Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity

Similar documents
Cause, Effect & Mitigation Strategies

{40C54206-A3BA D8-8D8CF }

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Electrical Arc Hazards

First Draft Language

COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

Standards for MV switchgear rated for arc flash protection

Arc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:

Steve Kovach District Sales Engineer

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

Webinar: An Effective Arc Flash Safety Program

Arc Flash Analysis and Documentation SOP

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

ARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.

Arc Flash Calculation Methods

ARC FLASH HAZARD ANALYSIS AND MITIGATION

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

STANDARDIZING ARC FLASH PPE LABELS

Arc Flash and NFPA 70E

Arc Flash Analysis Training

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

Key factors to maintaining arc flash safety

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

DESIGN STANDARD DS 29

3Ø Short-Circuit Calculations

Power System Study for the Pebble #2 Lift Station Las Vegas, Nevada

Short Circuit Current Calculations

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

Effective System Grounding

Paul Dobrowsky Innovative Technology Services

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

NOTICE ER Roland Flood Pumping Station Arc Flash Study

CHANGEABILITY OF ARC FLASH PARAMETERS AND ITS IMPACT ON HAZARD MITIGATION IN LOW VOLTAGE POWER SYSTEMS

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Arc Hazard Assessment for DC Applications in the Transit Industry

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Electrical Measurement Safety. Sponsored By:

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Distribution Feeder Principles

How to maximize reliability using an alternative distribution system for critical loads

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

DC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE

7P Series - Surge Protection Device (SPD) Features 7P P P

A controlled arc-flash, produced in a flashtube. Even though the energy level used is fairly low (85 joules), the low-impedance, low-inductance

Electrical Protection System Design and Operation

Education & Training

Bus Protection Fundamentals

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

SECTION POWER SYSTEMS STUDIES

Distribution/Substation Transformer

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

NATIONAL ELECTRIC SAFETY CODE 2012 EDITION

Arc Flash Study Principles & Procedures for below 15 kv AC Systems. Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur

Arc Flash Hazard Standards:

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

7. INSPECTION AND TEST PROCEDURES

Technical T TECHNICAL. C o n t e n t s SPEEDFAX TM 2017

Grounding Recommendations for On Site Power Systems

Ampgard The name motor applications rely on

GE Multilin technical note

Electrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1

REDUCING ARC FLASH HAZARD BY REMOTE SWITCHING

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

1% Switchgear and Substations

Arc Flash Hazard. Can HRG Technology play a role in prevention?

Thomas Wilkins Wilkins Consulting Henderson Nevada U.S.A.

High Voltage Testing. Team 5: Justin Bauer, Matt Clary, Zongheng Pu, DeAndre Dawson, Adam McHale

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

CREATING A COMPARATIVE MAP OF RELATIVE POWER FOR DC ARC FLASH METHODOLOGIES. A Thesis. presented to

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Best Practice Reducing The Risk of Arc Flash Cross Over

MV network design & devices selection EXERCISE BOOK

In order to minimise distribution (11 and 22 kv) feeder breaker

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

INSTRUCTION MANUAL. March 11, 2003, Revision 3

Protective Relays Digitrip 3000

Earthing of Electrical Devices and Safety

Industrial and Commercial Power Systems Topic 7 EARTHING

2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Utility Interconnection and System Protection

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

Transcription:

Ft Worth IEEE-PES Presented by: Doug Harris Specifications Engineer Dallas, TX Arc-Flash Hazard Mitigation & Selectivity

Electrical hazards Energized circuit/conductor Today s power system engineer must not only assure that the facility receives all the power it needs efficiently and reliably, it is also important to make sure it is done as safely as possible without loss of reliability and under tight budgetary constraints. Electric Shock* Approximately 30,000 nonfatal shock accidents occur each year. The National Safety Council estimates that about 1,000 fatalities each year are due to electrocution, more than half of them while servicing energized systems of less than 600 volts Arc Flash* When an electric current passes through air between ungrounded conductors, or between ungrounded conductors and grounded conductors, the temperatures can reach 35,000 F. Exposure to these extreme temperatures both burns the skin directly and causes ignition of clothing, which adds to the burn injury. The majority of hospital admissions due to electrical accidents are from arc-flash burns, not from shocks. Each year more than 2,000 people are admitted to burn centers with severe arc-flash burns. Arc-flashes can and do kill at distances of 10ft (3m). Arc Blast* The tremendous temperatures of the arc cause the explosive expansion of both the surrounding air and the metal in the arc path. For example, copper expands by a factor of 67,000 times when it turns from a solid to a vapor. The danger associated with this expansion is one of high pressures, sound, and shrapnel. The high pressures can easily exceed hundreds or even thousands of pounds per square foot, knocking workers off ladders, rupturing ear drums, and collapsing lungs. The sounds associated with these pressures can exceed 160dB. Finally, material and molten metal is expelled away from the arc at speeds exceeding 700 mph (1600 km/hr), fast enough for shrapnel to completely penetrate the human body. * - Definitions are reproduced with permision from NFPA70E Handbook for Electrical Safety in the Workplace, Copyright 2009, National Fire Protection Association. Being near live electrical equipment is dangerous, whether shock or arc flash hazard, solutions exist to reduce hazard risk levels in a wide range of conditions and needs.

Example of an Arc Flash Event 635V/65kA 12 Cycle event, door open 33 cal/cm 2

BOTTOM LINE: 4 GE Title or job number 03/21/2014

Problem scope 1 8 Arc flash explosions per day 1-2 $16M Deaths per day related to arc flash incidents Average costs for each arc flash incident At this cost, why take chances? 1. U.S. statistic cited by CapSchell, Inc. in a study for the Electric Power Research Institute, 1999

Arc Flash Hazard Overview Voltage Av ailable Short Circuit Current Source Enclosure Working Distance Heat Measurement Arc Flash energy is a function of: Time to clear Arcing current RMS & peak magnitude, & time Electrode Gap Voltage Available short circuit current Working distance Arc gap Arcing fault clearing time (not short circuit clearing time) Sensitivity of Breaker/Trip Unit Fixed Based on system design and source Arms are only so long Determined by equipment type A function of the protective device acting upon the arcing current Clearing time is the only parameter than can be modified after the power system design is set. Therefore. Arcing fault clearing TIME becomes the critical factor

Arcing current (I a ) variability IEEE 1584 & NFPA 70E provide good guidelines... But real world variability may not be fully considered Tripping device response is dependent on arcing current Arcing current is dependent on: Gap, Voltage & I bf 45 The variables include: Utility information (worst case v installed), cable length, temperature, joint & device Z, transformer Z, etc. 40 35 30 25 20 15 Ia 100% I a, 32 mm gap 85% I a, 40 mm gap 10 5 20 30 40 50 60 Ibf 70 80 90 100

Arc flash protection PPE vs. cal/cm2 Many systems are > 12 cal/cm2: Generally uncomfortable and may impair dexterity Wearing suit could possibly cause accidents Getting the system <12 cal/cm2 can eliminate cumbersome PPE <12cal/cm2 >12cal/cm2

Incident energy dependant on event time Low level of incident energy requires fast mitigation. ~ ½ cycle interruption or less At the proper current level molded case CB & fuses operate in this range Large switchgear CB do not HRC-2 HRC-1 1.2 Cal/cm 2 9 8 7 6 5 4 3 2 1 0 Cal/Cm 2 10 20 30 40 I bf 50 60 70 80 90 100 3 cycle (large CB) clearing time (~50ms) 1.5 cycle 600-1200A (MCCB) clearing time (~25ms) 0.5 cycle clearing time, or less, (~<8ms)

Multiple approaches for arc flash safety and downtime Approach Key Limitations Keep incident energy low Preventive maintenance activity protection Minimize event equipment damage Shield personnel / add distance Arc Transfer Protection System Some extra footprint considerations, LV only Fast Grounding Crowbar System Potential equipment damage due to high fault current Temporary Maint. Settings -RELT Unplanned exposures if not enabled Arc Resistant Equipment Retrofit, effluent vents, footprint considerations Current Limiting (CL) Circuit Breakers Fault current variability Fast (CL) Fuses Large bus protection can increase arc flash energy Faster/More Sensitive Circuit Breakers System reliability/ selectivity Remote Operation Costs & complexity Personnel Protective Equipment (PPE) Comfort & dexterity

Some Present Approaches

Containment method arc resistant Common in MV systems Moving into LV systems Contains arc inside structure Barrier between person & arc Must be fully assembled Plenum needed to exhaust May be solution for operators, but not for maintenance

Testing for Arc Resistance Conformance Testing (IEEE C37.20.7) performed with covers & doors secured Arc resistance rating based on door & covers being properly secured Testing done at prescribed voltage & current levels and presumes limited arc duration (0.5 sec recommended) but no standard set. Specified flammable cotton indicators are positioned to detect the escape of hazardous gases, plasma, etc. Pass/Fail Criteria - Door, covers, etc. do not open. Bowing/distortion is permitted except in panel used for relays, meters, etc. - No parts are ejected into the vertical plane defined by accessibility type - No openings caused by direct contact with an arc - No indicators ignite due to escaping gases or particles - All grounding connections remain effective

Other characteristics and alternatives Heavier sheet metal Double wall construction Space dedicated to internal flues to channel gasses External flue to channel gasses to outside environment Potential impact of overall size Potential impact on density of devices Arc resistant gear does not address the ability to operate switches, inspect meters and trouble shoot the equipment. Most of those same benefits may be achieved via remote controls, remote instrumentation and judicious use of digital communication and modern electronics.

Modern Circuit Breaker Technology Reduced Energy Let Thru or Maintenance Switch Flexible Time Current Curves to fit all your needs Advanced Instantaneous Algorithm ZSI (Zone Selective Interlock) now has Instantaneous Enables. Arc Flash Protection and Selectivity at the Same Time

Flexible Time Curves GTU Cu 1000.00 1 more precision in settings and tolerances 100.00 2 3 1) Plugs: 37.5-100% sensor. LTPU 50-100% Plug Universal Rating Plugs 2) CB & Fuse Shaped LT Bands 10.00 Seconds 1.00 4 3) 22 LT delays in both CB & Fuse shapes, 44 total 4) STPU:1.5-12X LTPU, (0.05 increments) 5) STI 2 T slope: 3 different slopes 0.10 5 0.024 sec ST PU 7 6 6) ST TB: As fast as 1.5 Cycles, 11 different bands, in 55ms increments 7) Instantaneous pickup 2X-15X standard, optional 1.5-30X. 0.01 100 Amperes 1,000 10,000 100,000

Examples of TU curve flexibility FUSE BREAKER

The Dilemma? Arcing Current is typically below traditional Selective/Coordinated Instantaneous Pickup What s more Important? Reliability/Selectivity Reduced Arc Flash Energy AF Energy Reduction Instantaneous Selectivity Reliability

Example Arc Flash Current Level Arc Flash is typically 35-55% of the Bolted Fault Level 42KAIC Available fault current = ~18kA to 21kA Arc Flash Current (based on IEEE 1584) 3000A Breaker with Instantaneous set to 7X or Above won t see the fault and will be tripping on Short Time or maybe even Long time. Why not set the Instantaneous to 4X or 5X? Selectivity compromised. Loose coordination with downstream equipment. Don t want the upstream device to trip if the fault is below a downstream device.

A Popular Approach RELT Arc Flash Maintenance Safety Many other names However Switch EntelliGuard TU s RELT Switch With Positive Indication (Available on MCCB and ACB) 1. Remember to turn ON and LOTO 2. Turn it OFF: Uptime/Reliability is at stake

1000.00 GTU Curve, CB1 & CB2 RELT TCC 100.00 10.00 Seconds RELT OFF I-PU=45KAIC 1.00 0.10 RELT ON I-PU=4.5KAIC 0.01 100 Amperes 1,000 10,000 100,000 1,000,000

Now you can have Both, 24x7 Without the need for an ON/OFF Switch, Without sacrificing Reliability Trip unit algorithms monitor the current waveform to provide discriminant tripping Breaker to breaker communications HOW? Waveform Recognition Instantaneous Zone Selective Interlocking Instantaneous

Now you can have Both, 24x7 Without the need for an ON/OFF Switch, Without sacrificing Reliability HOW? OPTIMIZED INSTANTANEOUS SETTINGS Waveform Recognition Instantaneous Trip unit algorithms monitor the current waveform to provide discriminant tripping Zone Selective Interlocking Instantaneous Breaker to breaker communications

Waveform Recognition (WFR) Instantaneous 100,000 80,000 60,000 40,000 Prospective fault current (I bf ) Without WFR Instantaneous set above max peak let thru of downstream device (peak sensing) CL MCCB MCP FUSE x x 20,000 - - 0.005 0.010 0 (20,000) (40,000) (60,000) (80,000) Amperes Seconds TU Set below Current Limiting peak let thru Instantaneous set below Arcing Current while maintaining selectivity.

1000.00 GTU Curve, CB1 & CB2 Instantaneous 100.00 Selectivity TU selective settings based on the curve of the downstream current limiting molded case CB. Depends on the MCCB curve being defined correctly. 10.00 Seconds 1.00 Minimum selective IPU setting Transition 0.10 0.01 100 Amperes 1,000 10,000 100,000 1,000,000 1,000 10,000 100,000

Larger motor circuit protector 250A MCP 100,000 Peak Let-Through (I pk) 10,000 Feeder TU with Setting using WFR 1,000 100 Feeder TU with Setting using peak Arcing current 1,000 10,000 100,000 Fault Current (I bf ) 50 ka Ibf ~ 23 28 ka Ia Feeding a 250A MCP or CB in MCC with: > peak sensing trip, pickup overlaps arcing current so setting does not provide reliable instantaneous arcing fault protection > waveform recognition (WFR) capability, provides selectivity & instantaneous arcing fault protection with ~10kA of margin

Zone Selective Interlocking (ZSI) Trip Trip ZSI blocking signal > Zone Selective Interlocking used to force upstream CB to be selective with downstream CB > When upstream CB receives signal that CB below is interrupting fault it operates at a restrained slower speed allowing downstream CB to clear > All manufacturers offer ST & G > Can only be applied when using LVPCB upstream. > 1000 ft. Max signal cable length.

What about next level up? 1000.00 1000.00 I-ZSI 100.00 100.00 10.00 1.00 Fault below feeder shifts Main curve to restrained 10.00 At every level there is instantaneous protection 100% selective to 65kA and 85kA 1.00 x Seconds Seconds 0.10 0.10 0.01 100 1,000 Amperes 10,000 100,000 0.01 100 1,000 Amperes 10,000 100,000

Feeder Fault using Waveform Recognition and Instantaneous ZSI HRC 1 HRC 2 30 GE Title or job number 03/21/2014

LV system: <= 8 Cal/CM 2 on a 100KA I BF 480V MV Switchgear * 52 LV Switchgear * * * * * WFR - I MCC/Switchboard * ZSI - I * * * * Any Size 400A 1200A < 600A

A new approach What if a product could contain an arc fault in less than 8ms? a product could limit incident energy to 1.2 cal/cm 2? this could be done with equipment doors open? this could be done without adding additional bolted-fault type stress to the system? the product could be retrofit onto existing equipment?

Overview of arc containment method Arc Vault TM How it works

Alternative to Arc Resistance via containment - diversion Transfer to alternate current path 52 MV Breaker Present Technology - Crowbar > Remove arcing fault via bolted fault > Maximum bolted fault current > Electrical equipment damage XFMR Main LV Breaker Feeders..... New Technology Arc Containment Arc-to-arc transfer keeps energy low & allows fast mitigation Other equipment not damaged Fault eliminated in < ½ cycle No moving parts And, in new gear, meet the same Arc Resistance standard

Detection upstream controllable device MV Breaker XFMR Main Bus CT 52 Main LV Breaker Relay Entire switchgear line-up protected Incoming bus, main breaker, main bus, feeders Consider CT sensor placement Reasonable close-coupling Retrofit or new construction Arc Device Using transfer tripping & other techniques upstream protectors may be added as back up

Arc containment system Principle follows crowbar concept but.. Suppresses arc-flash with lower contained arc impedance Easier circuit interruption 63% less energy than a bolted fault Less impact on other components in electrical system Faster, simplified triggering method Fast transfer No moving parts Multiple use Maintenance tests

Arc containment device Outer Cover Isolation container Shock shield Arc created in interior chamber Vents Device has 3 functions Containment Isolation Dissipation Size = 2000A CB Electrode Plasma Gun Minimal venting Energy is dissipated/absorbed

Stress on power delivery system minimized I Z sys V sys Z capture sin Rt L wt e sin Open Air Arc Arc Containment Device 300 Crow Bar 150 110 90 48 65 63 62 30 ka RMS ka Peak A^2S(1,000,000) Arc impedance is key Not 0 ohms Resistive reduces DC offset I peak related to mechanical damage 40% less than bolted I 2 t related to thermal damage 63% less than bolted

Arc transfer principles V capture V sys Z arc Z arc Z source Path of least impedance Impedance of new arc lower than fault arc being removed But NOT zero impedance Introduced arc must be stable & divert current long enough for upstream CB to interrupt Pressure & heat must be predictable & controllable

Triggering Dielectric reduction with plasma B ph A ph C ph Plasma gun breaks down air allowing current to flow between electrodes <200 microsecond pulse is required Spacing & electrode geometry prevent breakdown during normal operation Limited wear allows testing & triggering system reuse

Trigger arc No moving parts Microsecond duration Microsecond response Multiple use Low energy trigger source Field testable

Limit energy and protect equipment Instead of containing arc flash event in the equipment; limit energy from arc flash event Decreased arc energy and increased system reliability 3 cycle CB interruption Arc Vault TM protection

Arc Vault components and indicators Device Status / Activation Switch Containment Dome D/O mechanism like circuit breaker Stored Energy health monitor D/O mechanism like circuit breaker

The Arc Transfer Protection System: Will contain an arc fault in less than 8ms, resulting in incident energy in accordance with IEEE 1584 at 18 from the arc event of less than 1.2 cal/cm², with the circuit breaker compartment doors open, in a 480V 65kAIC system. Can be retrofit onto existing LV equipment, including switchgear, switchboards, and MCCs Reduces building construction costs because it does not require exhaust chimneys or plenums Can be returned to service within a working day in the event of an arc flash incident, which improves overall system uptime Reduces energy released by 63%, compared to crow-bar type systems, which will lessen stresses on other system components, and improves overall system uptime

Summary of A-F Mitigation Alternates MV Breaker 52 F35 Relay Mains Feeders MV Fused Switch Technical Approach Incident Energy Incident Energy XFMR Existing System ~200 cal ~170 cal MV CB w/ F35 Relay ~10 cal Good ~10 cal Good TU w/ izsi ~200 cal ~5 cal Good ETU Main LV Breaker Arc Vault TU w/ izsi & MV CB ~10 cal Better ~5 cal Better Arc Transfer with MV CB ~1 cal Best ~1 cal Best Feeders..... Values shown are for a typical 13.8kV to 480Volt Substation with 2500 kva transformer, 65 KA.

Electrically Operated Remote Racking Device for Low Voltage Switchgear The electrically operated racking device allows maintenance personnel the ability to be up to 30 feet away from a draw-out breaker during the racking operation.

REMOTE OPEN/CLOSE and MONITORING - Near gear HMI in a stand-alone or wall mount unit can be placed well beyond the arc flash boundary. - HMI interface installed on a remote desktop or laptop PC connected via a LAN or the Web.

Thank you.