SM6. installation instructions. internal arc 16kA. 1s. addition to the standard cell user s instructions

Similar documents
Galaxy VM. Kit for IP32. Installation 06/

MCset 17.5 kv. Installation instruction April Medium Voltage Distribution

INSTALLATION MANUAL H A

Version: 1.0 Revised: 6/8/2011. CBU Assembly Instructions Manual

Pole Mount Installation Guide

REC Series Rack Installation Guide

INSTALLATION INSTRUCTIONS

Suited to vehicle/s SIDE RAIL 2 DOOR (SWB) SIDE RAIL 4 DOOR (LWB) WARNING

NISSAN T30 X-TRAIL WITH SUNROOF CARGO BARRIER FITTING INSTRUCTION PART NO YEARS OF MANUFACTURE MAY 2002 ONWARDS.

INSTALLATION INSTRUCTIONS UTV LIGHT BAR KIT Part Number: and Application: All UTV s*

ET-PKL100S. Installation Instructions. Ceiling Mount Bracket (for Low Ceilings) Model No.

INSTRUCTION MANUAL MANUAL DE INSTRUCCIONES

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTION ATV BUMPER/WINCH MOUNT Mount Kit: PN Application: POLARIS 300, 400, 500 and 700 Sportsman

Foot Rail. Nissan Navara_Frontier D23 DC START HERE! READ ME FIRST

FLOE DOCK FURNITURE WARNING ASSEMBLY INSTRUCTIONS

INSTALLATION INSTRUCTIONS

installation guide

TOYOTA TUNDRA CARGO DIVIDER Preparation. Part Number: PT

HD installation guide

LAnd Rover defender TDI & TD5 Gullwing WINDOW Box. You will need to have installed a Gullwing Door before installing the Window Box.

Installation Manual. Arc Chamber

INSTALLATION INSTRUCTIONS

Drawer Kit Jeep Wrangler JKU 4-Door (2007 current) READ ME! IMPORTANT WARNING!

SAFETY THIS PRODUCT IS FOR OFFROAD USE ONLY. ALL LIABILITY FOR INSTALLATION AND USE RESTS WITH THE OWNER.

SB-WM-ART2-L-BL SB-WM-ART2-XL-BL

SOLAR PANEL ACCESSORY. Solar Panel Mounting Bracket installation manual. Solar Panel Mounting Bracket

RE 2 Post Rack System

INSTALLATION INSTRUCTIONS

SAFETY THIS PRODUCT IS FOR OFFROAD USE ONLY. ALL LIABILITY FOR INSTALLATION AND USE RESTS WITH THE OWNER.

INSTALLATION MANUAL. All Recessed Wall-Mount Modules Front-Loading, Rear-Loading, Parcel-Only, Collection Box, Trash/Recycling Bin

Instruction Sheet P/N B Trim the new RTD wires. 5. Coat the new RTD with. 4. Strip the ends of the existing

IRM 2500 Rotation plate for oval rings (operating manual)

JEEP CARGO SLIDE IMPORTANT WARNING! SSST001. INSTALL TIME: 45 mins

Move System Swivel Caster Installation ( )

MSP-DCCPGSU Large Screen Static Display Mount

SAM. Model: STV-C65 LCD Mobile Visualized Stand Instruction Manual. Weight Capacity: 1251bs / 56.7kg Suits LCD Flat Panel Display: 42"-55" Page 20

Installation Instructions TMW Antenna Tower Mount for 4ft (1.2m) Antennas.

MSP-DCCPGTU Large Screen Tilt Display Mount

SB-WM-ART1-M-BL. Weatherproof Universal Single-Arm Articulating Mount for Medium Displays INSTALLATION MANUAL

INSTALLATION MANUAL FOR KINESIS STATIONS STEP MH67E EQUIPMENT REQUIRED FOR INSTALLATION

2-Door EXO-Top Roof Rack System

foot rail Toyota hilux REVO DC START HERE! READ ME FIRST

INSTALLATION INSTRUCTIONS ATV SNOW PLOW WARN KIT PN: KAWASAKI KIT PN: KAF Application: Kawasaki Prairie

PLOW MOUNT KIT FOR POLARIS RANGER P/N ASSEMBLY / OWNERS MANUAL

w w w. h d o n l i n e s h o p. d e VRSCF RIGID SADDLEBAGS GENERAL PREPARATION -J04704 REV Kit Number Models Tools and Supplies Required

Check the delivery for completeness and for any external damage. Contact your retailer if the delivery is incomplete or you find any damage.

READ ME! IMPORTANT WARNING! ENG. LED Light Bar Rack Mount Brackets

OB1U INSTALLATION INSTRUCTIONS. Interactive Flat Panel Over White Board Mount

RM4000 Tektronix 4000 Series Rackmount Kit

TOYOTA TACOMA ROOF RACK Preparation. Part Number: PT

Page No. 1 of 15. Issue F: 11/ FI

WARNING INSTALLATION MANUAL 1. SAFETY PRECAUTIONS 2. GENERAL DESCRIPTION TABLE OF CONTENTS

ATTENTION: PLEASE READ AND UNDERSTAND ALL INSTRUCTIONS AND WARNINGS BEFORE ASSEMBLING, INSTALLING OR USING THIS PRODUCT.

Installation Instructions

RMD5000 Rackmount Kit Instructions

MOTOR REPLACEMENT : STEP BY STEP.

INSTALLATION INSTRUCTIONS WINCH MOUNTING PLATE Part Number: Application: 2007 JEEP JK WRANGLER

INSTALLATION INSTRUCTIONS ATV PLOW Mount Kit: PN Application: HONDA RANCHER

Wall Mount Assembly and Mounting Guide (55 /84 )

Merloni Elettrodomestici. Technical Fitting Manual FRIDGE. Language Issue/Edition Page GB /

INSTALLATION & OWNER S MANUAL

2018+ Mustang Corner Pockets Installation Instructions P/N: (R B972)

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS. Large Flat Panel Wall Mount Model: PRO-2000 Series

INSTALLATION INSTRUCTIONS ATV Winch Mounting Kit Part Number: Applications: Honda Rancher. Before You Begin.

INSTALLATION INSTRUCTIONS ATV PLOW Mount Kit: PN Application: Sportsman 400, Magnum 425

23001 Industrial Blvd, Rogers, MN / Denali PLOW MOUNT

SM-RAZOR-ART2-L / SM-RAZOR-ART2-XL

Model Numbers: P/N Date TPS-200 POLE SAW ATT TPS-200. Supplier To The Outdoor Power Equipment Industry

INSTALLATION INSTRUCTIONS ATV WINCH MULTI-MOUNT Multi-Mount Mounting-Kit: PN Application: YAMAHA BIGBEAR 00+

Table Saw Small Parts Sled Instructions

INSTALLATION INSTRUCTIONS Small Flat Panel FMA Pivot Arrays Models: FMA-220 and FMA-320

VAN STORAGE SOLUTIONS FOR THE WAY YOU WORK

Installation Guide Philips MP80/90 Installation Kit for Penlon Anesthesia Machine

Instructions for Installation. S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection TABLE OF CONTENTS INTRODUCTION INSTALLATION

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off.

V Installation instructions, accessories. Auxiliary seat. Volvo Car Corporation Gothenburg, Sweden V70 (00-08) 2002

INSTALLATION INSTRUCTIONS Small Flat Panel Height-Adjustable, Extended Pitch Swing Arm Wall Mount Model KWE-110

RM4000 DPO4000 Series Rackmount Kit

AEROPRAKT SAFETY ALERT. No. SA A32-03 REPLACEMENT OF DOOR LATCHES

INSTALLATION INSTRUCTIONS

Wooden Frame Type Instruction Manual

OPERATOR'S MANUAL ROUTER MOUNTING KIT

ADULT ASSEMBLY REQUIRED

INSTALLATION INSTRUCTIONS. PLASMA TV WALL MOUNT TILT Universal (RGTU-210) WARNINGS WARNING

Read through the Operator's Manual carefully and understand the content before using the machine.

POWDER FEEDER #

RH-412 STEEL DOORS INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS POLE/PITCH- ADJUSTABLE MOUNT Model: TPM-2000 SERIES

Electrical Power Distribution Low-Voltage Systems SIVACON 8PS busbar trunking systems Installing with LI system

MOUNT KIT. Ford F-150 4X Installation Instructions CAUTION. Read this document before installing the snowplow. CAUTION

Installation Instructions

OWNER'S MANUAL. Parts list Check that all of the following items are present ENGLISH GERMAN FRENCH ITALIAN SPANISH. Before installation.

INSTALLATION INSTRUCTIONS RH 412 STEEL DOORS

Technical Newsletter #tnl e # 1 / 23

SENA INSTRUCTION MANUAL

MITSUBISHI PAJERO CK LONG WHEEL BASE 2100 MM TRACKS TRMP001

Shelf Converter Drawer System

JEEP JK ( 5 DOOR ) SLIMLINE II - FULL TRAY EXTREME RACK KIT

Transcription:

SM6 Anglais MV distribution factory built assemblies at your service installation instructions internal arc 16kA. 1s addition to the standard cell user s instructions

foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service unit for diagnosis and advice 3 4 distribution rules... safety rules... 4 4 general description... 5 description of cells on delivery... 5 package content sheet... 5 accessories, dimensions and masses... 7 list and no. of additional accessories and bags... 7 space requirements... 7 installation instructions... 9 preparation of cells before assembly of the panel... 9 frame preparation... closing the panel... 10 11 exhaust at the bottom... exhaust at the top... 14 15 assembling the cells together... refitting the rear roofs... 17 18 closing the panel... fixing to the ground... 19 19 installation in the unit... assembling the roofs together... 20 21 case of panel extension... 22 7897365EN revision : 02 1

2 7897365EN revision : 02

foreword symbols and conventions Caution: you will find all the symbols below throughout the document, indicating the hazard levels depending on the different types of situation. DANGER as per iso 3864---2 DANGER: failure to follow this instruction will result in death or serious injury. WARNING as per iso 3864---2 WARNING: failure to follow this instruction may result in death or serious injury. CAUTION as per iso 3864---2 CAUTION: failure to follow this instruction may result in injuries. This alert signal can also be used to indicate practices that could damage the SM6 unit. INFORMATION-ADVICE We draw your attention to this specific point. 7897365EN revision : 02 3

contact the Schneider Electric service unit for diagnosis and advice Call your sales representative who willputyouincontactwiththeclosest SCHNEIDER ELECTRIC group service centre. You can log on to: www.schneider-- electric.com distribution rules The aim of this publication is to enable the SM6 unit to be installed correctly. This document is not a commercial document. It is a strictly technical document drawn up by Schneider Electric. safety rules ATTENTION WARNING All the operations described below must be performed in compliance with applicable safety standards, under the responsibility of a competent authority. Thecontractormustbecertified and authorised to manipulate and perform work on the SM6 unit. WARNING Only undertake the work after having read and understood all the explanations given in this document. If you have any difficulty complying with these rules, please contact Schneider Electric. 4 7897365EN revision : 02

general description description of cells on delivery for dimensions: Width = 375 mm Width = 500 mm Width = 625 mm Exhaustatthetop The stack casing roofs are placed on the fixed cells roof with plastic collars. DOWNWARD gas evacuation UPWARD gas evacuation for dimension: Width = 750 mm Exhaustatthetop The stack casing roofs are placed on the fixed cells roof with plastic collars. DOWNWARD gas evacuation UPWARD gas evacuation 7897365EN revision : 02 5

6 7897365EN revision : 02

package content sheet Quantity for exhaust at the top N Description Quantity for exhaust at the bottom 2 51238823F0 panel reinforcement 2 1 51238815F0 RH vertical reinforcement 1 1 51238814F0 LF vertical reinforcement 1 2 51238813F0 interior reinforcement 2 1 51238812F0 LH top reinforcement 1 1 AAV48310 RH top reinforcement 1 1 51238832F0 LH end plate 1 1 51238831F0 RH end plate 1 2 51238488F0 casing side plate 0 1 51238077F0 panel end nuts and screws 1 1 3736016 cell divider 1 1 3729270 collector 1 1 3729278 collector 1 1 3728693 actuating lever 1 1 7897365 manual 1 7897365EN revision : 02 7

8 7897365EN revision : 02

accessories, dimensions and masses list and no. of additional accessories and bags exhaustatthetop: H Cell package --- 1 inter --- cell bag: S1: 51238084FA exhaust at the bottom: H Cell package --- 1 inter --- cell bag: S1 : 51238084FA H Panel package (AAV48533) H Internal arc casing kit width : 375 = AAV45358 width : 500 = AAV49368 width : 625 = AAV49371 width : 750 = 2 x AAV45358 H Panel package (AAV48538) space requirements Width = 375 mm mass: 150 to 210 kg* (maxi) Width = 500 mm mass: 230 kg* (maxi) 30 20 Width = 625 mm mass: 250 kg* (maxi) 1600 *depending on the type of cell 375/500/625 1060 1160 Width = 750 mm mass: 300 to 440 kg* (maxi) 30 1600 *depending on the type of cell 750 1060 1360 300 7897365EN revision : 02 9

10 7897365EN revision : 02

installation instructions preparation of cells before assembly of the panel exhaustatthetopor bottom for dimensions: Width : 375 mm Width : 500 mm Width : 625 mm A B Delivery condition: ground disconnecting switch in closed position. Remove the hoisting rings (A)......and the cross---pieces (B). C E D 1 Remove the rear roof (C). 12 screws (or 13 screws for cell 500 or 625). 2 Remove the LV hood (D). (2 screws). 3 Remove the LV cross --- piece (E). (2 screws) (except if LV casing). for dimensions: Width : 750 mm Delivery condition: --- circuit --- breaker open --- main isolate in ground position A B Remove the hoisting rings (A)... C E...and the cross---pieces (B). 1 Remove the 2 rear roofs (C). (24 screws). 2 Remove the LV hoods (D). (4 screws). 3 Remove the LV cross---pieces (E). (2 screws) (except if LV casing). D 7897365EN revision : 02 11

frame preparation only for cells at the end of the panel cell preparation for dimensions: Width : 375, 500 and 625 mm Width : 750 mm S4 nuts and screws bag: 51238077FA. 2 standard captive nuts M8 9 standard captive nuts M6 8blindcaptive nuts M6 Fitting the blind captive nuts. 1 Insert the captive nut from outside the cell in the rectangular hole provided for this purpose. 2 Tip the captive nut over into the cell. 3 Push the captive nut in the direction of the arrow to place the top part of the cage behind the plate. 4 Nut correctly placed. 1 2 4 3 Fitting the standard captive nuts. a Insert the captive nut from inside the cell in the rectangular hole provided for this purpose. b Nut correctly placed. a b 12 7897365EN revision : 02

closing the panel cell preparation for installing panel package C installing end plate Remove the hood (A) (2 screws). Remove the LV cross --- piece (B) (2 screws) (except if LV casing) Remove the back cover (C) (12 screws). Remove the front panel (D). B A D preparation and fitting of busbar kit 51238505FA (see instructions n 7897459 in package) Protection plate. 1 : fastening 1 screw M6x16 2 : verify correct alignment of the holes 3 : insulating plate 4 : installation of the inter---cell plate at each end of the panel (right and left) 1 2 3 4 7897365EN revision : 02 13

side upright fastening (E) 4 screws M6x16 + washers 2 screws M8x16 + washers 1screwM6x40+nut +washer 1screwM6x16+nut +washer detail E detail 1screwM6x16+washer (do not overtighten) bottom reinforcement fastening (F) 1screwM6x16+nut +washer 3 screws M6x16 + washers detail F fitting end plate (G) G 15 screws M6x16 +washers 14 7897365EN revision : 02

fitting top reinforcement (H) 4 screws M6x16 + washers H Overtighten screw M6x16 detail fitting the reinforcement bracket (J) detail 6 screws M6x16 + washers 1screwM6x16+washer fastening from the inside J refitting the rear roof plate (C) Securetheendplatetotheroof (C). 5 or 7 M6x16 screws + washer + M6 captive nut according to the version. Refit the LV cross---piece (B) (2 screws). Refit the LV hood (A) (2 screws). Refit the front panel (D). C B A D 7897365EN revision : 02 15

fitting the inter---cell ground collector G Exhaustatthetopandthe bottom on the first panel cell. Y G : ground collector Refit the front panel (D). 51238084FA. 1 screw + 2 washers + 1 nut Y: parttoremovetoconnect the main ground circuit. the collector (G) passes through the end plate. Depending on the panel layout, part (Y) will be removed on the LH or RH end plate. The collectors connect up. (HM screws 8x30) 2 ways of connecting to the unit s frame earth. exhaustatthebottom fitting the roof and fitting at the panel end X (the nuts and screws can be used again, see cell preparation chapter) It is vital to equip each roof with these 14 captive nuts before assembling it. S1 nuts and screws bag: 51238077FA. 14 standard M6 captive nuts C : rear roof (12 screws + washers) For width cells: 375, 500 and 625 mm The other roofs will be fitted after the busbar. Return the roof (C) to its position. C For 750 mm width cells Only the half---roof on the end platesidemustbefitted. The second roof will be fitted after assembling the busbar. 16 7897365EN revision : 02

exhaustatthetop fitting the roof and the panel end (the nuts and screws can be used again, see cell preparation chapter) It is vital to equip each roof with the 14 captive nuts before assembling them S4 nuts and screws bag: 51238077FA. 14 standard M6 captive nuts For width cells: 375, 500 and 625 mm Fix the top part of the end plate. Return the roof to its position. The other roofs will be fitted after the busbar is fitted. (the nuts and screws can be used again) For 750 mm width cells Fix the top part of the end plate. Only the half---roof on the end platesidemustbefitted. The second roof will be fitted after the busbar. fitting the side plate on the panel end H S4 nuts and screws bag: 51238077FA. 5 or 7 screws + washers Fit the screws by adding the side plate (H) against the roof flap. N.B.: perform the same operation on the RH end of the panel. 7897365EN revision : 02 17

fitting the front and rear vertical plate (J1) and (J2) by panel cell exhaustatthetop Bag of nuts and screws: 51238073FA. 2 screws + washers + nuts J1 and J2 are 2 identical plates J2 J1 Fixing from inside 4 screws + washers (the nuts and screws are to be recovered) Fit sheet (J1), then sheet (J2). Do the same for the continuity of the fitting of these plates for the entire panel. 18 7897365EN revision : 02

assembling the cells together exhaustatthetopor bottom S1 nuts and screws bag: 51238084FA 7 screws + washers + nuts P for panel up against the wall: L R 6 screws + washers for panel accessible from the rear: top view 8 screws + washers for dimensions: Width : 375 mm Width : 500 mm Width : 625 mm Width : 750 mm Fasten the cells together. (the remaining nuts and screws are used to fit the ground collector) L Bolt mounting direction L :leftcubicle R : right cubicle join the 2 cells together. HM6x60 screws to be tightened moderately to Tightening torque: 6Nm. R N Warning, for 750 mm widths: Remove the wiring cover (N). Fit the panel assembly screw (P). (be careful with LV wires) Put the wiring cover back in position. 7897365EN revision : 02 19

installing additional captive nuts to assemble the cells together exhaustatthetopor bottom S1 nuts and screws bag: 51238084FA. K If the panel is up against the wall, 6 standard captive nuts must be fitted inside the cell extension (K) and on one side only. (see details, fitting standard captive nut) If the panel is accessible from the rear, 8 standard captive nuts must be fitted inside the rear panel flap, and on one side only. (see details, fitting standard captive nut) refitting the rear roofs The nuts and screws can be used again. See chapter on preparation of cells. 20 7897365EN revision : 02

closing the panel exhaustatthetopor bottom cutaway overhead view on the right---hand end U N.B.: systematically fit an inter --- cell plate (U) available in the panel bundling always on the right--hand end, regardless of the output from the panel. closing the panel H Refer to the instructions: exhaust at the bottom.. H Refer to the instructions: exhaust at the top. fixing to the ground (nuts and screws to be provided by the installer depending on the civil engineering) for dimensions: Width : 375 mm Width : 500 mm Width : 625 mm Width : 750 mm 600 800 600 600 1600 2200 2800 1600 Exhaustatthebottom V Minimum volume of the service space (V): 2m 3 for the panel To be defined according to: 1 : Total width of the panel s cells 2 3 : Cable duct depth : Cable duct length 7897365EN revision : 02 21

installation in the unit exhaustatthetopor bottom for dimensions: Width : 375 mm Width : 500 mm Width : 625 mm Width : 750 mm Possible installation example 16 ka. 1s internal arc cubicle installed against a wall Exhaust at the bottom mini 50 mm 1 m recommandation 16 ka. 1s internal arc cubicle with corridor at the rear 800 mm Exhaust at the top and the bottom 22 7897365EN revision : 02

assembling the roofs together exhaustatthebottom for dimensions: Width : 375 mm Width : 500 mm Width : 625 mm Width : 750 mm screws + washers Assemble the roofs on each cell, use the existing nuts and screws again. Join each roof of each cell together using M6 screws. Reminder: you have already fitted captive nuts to the flaps of each roof. exhaustatthetop Use the roof plates present on the cell roofs and fix them to the casings. 7897365EN revision : 02 23

case of panel extension old (panel CEI 298) / new (panel CEI 62271 ---200) In the case of the extension, the performance of an extended panel (old/new) is the same as that of the old panel (standard CEI 298). Exhaustatthetop Keep the side plate of the stack (old right---hand or left---hand panel). Set up the new side plate and fit the stack casing kit (see chapter Exhaust at the top ) on the new cell coupled with the old one. 24 7897365EN revision : 02

group Schneider Electric service centers are there for: engineering and technical assistance start-up training preventive and corrective maintenance adaptation work spare parts Call your sales representative who will put you in touch with your nearest group Schneider Electric service centers. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F--- 92500 Rueil--- Malmaison (France) Tel:+33(0)141298500 http://www.schneider--- electric.com 7897365EN revision : 02 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Conception, rédaction: Service Documentation Technique T&D Edition du : 24/04/2008