PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

Similar documents
PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

Power Processor - Series 700F 10KVA to 150KVA

Power-Sure 700. Technical Data TD158001EN. Contents

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

ULTRA-K Series 600K - he

StatiVolt. Inverter UPS Systems. Features. Contents

TOSHIBA International Corp

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Transformer Basics AN05-10ST. Application Note. innovation in wire wound magnetic technology. January 09 Rev 1

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

USER S MANUAL. 1KSS60400/ ST Edition

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

60K(i) - 260K(i) THREE PHASE. SureImage IMAGING & TREATMENT SERIES

Phoenix DX Clean Power (18 Pulse) AC Drive

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

Power Protection and Conditioning

USER S MANUAL. 3KSS6050/ nd Edition

S11 Adjustable Speed Drive Engineering Specification

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

Table of Contents. Facility EMI Filter Products

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Multimode Video Fiber Optic Transmission Equipment

Amveco Toroidal Solutions. Acme Electric s class leading toroidal magnetics is the perfect solution for the most challenging applications.

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

SECTION PANELBOARDS

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

VF-nC1 Adjustable Speed Drive Engineering Specification

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

Low Pass Harmonic Filters

POWER QUALITY PRODUCTS FOR NON-LINEAR LOADS

1 INTRODUCTION ORDER CODE / INFORMATION

BUCK-BOOST TRANSFORMERS

WDG 61 - Technical Data Sheet

SPECIAL SPECIFICATION 6609 Fiber Optic Color Video and Data Transmission Equipment

Power Conditioners product guide

B. Manufacturers: Square-D, G.E. or Westinghosue.

LB115S 115W Single Output

WDG 12 - Technical Data Sheet

HPS Universal BUCK-BOOST TRANSFORMERS

TOA PROFESSIONAL POWER AMP

WDG 51 - Technical Data Sheet

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

EMI Installation Guidelines

WDG 83 - Technical Data Sheet

SECTION DISTRIBUTION SWITCHBOARDS

Design Specifications Low Voltage Active Harmonic Filter

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Bridgeport Magnetics Design Guide

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

Dry-Type Transformers

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 115VAC to 78% at 90VAC)

These power supplies are ideal for medical, telecom, datacom, industrial equipment and other applications.

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

WDG 71 - Technical Data Sheet

WDG 13 - Technical Data Sheet

WDG 07 - Technical Data Sheet

C.P. SENTINEL AQUA-LINE

ASX SERIES PACIFIC OPERATION MANUAL AC POWER SOURCE POWER SOURCE

SPECIAL SPECIFICATION 1789 Fiber Optic RS-232 Data Modem

5 x 3 x 0.75 Inches form factor. 275 Watts with Forced Air Cooling. Efficiencies up to 92% Standby Power < 0.5 W

CLP0224 Open Frame Power Supply Vac input; 24Vdc output; 200W Output Power

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC

The MBC550 range is ideally suited to a wide variety of medical applications, and also where airflow is limited or not available.

PRODUCT FEATURES TYPICAL APPLICATIONS

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Straight Isolation - Plug In (171 Series)

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

MODEL 3810/2 Line Impedance Stabilization Network

NetSure ITM. Contents 1. Site Planning Data 2. One Line Diagram 3. System Outline Drawings 4. Connection Details

American Power Design, Inc.

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 400VAC

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

These medical power supplies are ideal for, monitoring, home health equipment as well as surgical devices.

American Power Design, Inc.

Drives 101 Lesson 5. Power Input Terminology for a VFD

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

Installation requirements

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Transcription:

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) 1.0 General This specification covers the electrical characteristics and general requirements for a modular power distribution system with conditioning and regulation. The Medical Power Conditioner shall include all components and systems required to install, operate and maintain the system. The Medical Power Conditioner shall be tap switching regulator technology. 2.0 Applicable Documents 2.1 The National Electrical Code NFPA (Latest Edition). 2.2 American National Standards Institute Corp. and its Applicable standards C39.1, C80.1, C89, C84.1. 2.3 FCC Part 15, Sub-Part J, Class A. 2.4 IEC 435 International Electrotechnical Commission Recommendation "Safety of Data Processing Equipment". 2.5 VDE 0804/3.77 Verbauch Deulscher Elektotechniker standard. "Telecommunication and Electronic Data Processing Unit and Systems". 2.6 UL 1950 Underwriters Laboratories Inc. Standard for Safety. Electronic Data Processing and Office Equipment systems. 2.7 VDE 0806 Verbond Deutscher Electrotechniker Standard "Safety Design". 2.8 CSA 22.1 Canadian Standards Association, "Data Processing Equipment". 2.9 NEMA National Electrical Manufactures Association and its applicable standards. 2.10 Local Inspection Authorities having jurisdiction over electrical equipment and its installation. 2.11 MIL-T-27B Dry Transformer Insulation. 3.0 Major Components The basic components of the Medical Power Conditioner shall consist of: main input circuit breaker with 24 volt shunt-trip, caster based cabinet, double-shield computer grade isolation transformer, regulation electronics, internal wiring, single point ground, manual bypass switch, input filters, over current and over temperature protection. 4.0 System Package and Construction 4.1 Agency approval. The CP-18 shall be UL Listed under standard 1950. 4.2 Input Main Circuit Breaker (IMCB) The Medical Power Conditioner shall be equipped with a main input circuit breaker with a 24V shunt trip provided. The IMCB shall be rated for 125% of full load and be of thermal magnetic molded case construction. The IMCB shall have a minimum of 25,000 AIC rating. Provision for higher interrupting capacity shall be incorporated into the design to accommodate this type of breaker if required. The IMCB shall be UL Listed. 4.3 Cabinet Page 1 of 5

The Cabinet shall consist of the following: 1. Frame The Frame shall be of tubular construction of heavy gage metal and welded for maximum strength. Each frame shall be treated before paint is applied and be of textured baked enamel. The base shall be supported by (6) movable casters. 2. Internal Sheet Metal Internal sheet metal not welded to the frame shall be plated with Gold Zinc Wash to ensure RFI, EMI susceptibility reduced to the absolute minimum. 3. Access Access to the IMCB shall be through a heavy metal door attached with a continuous hinge and held shut with a magnetic strip which shall be attached to the door with screws and nuts. A removable rear access plate shall be provided for access to the transformer. All exposed access screws shall be bright nickel or black oxide plated. 4. Top Cover The top cover shall not contain any openings into the interior of the Medical Power Conditioner. 4.4 Isolation Transformer A double-shield, copper wound, convection cooled, 3 phase, isolation transformer shall be provided. Construction of the transformer should separate the Primary connections and the Secondary connections by placing them on opposite sides of the core. In addition, the output terminals of the secondary shall be at opposite ends of the coil for the input terminals of the primary to minimize the possibility of transverse node injection. A copper foil shield shall be provided to allow a large surface area for shunting RFI signals of the core to ground. The isolation transformer shall be mounted on rubber isolation pads to prevent 60 Hz hum of the core from being transmitted to the frame. The transformer core clamp shall be grounded to the frame through a 1" copper strap. The Transformer insulation system shall be 220 C. The transformer temperature rise shall be 150 C rise. Full load taps shall be provided (2) FCAN and (4) FCBN for connection to the tap switching regulator module. The unit shall be 150 C temperature rise. Two (2) temperature monitors shall be provided: 140 C (alarm) and 160 C (shut-down). 4.5 Regulation Electronics A solid state, electronic, zero current crossing tap switching regulation system shall be provided. This technology shall use SCR's (Silicon Control Rectifier) technology in its construction and shall be rated at 100% above worst case current ratings (26% below nominal) without any adverse effects. The regulation system shall respond to a change in the input voltage within a minimum of 1 cycle. 4.6 Bypass Switch (Regulation Only) A manually operated bypass switch shall be provided. In the event that the electronic control circuit fails, the switch shall select the 100% tap of the transformer to provide nominal voltage to the load. Access to the bypass shall not require removal of any panels. The bypass switch shall be accessible by the operator by opening the front door. The bypass switch is a "break-before-make" switch. 4.7 Internal Wiring All internal wiring shall be UL Listed appliance wire or Power wiring of multi stranded construction. Primary & Secondary Power wiring from transformer shall not pass through the same access holes in the transformer shield. When in close proximity, Secondary and Primary wiring shall cross at a 90 angle to minimize the injection of transient electrical noise between the two circuits. 4.8 Single Point Ground (SPG) A single point ground bus shall be provided and shall be of copper construction. Minimum thickness shall be 1/4" X 1" and be silver plated to provide connection of the lowest possible resistance of all ground wires secured to the Page 2 of 5

SPG. The following shall be grounded to the SPG: 1. Equipment grounds. 2. Neutral (star of isolation transformer). 3. Core of the Transformer. 4. Primary and Secondary shields. 5. Frame. 6. Equipment grounding conductor from the branch circuit. 7. System monitoring electronics. 8. All output conduits though the output conduit landing plate. 9. The input conduit though the input conduit landing plate. 4.9 Input Transient Noise Filter The Input Transient, electrical noise filter consist of a resistor/capacitor network which acts as a large snubber circuit to eliminate high frequency impulses from entering the power conditioner. 4.10 Output Transient Noise Filter The Output Transient Noise Filter consist of a capacitor network installed on the secondary. This capacitor network, when coupled with the primary filter, virtually eliminates most electronic noise from reaching the applied load or being fed back to the unit from noise generating loads. 4.11 Secondary Surge Suppression A transient suppression network shall be located on the secondary side of the isolation/regulation transformer. The SSS shall suppress load-induced noise to reduce the sensitivity of one load from another load. The SSS shall have the following characteristics: 1. Parallel (Shunt) Protection 2. Response time of < 5 ns 3. Repetitive transients up to 5000/sec 4. Clamping Voltage - 160 VAC line to neutral 274 VAC line to line (208Y/120) 5. Peak Pulse Power Rating of 27 kw line to neutral, 13.5 kw line to line 6. Each device shall be fused for circuit protection. Visual service indicators (one for each phase) shall be provided to indicate that the SSS is no longer providing protection. Page 3 of 5

5.0 Electrical Characteristics 5.1 60 Hz Frequency units 1. Output Rating KVA: 15 & 75 2. Input Voltage: 208, 480 or 600VAC 3. Output Voltage: 208y/120 or 480y/277 VAC 4. Input Frequency Tolerance: 60 Hz ± 3 HZ 5.2 50 Hz Frequency Units 1. Output Rating, KVA: 15 & 75 2. Input Voltage: 380 or 415 VAC 3. Output Voltage: 380y/220 or 415y/240 4. Input Frequency Tolerance: 50 Hz ± 3 Hz 5.3 Transformer 1. Type: Dry, isolation double-shield (Delta-Wye) 2. Impedance: 3% to 5% maximum 3. Efficiency: 96 % @ 100% load 4. Load Power Factor: Unity to 0.3 lead or lagging 5. Harmonic Distortion: < 1% maximum added 6. Waveform Distortion < 1% Added at Tap Switching: 7. Noise rejection (typical): Common mode - 120 db ( 0.1 Hz to 10 Mhz ) Normal Mode - 40 db/decade ( 2KHz ) 5.4 Audible Noise: <35 db measured on Response Curve A 5.5 Input Voltage Regulation: +10 to -26 % of nominal 5.6 Output Voltage Regulation: ± 3% typical; ± 4% maximum for all load and line conditions 5.7 Response time: 1 cycle typical 5.8 Output Rating: Continuous regardless of line / load conditions 5.9 Overload Inrush Rating: 200% of full load for 10 seconds 1000% of load for 1 cycle Page 4 of 5

6.0 Physical Characteristics 6.1 Dimensions: Height Width Depth 15 kva 32.0" 25.6" 17.0" 75 kva * 42.0" 32.0" 27.0" 6.2 Floor Loading Weight: Not to exceed 250 lbs. per sq./ft. 7.0 Operating Environment 7.1 Temperature: 32 F to 122 F (0 C to 50 C ) 7.2 Humidity: 10% to 90% relative humidity, non-condensing 7.3 Altitude: 0 to 7000 ft. 8.0 Storage Environment 8.1 Temperature: -4 F to 140 F ( -20 C to 60 C ) 8.2 Humidity: 0% to 95% relative humidity, non-condensing 9.0 Warranty The manufacturer shall warrant the Medical Power Conditioner to be free from defects in both material and workmanship for a period of 24 months from the time of installation or 30 months after shipment, which ever occurs first. 10.0 Manufacturer's Qualifications The Medical Power Conditioner shall be furnished by a manufacturer who specializes in the manufacturing of Power Distribution Systems with power regulation / conditioning and has been in business for at least 15 documented years, and with a nationwide service organization. The manufacturer shall be an ISO9001 certified company. 11.0 Qualified Systems. The unit shall be a Medical Power Conditioner manufactured by: CRUCIAL POWER PRODUCT 5701 Smithway Street City of Commerce, CA 90040 Page 5 of 5