NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PRESSURE GAUGES, Section 15130

Similar documents
Type F-20-3A Sanitary Pressure Transmitter NEMA 4X with Integral Junction Box

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS

FIELD DEVICES PRESSURE

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

11A Series Absolute Pressure Transmitters

ED701 General Industry Pressure Transmitter

SECTION FUEL OIL SYSTEM (PLUMBING)

ph or ORP Transmitter

Materials (other materials see WIKA diaphragm seal program) Model S-10

PAD - Heavy Duty Differential Pressure Trasmitter

NAVSEA STANDARD ITEM T9074-AS-GIB-010/271, Requirements for Nondestructive Testing Methods

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

SECTION COMMON WORK RESULTS FOR HVAC

The transducer component converts the measured signal and displays the actual value.

ADDENDUM NO. 1 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

FUEL GAS PIPING SECTION A. The provisions of SECTION 15010, MECHANICAL GENERAL REQUIREMENTS, apply to this section.

Digital inductive conductivity transmitter

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

1. ASME A Scheme for the Identification of Piping Systems.

Facility Services Subgroup Preface for Divisions 21` through 28

SECTION METAL FABRICATIONS

Flush pressure transmitter For viscous and solids-containing media Model S-11

QUALITY ASSURANCE SPECIFICATION

RCM DIRECT READING FLOWMETER

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CONTRACTOR SUBMITTALS. A. All submittals by the CONTRACTOR shall be submitted to the ENGINEER.

SECTION BASIC MATERIALS AND METHODS

Ashcroft Digital Pressure Gauges

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2

MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Valve Island with Electronic I/O

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

DPharp OVERVIEW PRESSURE SENSORS INTRODUCTION FEATURES. Resonant silicon sensor

.1 Materials and installation for steel piping, valves and fittings for hydronic systems in building services piping..2 Related Sections.

Pressure transmitter for general industrial applications Model A-10

Hydraulic Adapters STEEL PIPE ADAPTERS NPTF DRY SEAL PIPE ASSEMBLY INSTRUCTIONS. Steel Pipe Adapters. Steel Pipe Adapters. Hydraulic.

A Higher Level of Performance. Data Sheet. Series Pressure and Level Transmitters. For more information, please visit >

A. Extent of structural precast concrete work is shown on drawings and in schedules.

TECHNICAL SPECIFICATION FOR ANNUBAR (DELTA TUBE)

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400

A. Compatibility: Products shall be suitable for piping service fluids, materials, working pressures, and temperatures.

Screw-in resistance thermometers with plug connector

Ultrasonic level transmitter, non-contact

High-quality pressure transmitter For general industrial applications Model S-10

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration

VARIABLE FREQUENCY DRIVE SPECIFICATION

Pressure transmitter for general industrial applications Model A-10

General Specification

Heat Exchanger Construction Checklist

This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface.

Fisher 1052 Size 20 Diaphragm Rotary Actuator with H Mounting Adaptation

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

Conductivity Transmitter

UNIFIED FACILITIES GUIDE SPECIFICATIONS

FIELD DEVICES - PRESSURE

General Specifications

ATM.ECO - Analog Pressure Transmitter with Temperature Compensation

Pressure transmitter For general industrial applications Model A-10

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

APT3200L SMART PRESSURE TRANSMITTER. Application Areas: WITH DIAPHRAGM SEAL

Digital flow ELEMENT transmitter for continuous flow measurement

Thru Wall Floor Seals For New Installation

DOC. NO. : C3200-E04A APPROVED. Smart PressureTransmitter for Gauge and Absolute Pressure Measurement MODEL APT3200

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

The Metropolitan Sewer District of Greater Cincinnati

SECTION EQUIPMENT WIRING

General Information...SA1-SA4

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor

B34 Series Regulator Commercial and Industrial Regulator

Conductivity Analyzer

SECTION PANELBOARDS

STANDARD PHRASEOLOGY SECTION G. 1. This section of standard phraseology is for general use in piping disciplines.

Note: Do not bury sulphur dioxide lines Use stainless steel pipe and fittings only where specified on project drawings.

This specification describes the minimum requirements for piping systems for the following service:

Posiflow Proportional Solenoid Valves % ^ ) 2/2. Brass or Stainless Steel Bodies 1/8" to 1/2" NPT. Proportional Valves. Features.

Fisher 667 Diaphragm Actuators Size 80 and 100

SECTION MECHANICAL IDENTIFICATION

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

Digital flow ELEMENT transmitter for continuous flow measurement

Non-Submersible Industrial Pressure Transducer

USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER. Rev04009 USER MANUAL DEI MODEL USFT-CS

Digital conductivity transmitter

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

Model Sono-Trak Transit Time

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION WIRELESS CLOCK/TONE GENERATOR SYSTEM

Rosemount Product Discontinued. Alphaline Nuclear Pressure Transmitter. Reference Manual , Rev BA January 2008

CV Control Valves Installation and Operation Manual

Rosemount TGU 65 Tank Radar Gauge, Still Pipe Antenna

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

Pressure transmitter with flameproof enclosure For applications in explosion-protected areas Models E-10 and E-11

CITY OF TOMBALL. Section FIRE HYDRANTS 1.01 SECTION INCLUDES. A. Fire hydrants. B. Adjustment of fire hydrants and gate valves.

Wireless Transmitter Gauge Pressure Models Series XYR 6000 Specifications

Magnetic Flowmeter Systems

Transcription:

PART 1 GENERAL 1.01 SUMMARY Section 15130 PRESSURE GAUGES, This Section includes the furnishing and subsequent installation of pressure gauges and pressure level transmitters as shown on Plans and specified herein. 1.02 MEASUREMENT AND PAYMENT No separate payment for Work performed under this Section. Include cost of same in Contract price bid for Work of which this is a component part. 1.03 REFERENCES (NOT USED) 1.04 SUBMITTALS Submit the following in accordance with Section 01330 Submittal Procedures. A. Shop Drawings are required only when specified manufacturer, type, and/or features are/is deviated from. Shop Drawings, when required, are to include catalog data cut sheet showing manufacturer and highlighted with the exact model number. B. Operation and Maintenance Manual to be provided in accordance with Section 01782 - Operations and Maintenance Data 1.05 RELATED REQUIREMENTS A. Plans and Specification Sections show and/or specify those features required to describe and illustrate functional requirements for providing, testing, and installing pressure gauge, pressure level transmitters and appurtenances. B. All materials, supplies, labor, and supervision to be provided as required for a complete and workable system in coordination with available pressures and in accordance with manufacturer s recommendations. C. Section 01330 - Submittal Procedures D. Section 01782 - Operations and Maintenance Data E. Section 13346 - " Primary Instrument Devices" F. Section 16473 - "Water Receiving Facilities (WRF) Programmable Logic Controllers (PLC), SCADA Interface Panels and Panel Mounted Equipment" 15130 1

1.06 QUALITY ASSURANCE A. All products of a given type are to be furnished by a single manufacturer. B. All products to provide satisfactory operation and to require minimal maintenance under the following environmental conditions: 1. Temperature: 0 F to 140 F 2. Relative Humidity: 100 percent 1.07-1.13 (NOT USED) PART 2 PRODUCTS 2.01 MANUFACTURER(S) Subject to compliance with the Contract Documents, the manufacturers listed in the following paragraphs describing the elements are acceptable 2.02 MATERIALS AND/OR EQUIPMENT A. General Gauge and gauge seal materials to be equal to or better than the process piping materials of construction. B. Pressure Level Transmitter Provide pressure compensator for elevated tank applications. See Section 13346 - "Primary Instrument Devices" for more information on field devices. See "Pressure Gauge, Transmitters and Elements Schedule" in "ATTACHMENT" for type of transmitter(s) being installed. 1. Acceptable manufacturers: a. Rosemount, Model 3051 b. Siemens - Sitrans P500 series c. Endress-Hauser, Cerabar M d. Or Approved Equal 2. Materials a. Process-wetted parts 316 stainless steel b. Process connection: ½ in. NPT 15130 2

c. 316L stainless steel process diaphragm d. Utilize manufactures standard liquid fill e. Housing stainless steel f. Include two valve manifold for testing/vent/drain g. Include isolating diaphragm if designated in ATTACHMENT 3. Fabrication/Design: a. Output: 4-20 ma DC proportional to pressure b. Power supply: 24 volts DC c. Adjustable zero and span d. Temperature limits: -20 to 180 F, -4 to 175 F for LCD indicators e. Overpressure limits: Withstand 150 percent of stated maximum service pressure without damage f. Humidity limits: 0 to 100 percent relative humidity g. Damping: Adjustable between 0 and 32 seconds h. Inaccuracy (includes effects of linearity, repeatability and hysteresis): +/- 0.10 percent of calibrated span for 15:1 rangeability i. Stability: +/- 0.2 percent of upper range limit for 12 months j. Total temperature effect including span and zero errors: +/-0.2 percent of upper range limit per 100ºF for minimum 15:1 rangeability k. Include connections for ground storage tank levels to be able to be transmitted to SCADA System. See Section 16473 - "Water Receiving Facilities (WRF) Programmable Logic Controllers (PLC), SCADA Interface Panels and Panel Mounted Equipment" for more information on the interface between the pressure level transmitter and the SCADA system. 15130 3

C. Pressure Gauge 1. See "Pressure Gauge, Transmitters and Elements Schedule" in "ATTACHMENT" for type of pressure gauge(s) being installed. 2. Acceptable manufacturers a. Ashcroft b. Ametek c. Or Approved Equal 3. Materials a. Bourdon tube, socket, connecting tube: 316 stainless steel b. Glycerine-filled c. 316 stainless steel bourdon tube d. Phenolic or stainless steel case and ring, 4 1/2" diameter for pipes greater than 1 ½ in. and 2 ½ in. for pipes less than or equal to 1 ½ in. e. Stainless steel movement components f. Heat-resistant acrylic window g. White dial with black markings h. ½-inch NPT 316 stainless steel stem connection for pipes greater than 1 ½ in., and ¼ in. for pipes less than or equal to 1 ½ in. i. Overload stop high-pressure protection j. Pressure range on ATTACHMENT k. Accessory: Diaphragm seal when called out on Plans (1) 316 stainless steel wetted parts (2) Zinc-plated carbon steel top (3) Silicone-filled (4) Factory-installed and provided as a gauge and seal assembly ready for field installation as a complete unit 15130 4

4. Fabrication D. Diaphragm Seal a. Include isolation valve between pressure source and gauge b. Provide viewer protection from element rupture c. Calibrate gauges at jobsite for pressure and temperature in accordance with manufacturer's instructions d. All components suitable for service at 250 F or the maximum process temperature to which the gauge is to be exposed. e. Gauge tapping position to be clear of equipment functions and movements, and protected from maintenance and operation of equipment f. Gauge to be readable from an accessible standing position g. Gauge accuracy: +/- 0.5 percent of full range h. Select gauge range so that: (1) The normal operating value is in the middle third of the dial (2) Maximum operating pressure does not exceed 75 percent of the full scale range 1. See "Pressure Gauge, Transmitters and Elements Schedule" in "ATTACHMENT" for type of diaphragm seal(s) being installed. 2. Acceptable manufactures a. Ashcroft b. Ametek c. Rosemount d. Endress-Hauser e. Or Approved Equal 3. Materials a. Housing: 316 stainless steel b. Diaphragm: 316 stainless steel 15130 5

c. Use manufactures standard fluid fill unless otherwise noted on ATTACHMENT d. Process connections (1) Process: ½ in. NPT (2) Instrument: ½ in. NPT 2.03 SOURCE QUALITY CONTROL Each device to be factory tested over its full operating range. PART 3 EXECUTION 3.01 GENERAL / MANUFACTURER(S) Instruments and appurtenances to be installed in accordance with Plans, approved shop drawing when required, and manufacturer s recommended installation instructions. 3.02 INSTALLATION A. Installation to occur after major piping is installed and tested. B. Install products in accordance with manufacturer's instructions. C. Install instrument mounting pipe stands level and plumb. D. Instrument Valves: 1. Orient stems for proper operation 2. Install arrays orderly and neat in appearance with true horizontal and vertical lines 3. Provide a minimum of 2 inch clearance between valve handle turning radii where there are multiple valve handles appearing in a straight line. 4. Valves shall have bonnets and any soft seals removed during welding or soldering into the line. a. When cool, reassemble the valves 5. Support each valve individually. a. The tubing system does not qualify as support for the valve E. Locate instrument piping and tubing so as to be free of vibration and interference with other piping, conduit, or equipment. 15130 6

F. Keep foreign matter out of the system G. Remove all oil on piping and tubing with solvent before piping and tubing installation. H. Plug all open ends and connections to keep out contaminants I. Threaded Connection Seals: 1. Use Tite-Seal or acceptable alternate. 2. Use of lead base pipe dope or Teflon tape is not acceptable 3. Do not apply Tite-Seal to tubing threads of compression fittings 3.03 FIELD QUALITY CONTROL Field Calibration: Gauges are to be calibrated at 10, 50, and 90 percent of span using test instruments to simulate inputs. Outputs to be read that are rated to an accuracy that is at least five times greater than the specified accuracy. Such test instruments to have accuracies traceable to the National Bureau of Standards. 3.04-3.10 (NOT USED) 15130 7

A. Plans/Details ATTACHMENT [Design Engineer is to complete blanks per site requirements] 1. Drawing(s): 2. Detail Number(s): 3. Electrical Wiring Drawing(s): 4. Electrical Wiring Detail(s): Tag Number* PRESSURE GAUGE, SCHEDULE Pressure Range Diaphragm Seal (Y/N) Case * Tag number is the number identified with pressure gauge, transmitter or diaphragm seal on Plans. END OF SECTION 15130 8