Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Similar documents
Effects of GIC on Power Transformers and Power Systems

Transformers and power quality Part II. Modelling and researching generation of higher harmonics in small three-phase transformers

TECHNICAL BULLETIN 004a Ferroresonance

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

MATHEMATICAL MODELING OF POWER TRANSFORMERS

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

Magnetizing current of a Large Power Transformer and its Harmonic Spectrum in Normal and GIC conditions

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

Long lasting transients in power filter circuits

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

OPTIMUM DESIGN ASPECTS OF A POWER AXIAL FLUX PMSM

Frequency domain analysis of a power transformer experiencing sustained ferroresonance

936 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL /$ IEEE

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Evaluating Transformer Heating due to Geomagnetic Disturbances

Keywords: Transformer modeling, saturation, hysteresis, MATLAB. Introduction

Importance of Transformer Demagnetization

Electromagnetic Modelling of Power Transformers with DC Magnetization Seyed Ali Mousavi

Ferroresonance Experience in UK: Simulations and Measurements

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC Converter Transfomer Due to GIC

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Effect of Harmonics on the Performance Characteristics of Three Phase Squirrel Cage Induction Motor

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

DIRECT CURRENT COMPENSATION FIELD EXPERIENCE UNDER SERVICE CONDITIONS

Demagnetization of Power Transformers Following a DC Resistance Testing

EMT Model of the Sen Transformer for Fault Analysis Studies

FERRORESONANCE SIMULATION STUDIES USING EMTP

Picture perfect. Electromagnetic simulations of transformers

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Transformer Technology Seminar GIC Capability of Power Transformers

Power System Impacts of Geomagnetic Disturbances

OMAR SH. ALYOZBAKY et al : THE BEHAVIOUR OF THREE PHASE THREE- LEG 11KV TRANSFORMER CORE.

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Sensitivity studies on power transformer ferroresonance of a 400 kv double circuit

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

Transients under energizing multiple power filter circuits

IMPACT OF INRUSH CURRENTS AND GEOMAGNETICALLY INDUCED CURRENTS ON TRANSFORMER BEHAVIOR

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in Docket No. RM15 11 on June 28, 2016.

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

Simultaneous AC-DC Transmission Scheme Under Unbalanced Load Condition

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

Failure of Transformers Due to Harmonic Loads

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Effects of the Short-Circuit Faults in the Stator Winding of Induction Motors and Fault Detection through the Magnetic Field Harmonics

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

Direct Harmonic Analysis of the Voltage Source Converter

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

POWER TRANSFORMERS: Saturation Compensation Modeling, Simulation, and Experiments

International Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD

UNDERSTANDING SUB-HARMONICS

A NOVEL METHOD FOR ENERGIZING TRANSFORMERS FOR REDUCING INRUSH CURRENTS

Investigation of Magnetic Field and Radial Force Harmonics in a Hydrogenerator Connected to a Three-Level NPC Converter

Control Strategies and Inverter Topologies for Stabilization of DC Grids in Embedded Systems

The Engineering Problem. Calculating GIC Flow through the EHV System

High-frequency Transformer Modeling for Transient Overvoltage Studies

Development of power transformer design and simulation methodology integrated in a software platform

Analysis of Losses in High Speed Slotless PM Synchronous Motor Integrated the Added Leakage Inductance

An induced emf is the negative of a changing magnetic field. Similarly, a self-induced emf would be found by

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

Simulation and Analysis of Ferroresonance in Power System

Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator

Measurements for validation of high voltage underground cable modelling

Impact of Solar Storms on the Swiss Transmission Network

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Voltage and Current Waveforms Enhancement using Harmonic Filters

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

Keywords: Wavelet packet transform (WPT), Differential Protection, Inrush current, CT saturation.

Methods of measuring and modelling geomagnetically induced currents (GICs) in a power line.

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

GMD Impacts on Generators

Electric Power Applications

I p = V s = N s I s V p N p

About the High-Frequency Interferences produced in Systems including PWM and AC Motors

The power transformer

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Power Quality Analysis in Power System with Non Linear Load

Analysis of Modern Digital Differential Protection for Power Transformer

POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

CHAPTER 4. Distribution Transformers

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*

(2) New Standard IEEE P (3) Core : (4) Windings :

Transcription:

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs S. A. Mousavi, C. Carrander, G. Engdahl Abstract-- This paper studies the effect of DC magnetization of power transformers on injected harmonics to power systems. DC magnetization due to geomagnetically induced currents can saturate the core of a power transformer during a half cycle. It causes a very asymmetric, high value magnetization current that contains large harmonic components. In this work, by using a three-dimensional finite element model, the effect of core type and DC current level on generated harmonics is investigated. The results could help power system engineers to choose the proper types of power transformers and improve the protection aspects of the network. Keywords: Geomagnetically induced currents, GIC, Power transformers, saturation, magnetization current, harmonic, FEM. I. INTRODUCTION C currents in the form of geomagnetically induced Dcurrents (GIC) can be injected in three-phase transformers or banks of single-phase transformers with grounded star-connected windings [1-5]. The frequencies of these currents are very low and they are quasi-dc. GIC current causes the transformer core to be saturated during one of the half cycles of each supply voltage period [1]. This phenomenon can lead to several ill effects in both power transformers and the power system. One of these effects is the problems of harmonics that are created due to magnetization currents of transformers. Both even and odd harmonics could exist during a GIC event. These harmonics cause increased stray losses inside transformers and also wrong relay tripping in power generators and capacitance filter bank [1-5]. The study on the effects of GICs on power transformers and harmonics of magnetization current has been performed in previous works such as [6-7]. However, most of them were based on the lumped parameter model of transformers or case S. A. Mousavi is with Royal institute of technology, KTH, 144 Stockholm, Sweden (e-mail : seyedali@kth.se) C. Carrander is with Royal institute of technology, KTH, 144 Stockholm, Sweden (e-mail: claesca@kth.se). Paper submitted to the International Conference on Power Systems Transients (IPST213) in Vancouver, Canada July 18-2, 213. study investigation. Therefore, there is a lack of comprehensive study using an accurate model of a power transformer. In this paper, a three dimensional finite element model of a power transformer coupled with the external circuit is presented. The analysis type is the time-step transient. A script for 3D modeling of two, three and four-limb single-phase and three and five-limb three-phase power transformers have been written in the Vector Field 3D FEM package. The transformer model includes the core, windings and tank. Nonlinearity and anisotropy of the core material is considered and windings are coupled with external circuits. Then, the magnetization current is obtained by performing transient analysis. In the post processing stage, by applying FFT analysis on the waveform of the magnetization current, the harmonic components are acquired. The role of core type and GIC level on the waveform and the harmonic components of the magnetization current are investigated. These results could help designers of power transformers when they want to take into account the probability of GIC. Also, they could be employed to distinguish GIC from other transient phenomena in power networks in order to avoid misoperation of protection and control systems. II. FE MODELING AND CIRCUIT COUPLING A. Finite element modeling The finite element method is a powerful tool in order to solve electromagnetic problems. It is widely used for modeling and calculations regarding power transformers [8-9]. Generally, transformers have a complex three-dimensional geometry and consist of linear and nonlinear magnetic and electric materials. However, according to the aim of the modeling, some simplification is required. In this work a three-dimensional model is used for simulation of transformers with the aim of studying the effect of DC on the magnetization currents of power transformers. The different core types of core-form transformers: two-limb, three-limb, four-limb single-phase and three-limb and fivelimb three-phase are modeled. This allows investigation of the impact of core type on the magnetization current when the transformer is under DC magnetization. Due to symmetry the

computational load can be reduced to one eighth or one fourth of the geometry of single-phase and three-phase transformers respectively. Fig. 1 - Fig. 5 show the finite element model of the modeled transformers with symmetry. Fig. 5. Three-phase five-limb transformer model with 1/4 symmetry. Fig. 1. Single-phase two-limb transformer model with 1/8 symmetry. Fig. 2. Single-phase three-limb transformer model with 1/8 symmetry. The core material in this model is considered nonlinear and anisotropic. The relative permeabilities of oil and windings are set to one. The tank material is linear with relative permeability of 1. The conductivity of the tank is set to zero. The windings are modeled as stranded coils. This means that the current density distribution on cross section of the winding is assumed uniform. The program OPERA by Vector Fields [1] is employed for the modeling in this work, and all models are created by parametric scripts that allow changing the geometry and other parameters easily. B. Circuit coupling The connections of single-phase and three-phase transformers to external circuits are sketched in Fig. 6 and Fig. 7, respectively. Fig. 3. Single-phase four-limb transformer model with 1/8 symmetry. Fig. 6. External circuit coupled with a single-phase transformer Fig. 7. External circuit coupled with a three-phase transformer Fig. 4. Three-phase three-limb transformer model with 1/4 symmetry. It is assumed that the injected DC is the same in each phase of a three-phase transformer or bank of single-phases. This is

because the resistance determines the distribution of the DC current and we assume that the DC path is identical for each phase. Therefore, to study the effect of DC on no-load conditions of power transformers, the high voltage winding of each phase is connected to the DC current source and a resistor in series. The LV windings are connected to the voltage source. For three-phase transformers the connection type of the LV winding is a delta connection that is usual for step up transformers in power plants. C. Soft-start energization There is a transient phenomenon during the energization of RL circuits with an AC voltage [11]. This transient, which is damped through the resistance of the circuit, typically takes several cycles to decay. Therefore, in time-dependent finite element analyses it wastes a lot of time and computational effort to reach the steady state condition that is in the field of interest. In this work a soft-start energization is developed for omission of this transient. The soft-start process takes less than a quarter of a cycle and after that the real voltages are applied. The idea of soft-start process is to provide the linkage flux in each phase as the same as the steady state linkage flux corresponding to the applied phase voltage at the first moment, V start. The relation between the linkage flux and the induction voltage is determined by Faraday s law: () t Vtdt () (1) In power system under steady state condition the linkage flux of each limb crosses zero at the turning point (maximum or minimum) of the phase induction voltage and according to this reference point, the linkage flux corresponding with V start, ψ start, is calculated by using (1): Vmax Vstart 2 1 ( ) (2) start 2 f Vmax, where V max and f are the maximum and frequency of the sinusoidal induction voltage, respectively. β determines the sign of ψ start. It can accept the value of +1 or -1 depends on the angle of the induction voltage at the first moment. If the induction voltage increases after V start, it is -1. Otherwise it will be +1. Therefore, the linear applied voltage to the windings during soft-start energization to reach the value of ψ start could be: Vmax Vstart t Vt () ( 1 ( ) 2.5 tv s start) 2 f V T max start, where T start and t s are the duration of the soft-start period, and time step of the simulation, respectively. Fig. 7 and Fig. 8 show the magnetization currents of a three-phase transformer with the soft-start energization method and corresponding applied voltages, respectively. (3) Current (A).25.2.15.1.5 -.5 -.1 -.15 -.2 Soft-Start Ts -.25 5 1 15 2 25 3 Fig. 8. Magnetization currents of a three-phase transformer with the softstart energization. Voltage (kv) 1 8 6 4 2-2 -4-6 -8-1 5 1 15 2 25 3 Fig. 9. Applied voltages with soft-start energization. III. RESULTS AND DISCUSSION Saturation of a transformer core in one of the half cycles causes a very asymmetric magnetization current which contains both odd and even harmonics. These higher harmonics increase winding losses and stray losses in the metallic parts of the transformer. Furthermore, they can be important for the network and for protection relays. In this study the effect of core design on the created harmonics is investigated. The simulations have been performed for all mentioned types of power transformers. The generator step up transformer is studied in this work. The magnetization current has been obtained for several levels of GIC and applied voltage. The Fast Fourier Transform (FFT) has been employed for finding the frequency spectrum of the magnetization current waveforms. The simulation results demonstrate that single-phase transformers are very sensitive to GICs. The various core types: two-limb, three-limb and four-limb, show similar behavior. The reason is that the DC current can easily saturate

the core in single-phase transformers. In contrast, a threephase three-limb transformer is very resistant against GICs. This is because of the structure of the core. The DC currents compensate each other in the main limbs and connecting yokes. As a result the core doesn t saturate easily and consequently it is not so affected by GICs. Nevertheless, three-phase five-limb transformers behave more similarly to single-phase transformers. Although DC currents compensate their effects of each other in the main limbs and their connecting yokes, they enhance each other to saturate the return limbs. A. Single-phase transformers The results of the simulations showed that single-phase power transformers have similar behavior regarding the magnetization current. For instance, the magnetization currents for a single-phase two-limb transformer without GIC, with GIC current near 5% and 1% of the maximum normal magnetization current are shown in Fig. 1 - Fig. 12, respectively. Also, Fig. 13 - Fig. 15 demonstrate the corresponding frequency spectrums. The amplitude of each harmonic is normalized to the peak value of the magnetization current waveform. Analysis of the results shows that under normal AC magnetization, the first, third and fifth harmonics are dominant. However, in the presence of GIC, the second and fourth harmonics are enhanced. And, as was expected, the waveform contains a considerable DC component as well. The amplitude of the main harmonic can reach 3-4 % of the maximum magnetization current, which can reach nominal load current and even more, in turn. It means that the winding at least should endure 3-4% overload during the GIC. Current (A).1.8.6.4.2 -.2 -.4 -.6 -.8.35.3.25.2.15.1.5 -.5 -.1 1 2 3 4 5 6 7 8 9 1 Fig. 11. Magnetization current of a single-phase two-limb transformer with GIC near 5% of maximum normal magnetization current. 8 7 6 5 4 3 2 1-1 1 2 3 4 5 6 7 8 9 1 Fig. 12. Magnetization current of a single-phase two-limb transformer with GIC near 1% of maximum normal magnetization current..8.7.6.5.4.3 -.1 1 2 3 4 5 6 7 8 9 1 Time (ms).2 Fig. 1. Magnetization current of a single-phase two-limb transformer without GIC..1 2 4 6 8 1 12 Fig. 13. Spectrum of a single-phase two-limb transformer without GIC.

.35.3.1.25.2.15.1 Curent(A).8.6.4.2 -.2.5 -.4 2 4 6 8 1 12 -.6 -.8 Fig. 14. Spectrum current of a single-phase two-limb transformer with GIC near 5% of maximum normal magnetization current. -.1 1 2 3 4 5 6 7 8 9 1 Fig. 16. Magnetization currents of three-phase three-limb transformer without GIC..45.4.35.3.25.2.15.1.5 2 4 6 8 1 12 Fig. 15. Spectrum current of a single-phase two-limbs transformer with GIC near 1% of maximum normal magnetization current. B. Three-phase transformers As was expected, the behavior of three-phase three-limb transformers is different from three-phase five-limb transformers. Though five-limb transformers function similarly to single-phase transformers regarding GIC, the magnetization current shows a small difference. The magnetization currents and the frequency spectrum of one of the phases under normal condition without GIC for a three-limb transformer are shown in Fig. 16 and Fig. 17, respectively. The magnetization current of this type of transformer does not show considerable change for low GIC levels. Fig. 18 and Fig. 19 show the magnetization currents and frequency spectrum, respectively, in the case of a high GIC level that is near 1 times the maximum of normal magnetization. It is obvious that GICs have no significant impact on the amplitude of the magnetization current. Although the even harmonics increase, they still are relatively small. Although this type of transformer seems better for networks, due to higher leakage fluxes it could be more dangerous for transformer itself. Also, any unbalance in DC current distribution between phases could lead to saturation of the core..9.8.7.6.5.4.3.2.1 2 4 6 8 1 12 Fig. 17. Spectrum of a three-phase three-limb transformer without GIC.

.1.2.8.15.1.5 -.5 -.1 1 2 3 4 5 6 7 8 9 1 Fig. 18. Magnetization currents of a three-phase three-limbs transformer with a high GIC level..6.4.2 -.2 -.4 -.6 -.8 -.1 1 2 3 4 5 6 7 8 9 1 Fig. 2. Magnetization currents of a three-phase five-limb transformer without GIC..7.9.6.5.4.3.2.1.8.7.6.5.4.3.2.1 2 4 6 8 1 12 2 4 6 8 1 12 Fig. 19. Spectrum of a three-phase three-limb transformer with a high GIC level. The magnetization currents of a five-limb transformer and the corresponding frequency spectrum are illustrated in Fig. 2 - Fig. 21 respectively. Comparison with Fig. 16 reveals that unlike the three-limb transformer the magnetization currents in each phase of the five-limb transformer have the same magnitude. Fig. 22 and Fig. 23 show the magnetization currents and frequency spectrum with GIC near half of the maximum normal magnetization current. It shows that the GIC can affect the magnetization current of a fivelimb transformer the same way as a single-phase one, but more intensely. Also, the fifth and fourth harmonics are larger than the third one. Fig. 21. Spectrum of a three-phase five-limb transformer without GIC. 16 14 12 1 8 6 4 2-2 1 2 3 4 5 6 7 8 9 1 Fig. 22. Magnetization currents of a three-phase five-limb transformer with GIC near 5% of maximum normal magnetization current.

.35.3.25.2.15.1.5 2 4 6 8 1 12 14 16 Fig. 23. Spectrum of a three-phase five-limb transformer with GIC near 5% of maximum normal magnetization current. IV. CONCLUSION The investigation of the effect of GIC on the magnetization current of power transformers has been done by using a three dimensional finite element model. This model can consider the geometry of transformers, saturation and leakage flux paths more realistically than transformer models that are used in power system analysis software. The aim of the study was the analysis of harmonic components that are generated by the asymmetric, high amplitude magnetization current caused by saturation of the transformer s core during a GIC event. Also, different types of core-form transformers are modeled to have comparison between them. The obtained results shows that in all types of single-phase transformers and also in five-limb three-phase transformers, even low level GICs can lead to half-cycle saturation of the core. This causes injection of both odd and even harmonics with considerable amplitude into the network, creating hotspots inside transformers and misoperation of protective relays. However, in three-phase three-limb transformers GIC hardly can saturate the core, since the injected DC currents in the limbs mostly compensate each other. As a result, even during high level GICs the magnetization currents of this type of transformers are not affected considerably. Although this type of transformer seems better for networks, due to higher leakage fluxes it could be more dangerous for transformer itself. Also, any unbalance in DC current distribution between phases could lead to saturation of the core. This work can help to improve the protection system of power networks and transformers. Also, it can give a guide to choose of power transformers where is subjected to GIC. V. REFERENCES [1] P. Price, Geomagnetically induced current effects on transformers, IEEE Trans. Power Delivery, vol. 17, no. 4, pp. 12-18, 22. [2] H. C. Tay and G. W. Swift, On the problem of transformer overheating due to geomagnetically induced currents, IEEE Trans. Power Apparatus and Systems, vol. PAS-14, no. 1, pp. 212-219, January 1985. [3] I. T. a. D. Committee, Geomagnetic disturbance effects on power systems, IEEE Trans. Power Delivery, vol. 8, no. 3, pp. 126-1216, 1993. [4] R. Pirjola, Geomagnetically induced currents during magnetic storms, IEEE Trans. Plasma Science, vol. 28, no. 6, pp. 1867-1873, 2. [5] S. A. Mousavi, Electromagnetic Modelling of Power Transformers with DC Magnetization, Licentiate Thesis, Stockholm, Sweden, 212. [6] Z. Xiaojun, Analysis of the DC Bias Phenomenon by the Harmonic Balance Finite-Element Method, IEEE Trans. Power Delivery, vol. 26, no. 1, pp. 475-485, Jan 211. [7] Harmonic generated from DC bias transformers, IEEE Trans. Power Delivery, vol. 8, no. 2, pp. 725-731, April 1993. [8] J. P. Av. Bastos and S. N., Electromagnetic Modeling by Finite Element Methods, NewYork. Basel: Marcel. Dekker, Inc., 23. [9] G. Loizos, T. Kefalas, A. Kladas and A. Souflaris, Flux Distribution Analysis in Three-Phase Si-Fe Wound Transformer Cores, Magnetics, IEEE Transactions on, vol. 46, no. 2, pp. 594-597, 21. [1] OPERA-3D User Guid, England, Vectorfield limited, 23. [11] J. A. Martinez-Velasco, Power System Transients: Parameter Determination, Taylor & Francis, 29.