:

Description of options Option H1 Serial communication CAN open 4189340277G SW version 2.42.X Description of options Functional description DEIF A/S Tables Parameter list Object dictionary DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615 DK-7800 Skive, Denmark E-mail: deif@deif.com, URL: www.deif.com

Table of contents 1. WARNINGS AND LEGAL INFORMATION... 3 LEGAL INFORMATION AND RESPONSIBILITY... 3 ELECTROSTATIC DISCHARGE AWARENESS... 3 SAFETY ISSUES... 3 DEFINITIONS...3 2. DESCRIPTION OF OPTIONS... 4 TERMINAL DESCRIPTION... 4 3. FUNCTIONAL DESCRIPTION... 5 GENERAL INTRODUCTION... 5 TRANSFER TYPES... 5 COMMUNICATION SPEED... 6 PDO TRANSFER... 6 COB-IDS USED FOR PDO TRANSFER... 6 IDENTIFIER ALLOCATION... 7 ADDITIONAL INFORMATION... 8 4. TABLES... 9 APPLICATION OBJECTS FOR PDO/SDO TRANSFER... 9 APPLICATION OBJECTS FOR SDO TRANSFER... 13 EDS-FILE... 17 5. PARAMETER LIST... 18 COMMUNICATION CONTROL... 18 CAN BUS ALARMS... 18 This manual is valid for standard multi-line 2 PPU/GPC/GPU units with firmware version 2.42.1 or later. DEIF A/S Page 2 of 18

1. Warnings and legal information Legal information and responsibility DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the generator set controlled by the unit, the company responsible for the installation or the operation of the set must be contacted. The units are not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost. Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary. Safety issues Installing the unit implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment. Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death. Definitions Throughout this document a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text. Notes The notes provide general information which will be helpful for the reader to bear in mind. Warning The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed. DEIF A/S Page 3 of 18

2. Description of options This document describes the functionality of the CAN open communication for the GPU, GPC and PPU. Function ANSI no. CAN open communication - Terminal description Term. Function Description 29 CAN-H The CAN is based on CAN open 30 GND 31 CAN-L 32 CAN-H 33 GND 34 CAN-L 35 Not used 36 Not used Terminals 29 and 32 are internally connected (CAN-H). Terminals 30 and 33 are internally connected (CAN-L). Terminals 31 and 34 are internally connected (GND). For wiring diagrams, please refer to the installation instructions. DEIF A/S Page 4 of 18

3. Functional description General introduction This document describes the CAN bus based serial interface to the multi-line 2 GPU, GPC and PPU. The CAN protocol implementation is based on the CAN open Application Layer and Communication Profile Specification CiA Draft Standard 301 Version 4.01. This protocol does not describe all functionalities of the CAN open communication, which have been implemented and are running in accordance with the CAN open standards and therefore require no consideration from the user. Please visit http://www.can-cia.com to download a detailed explanation of the CAN open description. Transfer types The transfer types are described shortly. PDO transfer Process Data Objects (PDO) provide direct access to application objects within a device, e.g. the Multi-line 2. The application objects for PDO transfer are the measurement values which can be seen in the table Application objects for SDO/PDO transfer, p. 9. PDOs are used to performing real-time transfers of short blocks of high priority data. Each PDO telegram must contain one COB-ID (Communication Object-Identifier) and maximum eight bytes of data (the application objects). PDO telegrams are used for transfer of measurement values in this protocol (e.g. UL1-L2, UL2- L3, UL3-L1, UL1-N) from a slave device (multi-line 2 unit) to the master (PLC). SDO transfer Service Data Object (SDO) can be used for access with read/write attributes of all application objects (some objects can only be accessed with reading or writing attribute) implemented in the multi-line 2 regarding CAN open. SDO telegrams are used for transfer of measurement data from a slave device (multi-line 2 unit) to the master (PLC) and they are used for transferring commands from the master device (PLC) to the slave device (Multi-line 2 unit). NMT transfer Network Management (NMT) transfer is used to control the application in the slave device from the master. DEIF A/S Page 5 of 18

Communication speed The table shows the communication speed that is supported. Bit rates Bus length Comment 125 kbit/s 500 m Factory setting 50 kbit/s 1000 m 20 kbit/s 2500 m 10 kbit/s 5000 m When the bit rate is changed the multi-line 2 must be reset (powered down) to activate the new communication speed. PDO transfer PDO triggering mode The transmission type 5 to 240 is supported in the multi-line 2 units. (Default value is 5 in the EDS file). Each time the multi-line 2 unit has received 5 synchronisation objects (sync. telegrams with the COB-ID 0x80) from the master, the slave device is trigged to a response with all PDO telegrams using the transmission type 5 as trigging mode. It is recommended to use the same transmit type for all the PDOs telegrams in this protocol. PDO static mapping It is not possible to change the address ranges of the values used for PDO transfer. Therefore, the values map in each PDO is static. (See page 9 for application objects used for PDO transfer). PDO configuration and allocation of COB-ID In this application for CAN open there is room for 8 transmit PDOs, all PDOs are used for transfer of measurement values. The configuration of a PDO consists of setting the communication parameters of each PDO itself, the COB-ID and the transmission type. This protocol supports 11 bit identifiers meaning the possibility of 2047 different COB-IDs. Do not use COB-IDs for PDO transfer which is used for other communication processes in CAN open. Each multi-line 2 unit must have a unique node-id, which is configured in the display or in the PC utility software. COB-IDs used for PDO transfer The tables show the default selected COB-IDs (communication object identifiers) which are used for PDO transfer. DEIF A/S Page 6 of 18

Default COB-ID, node 1 Default COB-ID, node 2 COB-ID Dec. Hex. PDO telegram No. 259 0x103 1 386 0x182 2 514 0x202 3 642 0x282 4 770 0x302 5 898 0x382 6 1026 0x402 7 1154 0x482 8 COB-ID Dec. Hex. PDO telegram No. 260 0x104 1 387 0x183 2 515 0x203 3 643 0x283 4 771 0x303 5 899 0x383 6 1027 0x403 7 1155 0x483 8 Example of PDO telegram Examples of transmitting PDO telegrams from slave device to master device with node-id number 1: Field name COB-ID U L1-L2 U L2-L3 U L3-L1 U L1-N Example 0x103 2 bytes 2 bytes 2 bytes 2 bytes Identifier allocation In networks where the identifier allocation is to be altered by a configuration tool using SDOs there are some recommendations which should be taken into account. SDO transfer is used to access all objects implemented in the multi-line 2 unit regarding CAN open. Be aware of the allocation of the COB-ID for PDO transfer because some COB-IDs are predefined for other communication processes in CAN open. Object Resulting identifiers (COB-ID) NMT module control 0 Synchronisation object 128(0x80) SDO (transmit) 1409-1535(0x581-0x5FF) SDO (receive) 1537-1663(0x601-0x67F) NMT error control and boot-up service 1793-1919(0x701-0x77F) If the configuration tools cannot read the default values for the COB-ID for PDOs from the eds-file, the COB-IDs have to be allocated manually. DEIF A/S Page 7 of 18

Additional information Please note the below-mentioned important information regarding CAN open features. These points must be taken into consideration when using CAN open. 1. This protocol does not support any device profile. 2. Object index 1000 and sub index 0 for device profile is implemented with the value 0x00. 3. Object index 100C and sub index 0 for guard time is implemented with the value 0x1000. 4. The guarding time must be 1000 ms as a minimum. Please also refer to www.can-cia.com for details. DEIF A/S Page 8 of 18

4. Tables Application objects for PDO/SDO transfer Table for measurement values used for PDO telegrams. Content Type PDO no. U L1-L2 Generator voltage. Measured in [V] 1 U L2-L3 Generator voltage. Measured in [V] 1 U L3-L1 Generator voltage. Measured in [V] 1 U L1-N Generator voltage. Measured in [V] 1 U L2-N Generator voltage. Measured in [V] 2 U L3-N Generator voltage. Measured in [V] 2 F GEN Generator frequency. Measured in [Hz/100] 2 Cos-phi -99...0...100 Generator cosinus-phi. Measured in 2 cos-phi:100 Negative value means capacitive cosphi I L1 Generator current. Measured in [A] 3 I L2 Generator current. Measured in [A] 3 I L3 Generator current. Measured in [A] 3 P GEN Generator active power. Measured in [W]. Negative 3 value means reverse power Q GEN Generator reactive power. Measured in [var]. 4 Positive value means generated inductive reactive power S GEN Generator seeming power. Measured in [VA] 4 [HI] E GEN Energy counter. Measured in [kwh]. Max. 300000 4 MWh [LO] E GEN Energy counter. Measured in [kwh]. Max. 300000 MWh 4 Alarms Bit 0 1010. Reverse power 5 Bit 1 1020. Overcurrent step 1 Bit 2 1030. Overcurrent step 2 Bit 3 1060. Overcurrent inverse Bit 4 1070. Fast overcurrent Bit 5 1080. High overcurrent Bit 6 Reserved Bit 7 1100. U-DG high step 1 Bit 8 1110. U-DG high step 2 Bit 9 1120. U-DG low step 1 Bit 10 1130. U-DG low step 2 Bit 11 1140. f-dg high step 1 Bit 12 1150. f-dg high step 2 Bit 13 1160. f-dg low step 1 Bit 14 1170. f-dg low step 2 Bit 15 1180. U-BB high step 1 DEIF A/S Page 9 of 18

Content Type PDO no. Alarms Bit 0 1190. U-BB high step 2 5 Bit 1 1200. U-BB low step 1 Bit 2 1210. U-BB low step 2 Bit 3 1220. f-bb high step 1 Bit 4 1230. f-bb high step 2 Bit 5 1240. f-bb low step 1 Bit 6 1250. f-bb low step 2 Bit 7 1260. Overload step 1 Bit 8 1270. Overload step 2 Bit 9 1280. Unbalance current Bit 10 1290. Unbalance voltage Bit 11 1300. Q import Bit 12 1310. Q export Bit 13 1320. Gen. neg. sequence current Bit 14 1330. Gen. neg. sequence voltage Bit 15 1390. Overload step 3 Alarms Bit 0 1350. df/dt (ROCOF) 5 Bit 1 1360. Vector jump Bit 2 3010. 4-20 ma input no. 1 Bit 3 3020. 4-20 ma input no. 2 Bit 4 3030. 4-20 ma input no. 3 Bit 5 3040. 4-20 ma input no. 4 Bit 6 3050. 4-20 ma input no. 5 Bit 7 3060. 4-20 ma input no. 6 Bit 8 3070. 4-20 ma input no. 7 Bit 9 3080. 4-20 ma input no. 8 Bit 10 3090. Pt100 no. 1 Bit 11 3100. Pt100 no. 2 Bit 12 3110. Overspeed (tacho) Bit 13 3120. Dig. input term. 23 Bit 14 3130. Dig. input term. 24 Bit 15 3140. Dig. input term. 25 Alarms Bit 0 3150. Dig. input term. 26 5 Bit 1 3160. Dig. input term. 27 Bit 2 3170. Dig. input term. 43 Bit 3 3180. Dig. input term. 44 Bit 4 3190. Dig. input term. 45 Bit 5 3200. Dig. input term. 46 Bit 6 3210. Dig. input term. 47 Bit 7 3220. Dig. input term. 48 Bit 8 3230. Dig. input term. 49 Bit 9 3240. Dig. input term. 50 Bit 10 3250. Dig. input term. 51 Bit 11 3260. Dig. input term. 52 Bit 12 3270. Dig. input term. 53 Bit 13 3280. Dig. input term. 110 Bit 14 3290. Dig. input term. 111 Bit 15 3300. Dig. input term. 112 DEIF A/S Page 10 of 18

Content Type PDO no. Alarms Bit 0 3310. Dig. input term. 113 6 Bit 1 3320. Dig. input term. 114 Bit 2 3330. Dig. input term. 115 Bit 3 3340. Dig. input term. 116 Bit 4 3350. Dig. input term. 117 Bit 5 3360. Dig. input term. 118 Bit 6 3370. Dig. input term. 127 Bit 7 3380. Dig. input term. 128 Bit 8 3390. Dig. input term. 129 Bit 9 3400. Dig. input term. 130 Bit 10 3410. Dig. input term. 131 Bit 11 3420. Dig. input term. 132 Bit 12 3430. Dig. input term. 133 Bit 13 3440. Oil pressure (VDO sensor 1) Bit 14 3450. Water temperature (VDO sensor 2) Bit 15 3460. Fuel level (VDO sensor 3) System alarms/status Bit 0 Sync. fail. alarm Bit 1 Generator breaker ON Bit 2 Generator breaker OFF Bit 3 Generator breaker position fail. alarm Bit 4 Phase sequence error alarm Bit 5 Governor regulator fail. alarm Bit 6 AVR regulator fail. alarm Bit 7 Battery voltage alarm Bit 8 Sync. timer runout Bit 9 Reserved Bit 10 Reserved Bit 11 Start attempt alarm Alarm relay status Bit 0 Relay 0 Bit 1 Relay 1 Bit 2 Relay 2 Bit 3 Relay 3 Bit 4 Relay 4 Bit 5 Relay 5 Bit 6 Relay 6 Bit 7 Relay 7 Bit 8 Relay 8 Bit 9 Relay 9 (stop engine) Bit 10 Relay 10 Bit 11 Relay 11 Bit 12 Relay 12 Bit 13 Relay 13 6 6 DEIF A/S Page 11 of 18

Content Type PDO no. Status Bit 0 Mode 1 6 Bit 1 Mode 2 Bit 2 Mode 3 Bit 3 Mode 4 Bit 4 Mode 5 Bit 5 Mode 6 Bit 6 De-load Bit 7 Start sync./reg. Bit 8 Alarm inhibit Bit 9 Breaker position ON Bit 10 Synchronising U DG-Max Generator max. voltage. Measured in [V] 7 U DG-Min Generator min. voltage. Measured in [V] 7 U SUPPLY Supply voltage. Measured in [V/10] 7 F BB Busbar frequency. Measured in [Hz/100] 7 Number of alarms 8 Number of unacknowledged alarms 8 U BBL1-L2 Busbar. Measured in [V] 8 U BBL1-N Busbar voltage. Measured in [V] 8 DEIF A/S Page 12 of 18

Application objects for SDO transfer These values can ONLY be accessed with SDO transfer. Control register table Index Sub index Content 200F 0 Power regulator set point 2010 0 PF regulator set point 2011 0 Control command 2012 0 Frequency regulator set point 2013 0 Voltage regulator set point 2014 0 Reactive power regulator set point Description 0...100% of nominal power Activated in menu 4051 60...100 stated as PF value/100. The value 100 means PF = 1 Activated in menu 4055 Bit 0 This bit must be 1 when writing the command word. If the bit is 0, the control command is ignored. Bit 1 Mode 1 Bit 2 Mode 2 Bit 3 Mode 3 Bit 4 Mode 4 Bit 5 Mode 5 Bit 6 Mode 6 Bit 7 De-load Bit 8 Start sync./control Bit 9 Alarm inhibit Bit 10 Alarm ack. This bit is automatically reset in multi-line 2 Bit 11 Second set point (protection functions) Bit 12 Remote mode (option M1/M2) * Bit 13 Local mode (option M1/M2)* -50...50Hz/10. Based on nominal frequency Activated in menu 4042-100...100%/10 of nominal voltage Activated in menu 4043-100...100% of nominal power. A negative value means capacitive reactive power and a positive value means inductive reactive power Measurement table Index Sub Content SDO transfer only index 2000 0 Application version 2001 1 U L1-L2 Generator voltage. Measured in [V] 2001 2 U L2-L3 Generator voltage. Measured in [V] 2001 3 U L3-L1 Generator voltage. Measured in [V] 2001 4 U L1-N Generator voltage. Measured in [V] 2001 5 U L2-N Generator voltage. Measured in [V] 2001 6 U L3-N Generator voltage. Measured in [V] 2002 1 F GEN Generator frequency. Measured in [Hz/100] 2002 2 Cos-phi -99...0...100 Generator cosinus-phi. Measured in cosphi:100. Negative value means capacitive cos-phi 2002 3 P GEN Generator active power. Measured in [kw]. Negative value means reverse power DEIF A/S Page 13 of 18

Index Sub Content SDO transfer only index 2002 4 Q GEN Generator reactive power. Measured in [kvar]. Positive value means generated inductive reactive power 2003 1 I L1 Generator current. Measured in [A] 2003 2 I L2 Generator current. Measured in [A] 2003 3 I L3 Generator current. Measured in [A] 2004 1 U BBL1-L2 Busbar. Measured in [V] 2004 2 F BB Busbar frequency L1. Measured in [Hz/100] 2005 1 [HI] R GEN Reactive energy counter. Measured in [kvarh]. Max. 300000 Mvarh 2005 2 [LO] R GEN Reactive energy counter. Measured in [kvarh]. Max. 300000 Mvarh 2005 3 [HI] E GEN Energy counter. Measured in [kwh]. Max. 300000 MWh 2005 4 [LO] E GEN Energy counter. Measured in [kwh]. Max. 300000 MWh 2006 1 Alarms Bit 0 1010. Reverse power Bit 1 1020. Overcurrent step 1 Bit 2 1030. Overcurrent step 2 Bit 3 1060. Overcurrent inverse Bit 4 1070. Fast overcurrent Bit 5 1080. High overcurrent Bit 6 Reserved Bit 7 1100. U-DG high step 1 Bit 8 1110. U-DG high step 2 Bit 9 1120. U-DG low step 1 Bit 10 1130. U-DG low step 2 Bit 11 1140. f-dg high step 1 Bit 12 1150. f-dg high step 2 Bit 13 1160. f-dg low step 1 Bit 14 1170. f-dg low step 2 Bit 15 1180. U-BB high step 1 2006 2 Alarms Bit 0 1190. U-BB high step 2 Bit 1 1200. U-BB low step 1 Bit 2 1210. U-BB low step 2 Bit 3 1220. f-bb high step 1 Bit 4 1230. f-bb high step 2 Bit 5 1240. f-bb low step 1 Bit 6 1250. f-bb low step 2 Bit 7 1260. Overload step 1 Bit 8 1270. Overload step 2 Bit 9 1280. Unbalance current Bit 10 1290. Unbalance voltage Bit 11 1300. Q import Bit 12 1310. Q export Bit 13 1320. Gen. neg. sequence current Bit 14 1330. Gen. neg. sequence voltage Bit 15 1390. Overload step 3 2006 3 Alarms Bit 0 1350. df/dt (ROCOF) Bit 1 1360. Vector jump Bit 2 3010. 4-20 ma input no. 1 Bit 3 3020. 4-20 ma input no. 2 Bit 4 3030. 4-20 ma input no. 3 Bit 5 3040. 4-20 ma input no. 4 Bit 6 3050. 4-20 ma input no. 5 Bit 7 3060. 4-20 ma input no. 6 Bit 8 3070. 4-20 ma input no. 7 DEIF A/S Page 14 of 18

Index Sub index Content SDO transfer only Bit 9 3080. 4-20 ma input no. 8 Bit 10 3090. Pt100 no. 1 Bit 11 3100. Pt100 no. 2 Bit 12 3110. Overspeed (tacho) Bit 13 3120. Dig. input term. 23 Bit 14 3130. Dig. input term. 24 Bit 15 3140. Dig. input term. 25 2006 4 Alarms Bit 0 3150. Dig. input term. 26 Bit 1 3160. Dig. input term. 27 Bit 2 3170. Dig. input term. 43 Bit 3 3180. Dig. input term. 44 Bit 4 3190. Dig. input term. 45 Bit 5 3200. Dig. input term. 46 Bit 6 3210. Dig. input term. 47 Bit 7 3220. Dig. input term. 48 Bit 8 3230. Dig. input term. 49 Bit 9 3240. Dig. input term. 50 Bit 10 3250. Dig. input term. 51 Bit 11 3260. Dig. input term. 52 Bit 12 3270. Dig. input term. 53 Bit 13 3280. Dig. input term. 110 Bit 14 3290. Dig. input term. 111 Bit 15 3300. Dig. input term. 112 2006 5 Alarms Bit 0 3310. Dig. input term. 113 Bit 1 3320. Dig. input term. 114 Bit 2 3330. Dig. input term. 115 Bit 3 3340. Dig. input term. 116 Bit 4 3350. Dig. input term. 117 Bit 5 3360. Dig. input term. 118 Bit 6 3370. Dig. input term. 127 Bit 7 3380. Dig. input term. 128 Bit 8 3390. Dig. input term. 129 Bit 9 3400. Dig. input term. 130 Bit 10 3410. Dig. input term. 131 Bit 11 3420. Dig. input term. 132 Bit 12 3430. Dig. input term. 133 Bit 13 3440. Oil pressure (VDO sensor 1) Bit 14 3450. Water temperature (VDO sensor 2) Bit 15 3460. Fuel level (VDO sensor 3) 2006 6 System alarms/ Bit 0 Sync. fail. alarm status Bit 1 Generator breaker ON Bit 2 Generator breaker OFF Bit 3 Generator breaker position fail. alarm Bit 4 Phase sequence error alarm Bit 5 Governor regulator fail. alarm Bit 6 AVR regulator fail. alarm Bit 7 Battery voltage alarm Bit 8 Sync. timer runout Bit 9 Reserved Bit 10 Reserved Bit 11 Start attempt alarm DEIF A/S Page 15 of 18

Index Sub index Content 2006 7 Alarm relay status SDO transfer only Bit 0 Relay 0 Bit 1 Relay 1 Bit 2 Relay 2 Bit 3 Relay 3 Bit 4 Relay 4 Bit 5 Relay 5 Bit 6 Relay 6 Bit 7 Relay 7 Bit 8 Relay 8 Bit 9 Bit 10 Relay 10 Bit 11 Relay 11 Bit 12 Relay 12 Bit 13 Relay 13 2007 0 Status Bit 0 Mode 1 Bit 1 Mode 2 Bit 2 Mode 3 Bit 3 Mode 4 Bit 4 Mode 5 Bit 5 Mode 6 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Relay 9 (stop engine) De-load Start sync./reg. Alarm inhibit Breaker position ON Synchronising 2008 1 Number of alarms 2008 2 Number of unacknowledged alarms 2009 1 U DG-Max Generator max. voltage. Measured in [V] 2009 2 U DG-Min Generator min. voltage. Measured in [V] 2009 3 U BBL2-L3 Busbar voltage. Measured in [V] 2009 4 U BBL3-L1 Busbar voltage. Measured in [V] 200A 1 U BB-Max Busbar max. voltage. Measured in [V] 200A 2 U BB-Min Busbar min. voltage. Measured in [V] 200A 3 U BBL1-N Busbar voltage. Measured in [V] 200A 4 U BBL2-N Busbar voltage. Measured in [V] 200A 5 U BBL3-N Busbar voltage. Measured in [V] 200B 0 S GEN Generator seeming power. Measured in [kva] 200C 1 VDO 1 Oil pressure in [bar]/10 200C 2 VDO 2 Water temp. in [ o C] 200C 3 VDO 3 Fuel level in [%] 200C 4 PHI BBL3-L1 0 359 Busbar phase angle. Measured in [deg] 200C 5 PHI BBL1-DGL1 0 359 Busbar/generator phase angle. Measured in [deg] 200D 0 Spare 200E 0 U SUPPLY Supply voltage. Measured in [V/10] 2015 1 Pt100-40. 250 temperature in deg. (engine interface) 2015 2 Pt100-40. 250 temperature in deg. (engine interface) 2016 1 Control register table address 0 2016 2 Control register table address 1 2016 3 Control register table address 3 2016 4 Control register table address 4 2016 5 Control register table address 5 DEIF A/S Page 16 of 18

Index Sub Content SDO transfer only index 2017 1 Analog input engine interface no. 1 (scaled) 2017 2 Analog input engine interface no. 2 (scaled) 2017 3 Analog input engine interface no. 3 (scaled) 2017 4 Analog input engine interface no. 4 (scaled) 2017 5 Analog input engine interface no. 5 (scaled) 2017 6 Analog input engine interface no. 6 (scaled) 2017 7 Analog input engine interface no. 7 (scaled) 2017 8 Analog input engine interface no. 8 (scaled) 2018 0 Running time Hour 2019 0 RPM RPM 201A 0 CB oper Circuit beaker operations counter EDS-file The EDS-file (ELECTRONIC DATA SHEETS) is used for configuration tools to read the implementation of the CAN open features supported in the multi-line 2 unit. The EDS file contains the object dictionary. The object dictionary describes all data types, communication objects and application objects implemented in multi-line 2 units regarding CAN open. All objects can be accessed with SDO transfer. The object dictionary is similar to the EDS file, and to see the entire object dictionary please refer to this file. It can be downloaded from www.deif.com and can be opened in the program Notepad. DEIF A/S Page 17 of 18

5. Parameter list The setup of parameters is done via the display or the PC utility software (USW). For further information about menu structure, see the Designer s Reference Handbook. Communication control 4050 Communication control This selection enables/disables the CAN bus control of the parameters: No. Setting Min. setting Max. setting Factory setting 4051 Comm. control Power OFF ON OFF 4052 Comm. control Frequency OFF ON OFF 4053 Comm. control Voltage OFF ON OFF 4054 Comm. control VAr OFF ON OFF 4055 Comm. control PF OFF ON OFF Selecting communication control ON will overrule external and internal settings. 4060 External communication control No. Setting Min. setting Max. setting Factory setting 4060 External comm. Selection display - - - 4061 External comm. ID 1 50 1 4062 External comm. Baud rate 10000 125000 125000 4090 External communication error No. Setting Min. setting Max. setting Factory setting 4091 Ext. comm. error Delay 1.0 s 100.0 s 10.0 s 4092 Ext. comm. error Relay output A R0 (none) Option R0 (none) 4093 Ext. comm. error Relay output B R0 (none) dependent R0 (none) 4094 Ext. comm. error Enable OFF ON OFF CAN bus alarms Failed CAN transmit : Failed CANBUS OFF : E.g. noise disturbances or CAN bus line not connected E.g. noise disturbances or CAN bus line short-circuited DEIF A/S reserves the right to change any of the above DEIF A/S Page 18 of 18