ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

Similar documents
SOCOMEC - Réf.: A

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Guidelines to Using a Three Phase Voltage Monitor

CONTROLLER ATyS C20/C30

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

PACSystems* RX3i IC695MDL765

WARRANTY. Long Range Systems, LLC, 20 Canal St, Suite 4N, Franklin, NH 03235

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

SUNDIAL Light Dimmer. User's Manual

NX Series Inverters. HVAC Pocket Programming Guide

BeeLine TX User s Guide V1.1c 4/25/2005

TCS2P125. Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual

S! Applications & Widgets

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Sentry Digital Timers

Monicon International Co., Ltd ATS 100 ATS 100 Controller User Manual

Philips Ledalite Phone: Fax: Web: Programming Guide Version 2.0

Digital Director Troubleshooting

FCR 06, FCR 12. Power factor correction controller. User and service manual

Solectria Renewables Modbus Level 5 For models PVI KW

HPVFP High Performance Full Function Vector Frequency Inverter

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

Model # PCYFC-10kW-250A PCYFC-20kW-250A PowerCycle Battery Conditioner Operation Manual

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay

CROSS Chassis from 160 A to 450 A

User Manual 3X300 DIMMER MODULE DM03B02KNX

Supply 12Vdc nominal (9 Vdc minimum, 14,5Vdc maximum ) Max Current Drain. from a , V Carrier Frequency

ICS REPEATER CONTROLLERS

User Guide & Owner Manual. InterPuls IUC 24

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

IDA 4 XM V 1.X. Installation and configuration of IDA 4 XM User Manual

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A.

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

13. Before making a service call Trip information and remedies

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

DPF-MAC Auto power factor controller

What is VC-VH? Old capacitor voltage terminology. Terminals on capacitor

PACSystems* RX3i IC695MDL664-BB

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04

Solectria Renewables Modbus Level 6 For models SGI 500XT

TI 360 System check (1.7 EN) System check function within the d&b D6, D12 and E-PAC amplifiers and remote control via R1

Voltage Volts AC RMS , 1 Phase

Kurz Instruments Inc. 19 August 2010

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1

ATyS M 6e Operating instructions GB

R&D TECHNICAL SPECIFI

PD300. Transformer, generator and motor protection Data sheet

VTSC100. Transfer Switch Controller

Before you operate the inverter, the parameters that you must first program are the basic parameters.

1000TR. Instructions

M2M i-link POINT-TO-MULTIPOINT INSTALLATION INSTRUCTIONS

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 6.2 June 12, 2013 USER MANUAL. metaphase-tech.com. pg. 1

V22 Thermostat N515/R00( )

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

Q-SERIES. Amplifiers. QPAIR Redundancy Switch Amplifier System. Installation & Operation Manual

Microprocessor Control Board Set Up Procedures (OR PLC)

vacon 100 flow ac drives application manual

CAT-260 Repeater Controller Computer Automation Technology, Inc

PROCESS & TEMPERATURE CONTROLLERS

OPERATING GUIDE OPERATING GUIDE FOR IC-F5060/F6060 SERIES BIIS 1200/MDC 1200 SYSTEM/ LTR /IDAS OPERATION

MOTOR MANAGER RELAY INSTRUCTION MANUAL. Copyright 1993 Multilin All Rights Reserved. The 301 is CSA approved. 215 Anderson Avenue 9746 Whithorn Dr.

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

ALPTEC POWER FACTOR CONTROLLER

SDMO. Changeover switch VERSO 200

Contents. English User Manual Regulators

SIGMA S6100 S/LS Module

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Room Controller Thermostat

ACC-1. Arcade Crane Controller. Manual Rev Page 1 of 9

Power Factor Controller RVT Installation and Operating Instructions

VISUALIZED DOUBLE FREQUENCIMETER WITH TWO ANALOG OUTPUTS

MDT Switch Actuator/FanCoil

Installation and Operating Instructions. Power Factor Controllers RVT

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

DUKANE. Frequency Tracking in iq Systems APPLICATION NOTE AN513. Intelligent Assembly Solutions

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

Océ User Manual. Océ CS550/CS6xx Pro Calibration

CONFIGURING DRIVE PARAMETERS

Precise Counting Scale GC. User Manual SNOWREX INTERNATIONAL CO., LTD. SRGC

About the DSR Dropout, Surge, Ripple Simulator and AC/DC Voltage Source

MFJ ENTERPRISES, INC.

BULLETIN # B

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

Installation and Operating Instructions. Power Factor Controller RVT-D

OPERATING GUIDE OPERATING GUIDE FOR IC-F5060/F6060 SERIES BIIS 1200/MDC 1200 SYSTEM/ LTR /IDAS NXDN OPERATION

MPS SERIES. INSTALLATION and TECHNICAL MANUAL MPS 4 MPS 5 MPS 9 4 PV

How to Guide: Controlling Blinds in C-Bus

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Eltek TU GenII GD900A Energy monitor (multidrop NDRail350) transmitter user instructions

OPERATION MANUAL MIMAKI ENGINEERING CO., LTD.

PROSOFT User Manual 3.03 VERSION

vacon 100 flow ac drives application manual

T25-35SA Subaudible Tone Decoder

+GF+ SIGNET Temperature Transmitter Instructions

INSTALLATION INSTRUCTIONS FOR SYMCOM S MODEL 77C-LR-KW/HP ELECTRONIC OVERLOAD RELAY

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

Model 532 ma/v Loop Calibrator with Loop Diagnostic Operating Instructions

SATELLITE RADIO/TELEPHONE

Transcription:

USER MANUAL ATS-I Tel.+39.0522.832004 P1/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.1/17

Index General description...3 Electrical specifics...3 Device operative logic...4 Manual mode...4 Automatic mode...5 Alarms...5 Display...6 Automatic transfer switch procedure mains-generator, generator-mains...8 Parameters Programmation...10 Phase detection special function...12 Mechanical Sizing...13 Rear View...14 Triple phase wiring diagram (230Vac, 400Vac, 440Vac)...15 Single phase wiring diagram (230Vac)...16 Tel.+39.0522.832004 P2/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.2/17

General description ATS-I controller allows an automatic transfer switch commutation between mains and generator. When faulty mains conditions are detected, the board sends a remote start signal to the engine; when the generator is running, if voltage and frequency measurements are compatible with programmed values, the changeover switch is activated towards generator side. When mains voltage returns back, transfer switch returns on mains side. Electrical specifics Supply voltage (isolated) 8 30 Vdc 230Vac 1ph Voltage measurements 230Vac 3ph 400Vac 3ph 440Vac 3ph Frequency measurements 45 65 Hz Generator voltage range 0 500 Vac Mains voltage range 0 500 Vac Measurements precision ± 2% Input LA 10 30 Vdc Input LM 10 30 Vdc Input LR 0 500 Vac Input LG 0 500 Vac Output START GEN. 5A, 10 30 Vdc Output TLR 5A, 230 Vac Output TLG 5A, 230 Vac Maximum reaction time for VF measurements 2 sec. Maximum phase detection delay 1 sec. Tel.+39.0522.832004 P3/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.3/17

Device operative logic There are two operative modes: - Manual - Automatic At the startup, device selects automatically the correct operative mode in accordance with P13 parameter; Aut/Man key allows to change operative mode without restriction. Front view: UP Aut/Man Generator Start Gen Select Mis Down LOCK Mains Manual mode In manual mode all system is controlled by ATS-I operative panel, on the left side of the display, a label shows the actual operative mode of the device ( MAN or AUTO ). Start Gen button allows to start and stop the generator; in case of idle generator, when Start Gen button is pushed, a blinking key icon will appear near MAN indicator to signal a starting phase for generator; when running engine is detected, the key become permanent. To stop the engine Start Gen key must be pushed again ( key icon will disappear). To switch contactor status from mains to genset, push Generator key: Generator icon will appear near frequency indicator, if genset line voltages are not within programmed limits (P5 and P6 parameters), the icon will blink; otherwise the icon will be permanent. Push Generator key a second time to disconnect generator line without switching; push Mains key to switch contactor status from genset to mains, a icon will appear near frequency indicator, if mains line voltages are not within programmed limits (P3 and P4 parameters), the icon will blink; otherwise the icon will be permanent. On display is possible to check mains line voltages, generator line voltages and frequency. Tel.+39.0522.832004 P4/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.4/17

To read mains voltages, push Select Mis key until L indication will appear on the left upper corner; at this point mains voltages will be showed on display. Push Select Mis again and G icon will appear; generator line voltages will replace mains measure. If generator is not running, OFF icon will appear which means unavailable genset measurements. In manual mode, operative generator alarms are not detected, are available only indicators LA and LM. Automatic mode Automatic mode allows to manage engine and transfer switch completely by software logic, it s not possible to start the generator or force switching through operative board, AUTO indication will appear on the low left corner. However with Select Mis is still possible to change displayed measurements from generator and mains. When controller commands switching on mains or generator, automatically values visible on display change in accordance. Each phase is checked separately, so a phase failure will start the automatic intervention procedure. Alarms If mains measurements are selected, in case of alarm will be possible to see one of these messages on the left side of the display : - LOW VOLT line voltage below programmed threshold ( P3 parameter ); - HIGH VOLT line voltage over programmed threshold ( P4 parameter ); Both alarms cause an automatic intervention procedure. With running generator, after programmable timer ( P8 parameter), the controller checks voltage status measured on alternator and in case of anomaly, one of these alarms will be showed on display: - ERROR 1 if generator s phase voltage is out of limits. ( P5, P6 parameters ). - ERROR 2 if generator s frequency is out of limits. ( P12 parameter ). - ERROR 3 if generator fails to start. If generator is working correctly, ERROR 1 or ERROR 2 alarms are showed if voltage or frequency values are out of limits for the duration of programmed time ( P15 parameter) To reset an alarm on display must be used Aut/Man key. The device returns on mains position and restarts commutation procedure towards generator. If generator alarm is active and mains voltage returns back, automatically the commutation will be switched on mains side. Tel.+39.0522.832004 P5/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.5/17

Display Display shows following indications: Line 1: Line 2: (Example G400 L1 L2 L3 ) this code indicates which line is measured and the connection type for the device. L230M Mains, 230Vac single phase connection L230 Mains, 230Vac three-phase connection L400 Mains, 400Vac three-phase connection L440 Mains, 440Vac three-phase connection G230M Generator, 230Vac single phase connection G230 Generator, 230Vac three-phase connection G400 Generator, 400Vac three-phase connection G440 Generator, 440Vac three-phase connection Below the code are displayed the values of measured line voltage. (Example Vac 384 387 383 ) On this line are showed the values of three measured voltages, at the beginning of the line is displayed the unit of measure. Line 3: (Example Hz 48 ) on this line is showed frequency value (Hz) measured on generator s phase 1, then after separation bar some status symbols are displayed. Generator symbol: is used when commutation is on generator side, the icon blinks if measured values are out of limits. Is alternative with Mains symbol. Mains symbol: is used when commutation is on mains side, the icon blinks if measured values are out of limits. Is alternative with Generator symbol. Pad lock symbol: is used when the keyboard is locked by LOCK button keep pushed for more than 5 seconds, to unlock the keypad, the procedure must be repeated. Tel.+39.0522.832004 P6/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.6/17

Symbol input LA active: the symbol is connected with LA input which usually means a generator alarm. Symbol input LM active: the symbol is connected with LMA input which means running engine. Line 4: On this line are showed information about device s operative modes. All available information are listed below: AUTO Indicates automatic operative mode, alternative with MAN and PROG. MAN Indicates manual operative mode, alternative with AUTO and PROG. PROG Indicates programmation mode, alternative with MAN and AUTO. When MAN or AUTO modes are selected, indicates running generator, blinking during start phase. When AUTO mode is selected, indicates the programmed delay time between faulty mains and starting generator (P7 parameter). Pxx xxx:xxx When PROG mode is selected, indicates parameter type Pxx and blinks to show that the parameter is going to be modified, the old values ( xxx: ) is showed on the left side of the colon, the new one Error message ( :xxx ) on the right side. When AUTO mode is selected, alarm messages are displayed in accordance with chosen visualization: L or G. Tel.+39.0522.832004 P7/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.7/17

Automatic transfer switch procedure mains-generator, generator-mains Initial configuration with mains OK (voltage values inside programmed thresholds) R = Mains G = Generator Delay P11 Mains coupling TLR closed TLG open START GEN closed Mains OK TLR closed TLG open START GEN open Mains KO + Delay P7 Starting engine TLR closed TLG open START GEN closed Delay 500ms Generator OK + Delay P9 Switching R-G TLR open TLG open START GEN closed Switching G-R TLR closed TLG open START GEN closed Mains OK + Delay P10 Generator OK TLR open TLG closed START GEN closed Delay 500ms When mains voltage is outside programmed limits (P3 and P4 parameters) for a delay time (P7 parameter), the intervention process starts; at the end of this period, the engine is started too and the controller waits for stable measurements for a delay time (P8 parameter), otherwise a ERROR 3 message will be displayed. With stable voltage and frequency values, after a delay time (P9 parameter) the commutation is switched on generator side; between mains contactor opening and generator contactor closure there is constant delay time of 500ms. Transfer switch remains on generator side until mains voltage returns in a stable way in accordance with programmed delay time (P10 parameter). Tel.+39.0522.832004 P8/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.8/17

With mains ok, generator contactor opens and after 500ms mains contactor is closed. After cooling time (P11 parameter) the generator is stopped. With running generator, if voltage and frequency value are outside programmed thresholds ( P5, P6 and P12 parameters) for a delay time (P15 parameter), the device will show an error message and the generator is turned off. In this case with Aut/Man key or when mains returns back, the device returns to the mains OK status where generator contactor is opened and mains contactor is closed. Tel.+39.0522.832004 P9/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.9/17

Parameters Programmation Parameters programmation can be performed without operative mode restriction. Hold UP and DOWN keys at the same time for 5 seconds to open programmation menu; the word PROG will be displayed with the indication relative to P1 parameter, with UP and DOWN keys is possible to scroll all parameters and select the one you need to change with Select Mis button. The chosen parameter begins to blink and will be possible to edit the value with UP or DOWN keys. Each increase/decrease command, the value will be modified by 1 unit. Hold the button to raise inc/dec speed by 1 unit every 500ms, and after 30 step, by 10 units every second. The old values ( xxx: ) is showed on the left side of the colon, the new one ( :xxx ) on the right side. To confirm the new value push Select Mis key, the parameter finish to blink and will be possible to select another value. To exit programmation mode and save changes made, hold UP and DOWN keys at the same time for 5 seconds. Below a comprehensive list with all parameters. Par. Values range Default (unit) values Description P1 230 M, 230, 400, 400(V tri Mains system type, shows nominal voltage and 440(V) phase) M symbol which indicates single phase system. P2 50, 60(Hz) 50(Hz) Mains nominal frequency P3 0-40(%) -15(%) Minimum mains voltage (percentage over nominal value) P4 0 +40(%) +15(%) Maximum mains voltage (percentage over nominal value) P5 0-40(%) -15(%) Minimum generator voltage (percentage over nominal value) P6 0 +40(%) +15(%) Maximum generator voltage (percentage over nominal value) P7 1 600(s) 5(s) Generator start delay P8 0 600(s) 120(s) Maximum engine running detection time P9 1 240(s) 5(s) Switching on generator delay P10 1 240(s) 10(s) Switching on mains delay P11 1 240(s) 30(s) Generator cooling time P12 1 5(Hz) 5(s) Generator frequency range P13 0(Automatic) 0 Operative mode selection at start up P14 1(Manual) 0(pad lock) 1(pad unlock) P15 1 10(s) 3(s) P16 0(Enable) 1(Disable) 0 Pad lock at start up Faulty mains / faulty generator delay. An alarm generating condition must be detected for this time long. 0 Phase detection function Tel.+39.0522.832004 P10/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.10/17

Voltage threshold limits change with 1% step, delay time change with 1s step, frequency range change with 1 Hz step, all other parameters have editing step in accordance with their range values. Tel.+39.0522.832004 P11/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.11/17

Phase detection special function Phase detection function can be enabled for both mains and generator three-phase systems with a special parameter ( P16 parameter). This function works only with manual mode and three-phase system; this function allows to check if each phase is detected correctly and if the phase sequence is the proper one. In case of anomaly on display will be showed this message: PH.SEQ.ERR, this alarm disable the closure of respective contactor ( G or L ). To reset the alarm can be used Select Mis key. After the device repeats the whole control and switching procedure. Tel.+39.0522.832004 P12/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.12/17

Mechanical Sizing Tel.+39.0522.832004 P13/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.13/17

Rear View GEN.INPUT MAINS.INPUT T S R T S R - + 8-30VDC LA LM L N L N START GEN. TLR TLG LR 230-440VAC LG 230-440VAC Tel.+39.0522.832004 P14/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.14/17

Three-phase wiring diagram (230Vac, 400Vac, 440Vac) Tel.+39.0522.832004 P15/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.15/17

Single phase wiring diagram (230Vac) Tel.+39.0522.832004 P16/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.16/17

NOTES: Tel.+39.0522.832004 P17/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.17/17