Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

Similar documents
SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

SECTION PANELBOARDS

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

B. Manufacturers: Square-D, G.E. or Westinghosue.

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION POWER SYSTEMS STUDIES

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

DESIGN CHECKLIST INTRODUCTION

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

First Draft Language

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Arc Flash Analysis Training

3Ø Short-Circuit Calculations

Arc Flash Analysis and Documentation SOP

Cause, Effect & Mitigation Strategies

Grounding Recommendations for On Site Power Systems

MV network design & devices selection EXERCISE BOOK

Arc Flash Calculation Methods

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

Short Circuit Current Calculations

Quality Control Checklist - Design Drawings

POWER SERVICE DETAILS

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motor Transformers and Distribution Systems

Electrical Arc Hazards

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

Electrical Wiring: Commercial, Seventh Canadian Edition

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

ARC FLASH HAZARD ANALYSIS AND MITIGATION

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

ARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

SUBMITTAL TRANSMITTAL OCPS CLAY SPRINGS ES REVIEWED SUBMITTAL NUMBER: SUBMITTAL DETAILS: CONTRACTOR/CM:

Power System Study for the Pebble #2 Lift Station Las Vegas, Nevada

ET 51 - Electrician Theory Examination Marking Schedule

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

NOTICE ER Roland Flood Pumping Station Arc Flash Study

STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

03/7/12 Issuance UTD Section Page 1 of 5 Electrical General

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

TABLE OF CONTENT

DESIGN STANDARD DS 29

Upgrading Your Electrical Distribution System To Resistance Grounding

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

Paul Dobrowsky Innovative Technology Services

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Copper Core & Coil Transformer

S11 Adjustable Speed Drive Engineering Specification

SECTION DISTRIBUTION SWITCHBOARDS

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

NORTHWEST FLORIDA STATE COLLEGE MONUMENT SIGNS WITH LED DISPLAYS

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

SECTION DISTRIBUTION SWITCHBOARDS

Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity

Electrical Measurement Safety. Sponsored By:

ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Electrical/Telecommunications Design

2. Electrical rooms shall be centrally located and stacked so that feeder conduits and bus duct are run as straight and short as possible.

2014 NEC Changes Part 1

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Electrical Overcurrent Studies

Guide to Low Voltage System Design and Selectivity

BAPTIST HOSPITAL BEAUMONT 3080 College Street

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Technical T TECHNICAL. C o n t e n t s SPEEDFAX TM 2017

Note: The let-through of the protective device must be equal to or less than the short-circuit current rating of the component being protected.

ELPT 1429 RESIDENTIAL WIRING

Effective System Grounding

Presents. Harmonics Years

Technical Assignment #2 Electrical Existing Conditions Report

4. Special Systems Design: including Fire Alarm and Security. C. Electrical and Telecommunications Ductbanks: Refer to Section 16118

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

Short-Circuit Current Calculations

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

Distribution System Development & Preliminary Studies

{40C54206-A3BA D8-8D8CF }

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Submittal Transmittal

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Steve Kovach District Sales Engineer

Transcription:

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Adam T. Powell, PE President Emerald Engineering, Inc. Jeffrey L. Small, Sr. Senior Specification Engineer GE Industrial Solutions October 12, 215

Quick Rundown: Selective Coordination: The Basics Arc Flash: The Basics Coordination vs. Arc Flash Who Wins & Why? Opportunities for Compromise System Growth Over Time What Can We Do? Equipment Selections & Specs Selectivity & Equipment Limitations Design Rules of Thumb Simple System Examples Things to Remember A Vendor s Perspective Frequent Oversights & Considerations

Selective Coordination: The Basics Concepts Regions of the Curve / LSI Thermal Magnetic LV Fuses Generators GFI Transformers Motors

Example #1: Basic Concepts

Example #2: Curve Regions / LSI

Example #3: Thermal Magnetics

Example #4: LV Fuses

Example #5: Simple Genset

Example #6: Ground-Fault

Example #7: Dry-Type Transformer

Example #8: Motors

Arc Flash: The Basics Concepts Personal Protective Equipment (PPE) NFPA 7E Incident Energy Mitigation Methods

Arc Flash: The Basics An Arc Flash occurs during a fault, or short circuit condition, which passes through this arc gap. The Arc Flash can be initiated through accidental contact, equipment which is underrated for the available short circuit current, contamination or tracking over insulated surfaces, deterioration or corrosion of equipment and, or parts, as well as other causes. An Arc Flash event can expel large amounts of deadly energy. The arc causes an ionization of the air, and arc flash temperatures can reach as high as 35, degrees Fahrenheit. This is hotter than the surface of the sun. -GE Industrial Solutions

Before:

After:

Example #9: Simple 1-Line

Personal Protective Equipment (PPE)

Incident Energy Incident Energy measured on a surface at a specified working distance from the arc flash location Measured in cal/cm 2 Factors include: Available Fault Current System Impedance Protective Device Settings & Clearing Times

Coordination vs. Arc Flash: Who Wins, and Why? Selective Coordination Often Comes at the Expense of Arc Flash Hazard. Short Time, Short Time Delay, and Instantaneous Settings Drastically Impact Incident Energies at the Buss(es) Downstream of the Protective Device. Tendency to Set Breakers to Max in Healthcare Applications As long as it coordinates Limiting the Impact of a Fault and Clearing it are Priority What are the Implications? Is there a Middle Ground? Revisiting Example #9

Example #9: Simple 1-Line

Example #9 Labels

Example #1: Revised Settings

Example #1 Labels

System Growth Over Time What Can We Do? System Sprawl What can Design Professionals do to Limit the Cost, Safety, and Reliability Impact of Future Renovations? Gear Provisions that Make Sense Specify Exactly What You Want Leave Room to Coordinate Design Rules of Thumb for LSI & Thermal Mag Leave Room to Limit Arc Flash Hazard

Gear Provisions that Make Sense Subfeed Lugs Front-Hinged Door Adequate Lug Sizes Inadequate Lug Sizes Frequently don t Present Until Submittals or Later Often too Late Contractors: Make the Vendor Own the 1- Line in Addition to the Panel Schedules and Specs. Sufficient Prepared Space for Future

Specify Exactly What You Want Gear Type: Switchgear Switchboard Distribution Panelboard Lighting/Appliance Panelboard Breaker Types LI/LSI/LSIG Thermal Mags Specific Types Coordination Study on the Documents

Panel Schedule #1: "N3L" 12/28V. 3PH, 4W 6A MLO NEMA-1 22, AIC COPPER BUS MFR: GE VOLTAGE/PHASE 6A BUS SURFACE FULLY RATED SOLID NEUTRAL CKT AMPS POLE DESCRIPTION NOTES LOAD VA CKT AMPS POLE DESCRIPTION NOTES 1 84 2 84 3 1 3 PANEL N3L1 84 4 1 3 PANEL N3L3 84 5 84 6 84 7 114 8 42 9 15 3 PANEL N3L2 114 1 6 3 PANEL N3L4 42 11 114 12 42 13 14 2 15 SPACE 16 2 3 CHILLER MRI 2 17 18 2 19 2 21 SPACE 22 SPACE 23 24 25 26 27 SPACE 28 SPACE 29 3 31 32 33 SPACE 34 SPACE 35 36 37 38 39 SPACE 4 SPACE 41 42 LOAD CONNECTED DEMAND DEMAND NOTES: DESCRIPTION LOAD (VA) FACTOR LOAD (VA) 1. LIGHTING 288 1.25 36 2. HVAC - COOL 3. 3. HVAC - HEAT 3 1. 3 4. RECEPTACLE 54.6 32 5. MISC 18 1. 18 6. TOTAL 132 872 7. TOTAL DEMAND CURRENT @12/28V, 3PH 242.AMPS LOAD VA

Panel Schedule #2: "N3L" 12/28V. 3PH, 4W 6A MLO NEMA-1 22, AIC COPPER BUS SOLID NEUTRAL GE: SBO VOLTAGE/PHASE 6A BUS SURFACE FULLY RATED HINGED DOOR CKT AMPS POLE DESCRIPTION NOTES LOAD VA CKT AMPS POLE DESCRIPTION NOTES LOAD VA 1 1 3 PANEL N3L1 SEHA 84 84 84 2 1 3 PANEL N3L3 SEHA 84 84 84 3 15 3 PANEL N3L2 SEHA 114 42 114 4 6 3 PANEL N3L4 SEHA 42 114 42 5 25 3 SPACE 2 6 2 3 CHILLER MRI SEHA 2 2 7 25 3 SPACE 8 25 3 SPACE 9 25 3 SPACE 1 25 3 SPACE 11 25 3 SPACE 12 25 3 SPACE 13 25 3 SPACE 14 25 3 SPACE SUB FEED 6 3 LUGS LOAD CONNECTED DEMAND DEMAND NOTES: DESCRIPTION LOAD (VA) FACTOR LOAD (VA) 1. LIGHTING 288 1.25 36 2. HVAC - COOL 3. 3. HVAC - HEAT 3 1. 3 4. RECEPTACLE 54.6 32 5. MISC 18 1. 18 6. TOTAL 132 872 7. TOTAL DEMAND CURRENT @12/28V, 3PH 242.AMPS

Leave Room in the System to Coordinate - Now and in the Future LSI : LSI 1.5 : 1 ratio Upstream : Downstream LSI : Thermal Magnetic 2 : 1 ratio Upstream : Downstream Thermal Magnetic : LSI 2 : 1 ratio Upstream : Downstream Thermal Magnetic : Thermal Magnetic (Distribution Panelboards) 2 : 1 ratio Upstream : Downstream Thermal Magnetic : Thermal Magnetic (Branch Panelboards) 5 : 1 ratio Upstream : Downstream

Leave Room in the System to Coordinate - Now and in the Future 15kVA Dry-Type Transformers Sometimes Useful but Items to Consider: 6A Secondary MCB Panelboard will have 1A or 125A Buss Cost Difference with 3kVA is Negligible Primary and Secondary Conductors have Negligible Cost Difference with 3kVA Primary & Secondary Most Manufacturers can Coordinate, but Limits Branch Breaker Sizes to Almost Exclusively 2A Plan on Dry-Types 45kVA or Less Being Last Level No Feeder Breakers Downstream

Simple System Examples

Simple System Examples

Example: LNA1

Example: HNDP

Example: LSLA

Example: LSHDP

Example: EQHDP

Example: CLA2

Example: CHDP

Example: MSB

Example: Genset

Example: GFI

Example: Arc Flash Analysis

Example: Arc Flash Analysis

Frequent Oversights & Considerations Compliance with NEC 211 7.1.B.5 Vertical Segregation of Required/Optional Emergency Loads Automatic Transfer Switches - Close and Withstand Rating Only not Interrupting If Switchgear/LVPCB are Utilized: 3-Cycle Transfer Switches Required How Shall We Comply with NEC 211 24.87? Avoid MLO Service Entrance Equipment System Origin: 3-Pole or 4-Pole ATS s Existing Conditions

Frequent Oversights & Considerations A Generator Submittal is not Complete without the Following: Generator Thermal Damage Data Generator Decrement Curve Data Generator Internal Thermal Overload Relay Data (if applicable) Generator OCPD Data Alternator Performance Data Consider the Impacts of: Paralleled Generators and Available Fault Current, Arc Flash Incident Energy, etc.

Frequent Oversights & Considerations Selective Coordination Considerations: Impacts of Generator MCB Settings, when Appropriately Applied, on Coordination Downstream Coordinate Normal Feed to ATS on ALL Facilities (Nursing Homes, etc.) OCPD Interrupting Rating Consider Zero Sequence Current Importance of Modeling Large Motor Contributions Generator OCPD AIC may Require De-rating per IEEE Blue Book 3.29 To Calculate Generator X/R: X/R = (2π)(f)(Ta)

Frequent Oversights & Considerations VFD Application from Generator Source: Restart from Power Loss Only LOTO Procedures Load Harmonic Content Bypass No Motor Contribution

End.