Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed

Similar documents
MODELING THE ELECTROMAGNETIC POLLUTION OF THE ELECTRIC ARC FURNACES

ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK

Functioning Analysis of a High Frequency Electro Thermal Installation with Electromagnetic Induction Using PSCAD-EMTDC Tool

MEASUREMENT OF THE PARAMETERS FOR ELECTRIC ENERGY QUALITY. (1) Gabriel VLADUT, (2) Petre-Marian NICOLAE

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Study of the deforming regime introduced in the power supply grid by the electric locomotives equipped with DC motors

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

Harmonics Elimination Using Shunt Active Filter

Researches Regarding the Pollution with Harmonics by the Frequency Converters

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

II. RESEARCH METHODOLOGY

HARMONIC contamination, due to the increment of nonlinear

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

SYSTEM OF CONTROLLING THE PROCESS OF STEEL ELABORATION IN DC ELECTRIC ARC FURNACES

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

p. 1 p. 6 p. 22 p. 46 p. 58

Current Transformers and the Accuracy of Electrical Powers and Energies Measurements

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction

System and equipment for measurement, registration of parameters and analyse of the quality of the electric energy

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

About the High-Frequency Interferences produced in Systems including PWM and AC Motors

Design and Simulation of Passive Filter

ISSN Vol.07,Issue.21, December-2015, Pages:

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Literature Review for Shunt Active Power Filters

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK

ASPECTS OF REAL-TIME DIGITAL SIMULATIONS OF ELECTRICAL NETWORKS

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

22.0 Harmonics in Industrial Power Systems

Power Quality Improvement in Distribution System Using D-STATCOM

ISSN Vol.03,Issue.07, August-2015, Pages:

Improving Passive Filter Compensation Performance With Active Techniques

Improvement of Power Quality Using a Hybrid Interline UPQC

Power Quality improvement of a three phase four wire system using UPQC

Power Quality Improvement using Active shunt Power filter using PI Controller

Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

FACULTATEA DE INGINERIE ELECTRICĂ. Ing. Lucian Diodiu. PHD Thesis ABSTRACT

Study for the electric arc of alternative current at the single phase welding machine using the Matlab/Simulink environment

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Exercises on overhead power lines (and underground cables)

HARMONIC DISTURBANCE COMPENSATING AND MONITORING IN ELECTRIC TRACTION SYSTEM

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Introduction to Rectifiers and their Performance Parameters

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system

Harmonic Analysis of a High Speed Automatic Reclosing on a 400 kv Overhead Transmission Line

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Modeling and simulation of a single phase photovoltaic inverter and investigation of switching strategies for harmonic minimization

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

shunt (parallel series

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Volume I Issue VI 2012 September-2012 ISSN

Experiment 2: Transients and Oscillations in RLC Circuits

Chapter 11. Alternating Current

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Long lasting transients in power filter circuits

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

A NEW DESIGN METHOD OF OUTPUT FILTER FOR SPACE VECTOR PWM FED INDUCTION MOTOR

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

Power Quality enhancement of a distribution line with DSTATCOM

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Power Quality Analysis in Power System with Non Linear Load

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Experimental Value of Network Harmonic Impedance

Energetic Analysis of the Drying Process of Current Transformers from 110 kv Ciungetu Power Station

Resonant wireless power transfer

Design and Analysis of Resonant Harmonic Filter

Resonances in Collection Grids of Offshore Wind Farms

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Generator Power [kw]

Indirect Current Control of LCL Based Shunt Active Power Filter

Design of a Cell Charger for an ipad Using Full Bridge Rectifier and Flyback Converter

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Investigation of D-Statcom Operation in Electric Distribution System

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Study about the possibility of flicker effect simulation caused by nonlinear power loads

Comparative Analysis of Multiple-pulse VSC-Based STATCOM s for Voltage-Dip Mitigation

SEVERAL static compensators (STATCOM s) based on

Figure 1: Closed Loop System

N100. example of application Ethernet www/ ftp. Ethernet TCP IP RS X MeaSUreMent of power network parameters.

FREQUENCY RESPONSE OF R, L AND C ELEMENTS

Transcription:

Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 69 Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed IOAN BACIU, CAIUS PANOIU, MANUELA PANOIU, CORINA CUNTAN Electrical Engineering and Computer Science Department Polytechnic University of Timisoara Revolutiei str. no 5, code 33117 ROMANIA {ioan.baciu, c.panoiu, m.panhttp://fih.upt.ro/op/electro_comp.html Abstract: - With the progress of power electronic devices in electric railway, harmonics in power systems become increasingly of concern. This paper presents a case study on harmonics in a traction power supply system. The study was based on measurements realized in an electrical drive station using a data acquisition system and a computer. It was analyzed the main power quality indicators: the power factor, the reactive power factor, the deforming power factor and the total harmonic distortion of the current and voltage. The paper present also the simulation results of process of electric drive vehicles especially in railway using different passive LC filters using PSCAD-EMTDC simulation program. Key-Words: - harmonics filtering, railway, power quality, PSCAD EMTDC simulation program 1 Introduction Nowadays the electric power is used in many real applications. Thus, it must taing account of the power quality with protection of environment. The exigencies that must by observed for the power distribution systems pertain to the power supplying continuity and power quality, and lead to a detailed analysis of the electric power parameters. The quality of electric power a requirement of the power supply must be analyzed in correlation with the distortions of the consumer s receivers, which are introduced in the electric supplying networ. If the power supplying parameters are not within the standard limits, the life span of the electrical equipments decreases. On the other hand the equipment has to be over dimensioned, in order to cope with these situations. The quality of the electric power, an important component of the electroenergetic system, is a concern of the producer and also of the consumer. The concern of the electric power producer is the distribution and transportation electric networ, which must wor within certain parameters. On the other hand the consumer is interested in an appropriate electric power quality, but, in the same time, he is involved in this quality preservation. On the output generators, electric voltage is practically sinusoidal, but, at the consumer, it is more or less disturbed. For study the possibility to improve the power quality it was use the simulation program PSCAD EMTDC. PSCAD (Power System Computer Aided Design) is a multi-purpose graphical user interface capable of supporting a variety of power system simulation programs. This release supports only EMTDC (Electro-Magnetic Transients in DC Systems). The main power quality indicators The criteria of quantitative analysis of power quality are [1], [3], [4], [5]: The power factor P P = = P S P + Q D (1) The reactive power factor Q ρ = = tgϕ P () The deforming power factor σ = D = tgξ (3) P + Q where P is active power, S is apparent power Q is reactive power and D is deforming power. The total harmonic distorsion for current, I THDI I = 1 1 [%], (4) respectively for voltage, U THDU 1 [%] (5) = U1 The pondered partial total harmonic distortion for current,

Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 7 I THDI P I = 1 1 [%], (6) respectively for voltage, U THDU P 1 [%] (7) = U1 where U 1, I 1 are the rms values for voltage and current on the fundamental and U, I the effective values for voltage and current on the th harmonic order. 3. Results obtained by measurement in electrical station For the nonsinusoidal operating identify we are performed some measurement on the railway electrical station in Romania, and we are determine the distortions level for the current and voltage. The measure data are store in a PC, and there are ulterior processes. The data were input to a computer in order to be processed at a later stage. The modern methods of measuring electric magnitudes use numeric systems based on systems of data acquisition and the method we introduced in this paper uses such a system. We used a computer with an ADA 31 acquisition board [9] to which we connected an adapting bloc for the high currents and voltages. The role of this bloc is to achieve the compatibility of the magnitudes to be measured with the measuring range of the data system, as well as to lead to a galvanic isolation between the force circuit and the data acquisition system. The adapting bloc allows the simultaneous acquisition of three currents and three voltages. In order to obtain an analysis of the variation of electrical magnitudes along a hour, the data acquisition has been carried out along this hour. This process shows a set of specific characteristics, depend on both the nature of the electric magnitudes to be measured and on the technical characteristics of the data acquisition system in use and the computer on which the programs run. Taing into account both the characteristics we have shown and the recommendations concerning data acquisition in the systems of measuring currents and voltages on medium and high voltage lines given in [4], [5] the -channel data acquisition has been done as follows: - during 5 ms we sampled data simultaneously on channels, the acquisition frequency being 5 KHz. In this way was sampled the signals along 1.5 time periods. This thing allows that in case of a different frequency value from 5 Hz, the sampled data containing a 1 full period of signals. - the 5 ms acquisition process was resumed at an interval of 9.75 seconds, interval along which we saved in the memory the data previously acquired. Thus, it results that along the entire duration of the charge we sampled data in time windows of 5 ms each, the interval between two windows of consecutive data being 1 seconds. From the set of data acquisition we select a window, which we considered representative, and we analyze this window. The current and voltage waveforms on the low voltage feeding line are present in figure 1. One can notice their strong distortion. Current (A) - 5 1 15 5 3 35 45 5 Time (ms) 5 Voltage (V) - -5 5 1 15 5 3 35 45 5 Time (ms) Fig. 1. The current and voltage waveforms on the low voltage feeding line The spectral characteristics are obtained by data acquisition processing, using the Fourier transform. Because the acquisition frequency was 5 KHz, the spectral analyzed frequency band are,5 KHz, which, divide by 15 samples from data window leads to Hz frequency step. Because, lie is present in the reference literature [5], the analyze of the first harmonics values, the power, power factors and distortions coefficients determination was made based on the harmonics values, but for a good clarity the graphics was represent by 1 Hz, according with the first harmonics values. The spectral charactersitic for the current and voltage are present in figure. By analyzing both, the variation of the current and voltage and the spectral characteristics one can observe that the higher deformation is on the current. However, the voltage is also deformed, but it preserves an approaching sinusoidal shape. One can also observe, on the spectral characteristic for the current and voltage that the odd order harmonics are higher

Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 71 comparative with the non-odd order harmonics. It can be observed that the 13 th order harmonic is the biggest, and after that the values are decreasing strongly. Current (A) Voltage (V) 1 8 6 1 3 5 6 7 8 9 1 Frequency (Hz) 5 3 1 1 3 5 6 7 8 9 1 Frequency (Hz) Fig.. The harmonics of the current and voltage Regarding the values of the active, reactive and distortion power, the values of the power factor and the reactive factor are present in table 1. We also gave in table 1, the values for the distortion coefficients. Table 1 The apparent power 3.4351 MVA The active power 1.837 MW The reactive power.18 MVAR The distortion power.9157 MVAD The power factor.558 The reactive factor.11798 The distortion factor 1.654 THDI 143.99% THDPI 54.% THDU 8.4473% THDPU 7.4% It can be observed from these data that the reactive power is greater than the active power, therefore active power compensation is necessary. The distortion of the current and voltage are also obvious by analyzing the value of the distortion power that is very significant. 4. Simulation results In this section will be present the filters effects for the 3, 5, 7, 9, 11, 13, 15, 17 and 19 harmonics. For this analyze we use the acquisition dates and introduced them to the input of filters. This result was obtained by using the simulation program PSCAD-EMTDC. For this aims it was present the current and voltage variation before and after filtering. The most frequently used solution (for the technical-economical reasons) is harmonics filters, which are, in fact, serial resonant LC circuits. In this paper the simplest type of such a filter was analyze. This type of filter is made by a single serial inductivity with a capacitor, named first order passed band filter (fig.3). C L FTB1 Distorted consumer Fig. 3. The electrical scheme for a first order pass-band filter. For each harmonic current it is use such a circuit. The components for each circuit are dimensioned so that for the resonance frequency, which are equal with the harmonic frequency, result null impedance: 1 Z = ω1l (8) ω1c where Z are resonant circuit equivalent impedance for the -order harmonic (equivalent resistances for the impedance, capacitors and electric cables are neglected) and ω 1 is fundamental current pulsation. Pulsation: ω = ω 1 1 = LC (9) represent the resonant pulsation for the LC circuit. It can be observed that for smallest values for the pulsation vis a vis resonant pulsation ω<ω, Z <, therefore the character is capacitive, and for greatest values for the pulsation vis a vis resonant pulsation the character is inductive. Usualy, the absorbing filters are installed for the harmonics with the highest amplitudes. Establishing of filters' inductivity and capacity values is made by applying of some algorithms that could be differentiated first depending on the filters' role from the viewpoint of reactive power compensation on the fundamental. All the resonant circuits will have capacitive character on the fundamental's frequency, so they will produce, no matter what, a capacitive transversal compensation of the networ. Even though this rare solution, it could be taen into account in boundary situations when the distorted

Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 7 regime in current is very pronounced. Even the reactive power compensation is not aimed either, the filter will flow in the networ reactive power on fundamental. Therefore, the filter's dimensioning criteria, more specifically of the capacity, is to minimize the installed capacitive reactive power (which, beside a minimum cost of the battery, leads to a minimum influence on the active power circulation in the networ). This reactive power will have two components corresponding to the two above mentioned currents, the current corresponding to the fundamental and the current corresponding to harmonic on which the resonance is taing place: I Qc = Qc1 + Qc = Uc ω 1 C + (1) ω1 C where: Q c1 is reactive power supplied by the filter's capacitor on fundamental; Q c is reactive power supplied by the filter's capacitor on harmonic; U c is voltage at the capacitor's terminals; I is harmonic current that follows to be filtered. Considering the partial derivate depending on capacity of the installed capacitive reactive power equation and canceling it, we obtain the equation of the filter's capacitor capacity: 1 I ( 1) C = (11) U1 ω1 The L filter's inductivity is determined from the resonance condition of the filter's LC serial circuit: 1 1 L = = (1) ω C ω1 C By introducing of such resonant filters on the odd harmonic frequencies, we can see the influence on each filter in part, as well as the effect of more filters connected in parallel. Is aimed also, beside the amplitude value, also the phase-difference introduced by each harmonic against the fundamental. The PSCAD EMTDC simulation scheme is show in fig. 4..1 [ohm] Ian Ea 1.5 [uf].7557 [H] 1. [uf].584 [H].6777 [H] 1. [uf].1587 [H] 1. [uf] 1. [uf].83736 [H].59953 [H] 1. [uf] 1. [uf].453 [H].3559 [H] 1. [uf] Ia 1. [ohm] Ia F F T F = 5. [Hz] Mag (31) Ph (31) dc 1 3 5 7 9 11 13 15 F8 F7a F6a a15 a13 a11 F5a a9 F1a a1 Fa a3 F4a a7 F3a a5 1 3 5 7 9 11 13 15 f15 f13 f11 f7 f9 f5 f1 f3 Fig. 4. The PSCAD EMTDC simulation scheme

Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 73 The waveforms and instrumentation corresponding to the harmonics and phase-differences are show, on a graphic corresponding to a single filter (fig. 5) and on a graphic corresponding to more filters (fig. 6). The analysis is made for each filter in part, the results being listed in table, as well as for an increasing number of filters, depending on the harmonic's order, of which results are in table 3. Table amplitude phase 3 18.73 171.1 5 11.56 157.4 7 11.3 118.1 9 11.19 48.54 11 11.15-59.98 13 11.13 144.6 15 1.78-64.9 Table 3 Ampl Numbers of filters [A] 1 3 4 5 6 7 Fig. 5 The waveforms, the harmonics amplitudes and phases for a single filter a 3 18.73 18.7 18.7 18.77 18.73 18.78 18.66 a 5 11.56 11.55 11.58 11.57 11.58 11.49 a 7 11.34 11.31 11.36 11.3 11.36 a 9 11.18 11.8 11. 11.43 a 11 11.9 11.9 11.1 a 13 1.99 11.6 a 15 11.6 Phase f 3 17.1 175.1 175. 175. 175.1 175.3 175.1 f 5 157.4 157.5 157.7 157.4 157.6 157 f 7 118. 118.6 118.4 118.6 117.8 f 9 48.8 49.6 49. 49.1 f 11-59.8-59.8-58.6 f 13 144.6 14.3 f 15-66.1 Fig. 6 The waveforms, the harmonics amplitudes and phases for multiples filters 5. Conclusions From the obtained data analysis, we can find the effect of each filter, both as harmonic's value and phase-difference on each frequency. From table 3 results that for a greater number of filters the effects are smaller and smaller, reason for which is not used a quite great number of passive filters for harmonics compensation. To attenuate the superior ran harmonics, which have more reduced values, usually are used power active filters, the general compensation being made by combining the two types of filters, passive and active. The number of passive filters utilized is determined depending on the consumer power, on its characteristics, on the electric power's quality requirements, as well as on the system's economical efficiency.

Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 74 References: [1] Ionescu T., Pop O., The power delivery engineering systems, Technical publ, Bucureşti, 1998. [] Chiuţă I., Conecini I., The compensation of the distorted functioning regime, Technical publ, Bucureşti, 1989 [3] Harmonics Woring Group IEEE PES T&D Committee, Modeling of components with nonlinear voltage current characteristics for harmonic studies, Power Engineering Society General Meeting, IEEE, 4, vol. 1., pp 769-77 [4] IEEE Woring Group on nonsinusoidal situation, Practical definitions for powers in systems with nonsinusoidal waveforms and unbalanced loads, IEEE Transactions on Power Delivery, vol. 11, 1998, pg. 79-87. [5] IEC 61-4-7 Ed. : Electromagnetic compatibility (EMC) Part 4-7: Testing and measurement techniques General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto,. [6] Buta, A., Pană, A., Ivaşcu, C., reactive power compensation criteria in unbalanced electrical networs, Energetica, vol. 45, 1997, pp. 89-94. [7] Buta A.,Pană A., Load balancing on the distribution electrical networs, Editura Orizonturi Universitare, Timişoara, ; [8] Zanotto, L.; Piovan, R.; Toigo, V.; Gaio, E.; Bordignon, P.; Consani, T.; Fracchia, M, Filter design for harmonic reduction in high-voltage booster for railway applications. Power Delivery, IEEE Transactions on Volume, Issue 1, Jan. 5, pp. 58 63 [9] ***, ADA 31/ ADA31A, User s Manual, Real Time Devices Inc., USA 1991.