FEDERAL SPECIFICATION SHEET FENCING, WIRE AND POST, METAL (CHAIN-LINK FENCE ACCESSORIES) (DETAIL SPECIFICATION)

Similar documents
RR-F-191/1D 14 May SUPERCEDING RR-F-191/1C July 22, 1981 FEDERAL SPECIFICATION SHEET

FEDERAL SPECIFICATION SHEET. FENCING, WIRE AND POST METAL (CHAIN-LINK FENCE FAfiRIC) (DETAIL SPECIFICATION)

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified.

PART MATERIALS. Section Fencing Materials. Description

Standard Specification for Fence Fittings 1

CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST

Item 550 Chain Link Fence

SECTION CHAIN LINK FENCING AND GATES

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

SECTION CHAIN LINK FENCING

COMMERCIAL ITEM DESCRIPTION RODS, GROUND (WITH ATTACHMENTS)

Project: # Solano Community College District

APPENDIX FENCE GENERAL NOTES

City of Regina Standard Construction Specification SECTION 2660 CHAIN LINK FENCE

MILITARY SPECIFICATION SHEET SCREW, CAP, SOCKET HEAD- HEXAGON, CORROSION RESISTANT STEEL, UNC-3A

FEDERAL SPECIFICATION WIRE, ELECTRICAL, COPPER (UNINSULATED)

SECTION CHAIN LINK FENCE GALVANZED CHAIN LINK FABRIC ON GALVANIZED FRAMEWORK [Provided by Master Halco]

Section 808. FENCING

SECTION METAL FABRICATIONS

FEDERAL SPECIFICATION SOCKETS, WIRE ROPE

NORMATIVE REFERENCES

COMMERCIAL ITEM DESCRIPTION SPLICE CONNECTORS

NORMATIVE REFERENCES

DRAFT UGANDA STANDARD

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

PERFORMANCE SPECIFICATION GLASS BEADS: FOR CLEANING AND PEENING

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

DETAIL SPECIFICATION SHEET TERMINAL, WIRE ROPE, SWAGING, FORK END

UNIFIED FACILITIES GUIDE SPECIFICATIONS

INCH-POUND. MIL-DTL June 2008 DETAIL SPECIFICATION WIRE ROPE, 1.5 INCH DIAMETER, GALVANIZED, COMPACTED STRAND, FOR AIRCRAFT ELEVATOR

SECTION TRAFFIC SIGNAGE

DETAIL SPECIFICATION SHEET TERMINAL, WIRE ROPE, SWAGING, STUD

I INCH-POUND I. MIL-sTD-47187(MI) 10 August 1993 SUPERSEDING MIL-N-47187B (MI) 31 Auqust 1990 NUTS, BLIND, PRESS, AND BLIND RIVET, INSTALLATION OF

Barofor Round System (polyester coated) Panels, Posts, Accessories

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

DETAIL SPECIFICATION SHEET SHACKLE, ANCHOR, FORGER CARBON STEEL SCREW PIN. Inactive for new design after 16 June 1997, For new design, use RR-C-271.

COMMERCIAL ITEM DESCRIPTION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DETAIL SPECIFICATION WIRE ROPE: STAINLESS STEEL, PREFORMED, ROTATION RESISTANT, FOR AIRCRAFT RESCUE HOIST, UTILITY HOIST AND WINCHING

PERFORMANCE SPECIFICATION GLASS BEADS: FOR CLEANING AND PEENING

DETAIL SPECIFICATION SHEET INSULATION SLEEVING, ELECTRICAL, HEAT SHRINKABLE, POLYOLEFIN, DUAL-WALL, OUTER WALL CROSSLINKED

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

VISUAL INSPECTION GUIDE FOR ALL-RUBBER GLOVES EXCEPT SURGICAL

DETAIL SPECIFICATION WIRE STRAND, NONFLEXIBLE, FOR AIRCRAFT APPLICATION

Woven Steel Wire Fence Type-47. Under the state specification for fencing, ASTM A 116 is called out.

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

FENCING PRODUCTS FENCING PRODUCTS. Please call:

Standard Specification for Carbon and Alloy Steel Nuts [Metric] 1

Exclusive Cantilever Gates

MIL-DTL-5421C 13 July 2007 SUPERSEDING MIL-T-5421B 20 May 1969 DETAIL SPECIFICATION TUBES, PITOT, ELECTRICALLY HEATED, AIRCRAFT

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

Standard Specification for Copper-Clad Steel Wire for Electronic Application 1

Standard Specification for Electric-Resistance-Welded Metallic-Coated Carbon Steel Mechanical Tubing 1

Government Recognized Export House OHSAS 18001:2007 ISO 14001:2004 PED Approved Company.

Heckmann Building Products Inc. DOVETAIL SLOT AND ANCHORS SPECIFICATION SECTION MASONRY ANCHORS AND ACCESSORIES PART 1 GENERAL

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL

2016 AASHTO BRIDGE COMMITTEE AGENDA ITEM: 24 (REVISION 1) SUBJECT: LRFD Bridge Design Specifications: Section 6, Various Articles (2)

ALLOY STEEL SOCKET SET SCREWS 1

HEARNE STEEL CO., INC.

International Tube & Conduit Company Ltd. BRITISH STANDARD STEEL CONDUITS & FITTINGS

NAVSEA STANDARD ITEM

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Standard Specification for Quenched and Tempered Steel Bolts and Studs 1

DETAIL SPECIFICATION SHEET FITTINGS, PIPE, CAST BRONZE, SILVER-BRAZING; REDUCING COUPLING, BUSHING, AND ADAPTER, PIPE

SUBMITTAL SHEET. Project Submittals by

COMMERCIAL ITEM DESCRIPTION FASTENER TAPES, HOOK AND LOOP, SYNTHETIC

STRUCTURAL STEEL AND ALUMINUM PART 1 - GENERAL 1.01 SCOPE:

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

MILITARY SPECIFICATION STUDS, BOLTS, HEX CAP SCREWS, SOCKET HEAD CAP SCREWS AND NUTS

SECTION BULLET- RESISTANT DOORS

SPECIFICATION FOR HIGH STRENGTH STRUCTURAL BOLTS

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

PIPE/CONDUIT SUPPORTS

Securifor Polyester Coated Welded Mesh Panels

MILITARY SPECIFICATION

METRIC TT-B-1325C June 1, 1993 SUPERSEDING TT-B-1325B April 25, 1978 FEDERAL SPECIFICATION BEADS (GLASS SPHERES) RETRO-REFLECTIVE

TECHNICAL CORRECTION October Process Industry Practices Structural. PIP STF05121 Fabrication and Installation of Anchor Bolts

SECTION THERAPEUTIC POOL ACCESSORIES

Procedure for Testing Direct Tension Indicators (DTI) Assemblies

METRIC FASTENERS 1520 METRIC FASTENERS

Section COUPLINGS AND COUPLING ADAPTERS. This Section covers couplings and coupling adapters for ductile iron and steel pipe.

ICC-ES Evaluation Report

Standard Specification for Steel Transmission Tower Bolts, Zinc-Coated and Bare 1

UFGS (November 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

DETAIL SPECIFICATION SHEET CONNECTORS, PRINTED CIRCUIT SUBASSEMBLY AND ACCESSORIES: KEYING ACCESSORIES

DETAIL SPECIFICATION SHEET

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the grade A325 structural bolt.

Downloaded from FEDERAL SPECIFICATION SHEET

Steel Nipples. Nipples & Fittings. Black and Galvanized Steel Nipples. Black and Galvanized. Steel Nipples. 142

COMMERCIAL ITEM DESCRIPTION CUP, DISPOSABLE: LID, DISPOSABLE CUP

1.1 SUMMARY. A. This Section includes the following: 1. Loose steel lintels. 2. Shelf angles. 3. Metal floor plate. 4. Pipe bollards.

STEEL PIPE GUIDERAIL 01/01/

Steel wire for general fencing purposes

Standard Specification for Steel Transmission Tower Bolts, Zinc-Coated and Bare 1

DETAIL SPECIFICATION SHEET ADAPTER, HYDRAULIC BLEEDER VALVE, AIRCRAFT WHEEL BRAKE

Annie Tel: MSN: All chain-link fences aren't the same

Downloaded from FEDERAL SPECIFICATION SHEET MAGNET, ELECTRICAL, CLASS 220, TYPE M, POLYIMIDE-COATED, P.

Transcription:

14 May 1990 SUPERSEDING RR- F-191/4C July 22, 1981 FEDERAL SPECIFICATION SHEET FENCING, WIRE AND POST, METAL (CHAIN-LINK FENCE ACCESSORIES) (DETAIL SPECIFICATION) IIIisFederal specification is approved by the Commissioner, Federal Supply Service, General Services Administration, for use of all Federal agencies. (This specification forms a part of the latest issue of Federal specification KR-F-191K/CEN) 1. SCOPE AND CLASSIFICATION 1.1 -. l%is specification covers general requirements for chain- link fence accessories. 1.2 Classification. Chain-link fence accessories Item 1 - caps. I tern 2 - Rail and brace ends. Item 3 - Rail sleeves. Item 4 - Wire ties and clips. I tern 5 - Brace bands. Item 6 - Tension wire Item 7 - Tension bars. I tern 8 - Tension wire. Item 9 - Truss rods. Item 10 - Barbed wire. Item 11 - Barbed wire support arms. Item 12 - Miscellaneous accessories. jbenef icial comments (recommendations, additions, deletions) and any pertinent j Idata vhich may be of use in improving this document should be addressed to: I ICommanding Officer (Code 156), Naval Construction Battalion Center, Port I IHueneme, CA 93043-5000, by using the self-addressed Standardization I IDocument Improvement Proposal (DD Form 1426) appearing at the end of this I Idocument or bv letter. I FSC 5660 DISTRIBUTION STATEMENT A Approved for public release; distribution is

unlimited. 2. APPLICABLE DOCUMENTS 2.1 Fon-Govemment documents. The following other non-government documents form a part of this specification to the extent specified herein. Unless othervise specified, the issues are those cited in the solicitation. Am! ASTM A 90 - Test for Weight of Coating on Zinc-Coated (Galvanized) Iron or Steel Articles. ASTM A.428 - Tests for Weight of Coating on Aluminum-Coated Iron or Steel Articles. ASTM B 211 - Aluminum-Alloy Bars, Rods, and Wire. ASTM B 687 - Measuring Metal and Oxide Coating Thicknesses by Microscopical Examination of a Cross Section. ASTM E 376 - Coating Thickness by Magnetic- Field or Eddy-Current (Electromagnetic) (Application for copies should be addressed to the ASTM, 1916 Race Street, Philadelphia, PA 19103. ) 3. REQUIREMENTS 3.1 Materials. Materials shall be as specified herein and in applicable specifications and standards, and other referenced documents. Materials not specified shall be selected by the contractor and shall be subject to all provisions of this specification. Materials shall be free of defects which adversely affect performance or serviceability of the finished product. 3.2 Zinc-coating. Unless otherwise specified (see 6.1), all ferrous accessories shall be hot-dip zinc-coated with an average weight of not less than 1.2 ounces of zinc per square foot of coated surface area. 3.3 Color coatinp and material. When color coating is required the color shall be as specified (see 6. 1), and shall match the color specified for chainlink fabric as cited in RR- F-191/lD. Ferrous accessories shall be zinc-coated in accordance with 3.2, prior to application of color coating. Unless otherwise specified (see 6.1), color coating material shall be at the option of the manufacturer. 3.4.1 Item 1. caps. All exposed ends of tubular posts shall be fitted with caps. The cap shall fit snugly over the posts and exclude moisture such as rain. When top rail is provided the caps shall have. a ring or hole suitable for the through passage of the cop rail Caps shall be formed steel, malleable or cast iron, or aluminum alloy. 3.4. Z Item 2. tou rail and brace ends. Ends for top rail and braces shall be provided when top rail or braces are required. Top rail and brace ends shall be formed steel, malleable or cast iron, or aluminum alloy. 2

3.4.3 Jtem 3. tou rail sleeves. Top rail sleeves shall allow for expansion and contraction of the top rail. Top rail sleeves shall have a inimum length of 6 inches, and be of the same material as the cop rail. Top rails provided with 3-inch swage ends are acceptable in lieu of top rail sleeves. 3.4. k Item 4. wire ties and clins. Wire ties or clips shall be provided for attaching fabric to line posts, top rail, or tension wire. Wtre ties and clips shall be at intervals not greater than 15- inches when attaching fabric or line posts, and the space inte~al shall noc exceed 24- inches when attaching fabric to top rails or tension wire. Unless otherwise specified (see 6.1), wire ties and clips shall be not less than the fabric wire gage size and of the same coatings. The minimum weight for zinc coated wire ties and clips is 0.8 ounces of zinc per foot of coated surface area. Wire ties and clips shall not fracture when tested in accordance with 4.4.1. 3.6.5 ~tems 5 and 6. brace and tension bands. Brace bands shall be used to secure top rail and brace ends to terminal posts. When tension bars are used, tension bands shall be used for securing chain- link fabric at each terminal post (see 3.4.6). Spacing of tension bands on posts shall be at 15- inch intenals or less. Brace and tension bands shall be steel and shall be 3/4- inch wide by 1/10- inch thick nominal. 3.4.6 Item 7. tension bars Tension bars for 1-3/4 and 2- inch mesh shall be no less than 3/16 by 3/4- inch or equivalent cross -sectional area. Tension bars for 1- inch mesh shall be no less than 3/8 by 3/16- inch or equivalent cross -sectional area. A tension bar shall be provided where chain-link fabric meets terminal posts. Tension bar shall be steel, of a continuous length compatible with the height of the fence and shall be threaded through che fabric and attached to the post by tension bands (see 3.4.5) Roll formed posts with integral loops for weaving fabric co posts are acceptable in lieu of tension bars. 3.4.7 Item 8. tension wire. Tens ion wire shall be furnished when top rail is not required. Tension wire shall be used at the bottom of the fence when fabric is not otherwise secured. Tension wire shall be zinc coated steel, aluminum coated steel, polyvinyl chloride (PVC) over zinc-coated steel, or aluminum alloy as specified (see 6. 1) Unless othervise specified (see 6.1), all tension wire shall be 7 gage wire size with an outside diameter of 0.177-inch (+0.005-inch) 3.4.7.1 Steel tension wire. Steel tension wire shall be marcelled or crimped coil spring hard tempered carbon steel wire. The tension wire shall have a minimum tensile strength of 75,000 pounds per square inch. Zinc coated steel shall not have less than 1.2 ounces of zinc per square foot of coated surface area unless otherwise specified (see 6. 1) Aluminum coated steel shall not have less than 0.40 ounces of aluminum per square foot of coated surface area. Unless otherwise specified (see 6.1), PVC coated wire shall have inimum coating thickness of 0.007- inches. The coatings shall match the fence fabric. 3.4.7.2 Aluminum allov tension wire. Aluminum alloy tension wire shall conform to the chemical composition of ASTM B 211, Alloy 6061 -T94. 3

3.6.8 Item 9. truss rods. Truss rods shall be steel and have a minimum diameter of 5/16-inch. 3.4.9 Item 10. barbed wire. Barbed wire shall consist of two 12-1/2-gage 0. 099-inch (+0. 005- inch) twisted line wires with 1~-gage 0.080- inch (+0, 005-inch) round barbs. Barbed wire shall be zinc-coated steel, aluminum coated steel, aluminum alloy, or PVC over zinc-coated steel as specified (see 6.1). All barbs shall consist of four points and spacing of barbs shall be at 5- inch (+1- inch) centers. 3.4.9.1 Zinc-coated steel barbed wire. Zinc-coated steel barbed wire shall have a zinc coating of at least O. 80 ounces per square foot of coated surface area (see 4.4,2.1) 3.4.9.2 Aluminum-coated steel barbed wire. Aluminum-coated steel barbed wire shall have an aluminum coating of at least O. 30 ounces per square foot of coated surface area (see 4.4.2. 1) Solid aluminum barbs are acceptable. 3.4.9.3 PVC coated steel barbed wire. PVC coated steel barbed wire shall have a PVC coating of at least 0.007- inch thickness. Wire shall be coated with a minimum of O. 3 ounces of zinc per square foot of coated surface area or meet the requirements of 3.4.9.2 before application of the PVC coating. 3.4.9.4 Aluminum alloy barbed wire. Aluminum alloy barbed wire shall conform to the chemical composition of ASTM B 211, Alloy 6061 -T94. 3.5 Item 11. barbed wire support arms. Barbed wire support arms shall be of the following types as specified (see 6. 1) (a) Single. arm, for three barbed wire strands. (b) V - arms, for six barbed wire strands (c) A - arms, for five barbed wire strands When installed, the barbed wire support arms shall project at an angle of 45 ~ 5 degrees from the plane of the fence line and the outer strand of barbed wire shall be positioned 12 ~ Z- inches horizontally from the fence line. Intermediate strands of barbed wire shall be uniformly spaced between the strand on the end of the support arm and the fabric. All support arms shall be fitted with clips or slots for attaching the barbed wire to the support arm Support arms shall be capable of withstanding a load of 250 pounds (lbs) when tested in accordance with 4.4.3. 3.6 Item 12. miscellaneous accessories Unless otherwise specified (see 6.1) miscellaneous items, such as bolts, nuts, and washers shall be galvanized steel or aluminum alloy at the manufacturer s option. 4, QUALITY ASS WCE PROVISIONS 4.1 Resvonsibilitv for inspection. (See RR- F-191 K/GEN) 4.2 SamDling. (See RR- F-191 K/GEN, section 6) 4.3 Examination: Examine accessories for defects listed in table 1. 4

RR- F-191/6D TABLE VIII. Classification of defects, posts, rails, and braces. Defects Maior Minor I ~Item not as specified. x ITension wire not as specified. x I IColor not as specified. x I IDimensions not within tolerance where applicable. x IBarbed wire not as specified. x IBarbed wire support arms not as specified. x IDamage or defects affecting function or serviceability. - x }Damage or defects not affecting function or serviceability. x 1 I 4.3.1 ~ickness of bands and diameter wire. Determine the thickness using a suitable micrometer. Measure diameter of wire by taking the average of cwo dimensions at right angles to each other. 4.4 Test methods 1 4.4.1 Wire ties snd clips. Bend wire from which ties and clips are formed through an angle of 180 degrees (0) on a mandrel having the same diameter as the wire under test to determine conformance to requirements of 3.k. 6. L.4.2 Weicht and thickness of metallic coatiruzs 4.4.2.1 Weight of zinc coating. Determine weight of zinc coating in accordance with ASTM A 90 (see 3.4.7.1 and 3.4.9.2). 4.4.2.2 Weirht of aluminum coating. Derermine weight of aluminum coating in accordance with ASTM A 428 (see 3.4.7.1 and 3.4.9.2). 4.4.2.3 Thickness of aluminum coating. Determine thickness of aluminum by any one of the following methods (see 3.4.7.1 and 3.4.9.2). 4.4.2.3.1 Measurements. Determine the thickness by taking half of the difference between the diameter of the aluminum-coated wire and the diameter of the wire after stripping the aluminum, or determined microscopically in accordance with ASTM B 487. Use the mean of two measurements at right angles to each other when determining the diameter of che coated or. the stripped wire, or use the mean of the coating thickness r.aken at right angles to each other when determined microscopically. 4.4.2.3.2 Magnetic. Determine thickness of aluminum coating magnetically in accordance with ASTM E 376, 4.4.3 Barbed wire SUDP orc arms. Clamp the base of the arm securely. Apply a vertical 250-lb load where the outer strand of barbed wire connects to the arm, permanent deflection of the arm is cause for rejection (see 3.5) 5. PREPARATION FOR DELIVERY (See RR-F- 191K/CEN) 5

may 6. NOTES (This section contains information of a general or explanatory nature that be helpful, but is not mandatory. ) 6.1 Orderin.e Data. Purchasers should select the preferred options permitted herein and include the following information in acquisition documents: a. Title, number, and date of this specification. b. Issue of DODISS to be cited in the solicitation, and if required, the specific issue of individual documents referenced (see 2.1). c. Item required (see,1.2) d. Material for accessories if other than specified (see 3.1) e. Zinc coating if other than specified (see 3.2) f. Color coating material if other than specified and color required (see 3.3). - )3. Type of tension wire required (see 3.4.7) h. When wire ties and clips are to be other than required (see 3.4.4) i. When tension wire is to be other than 7 gage and gage required (see 3.4.7). j. zinc coating for steel tension wire if other than specified (see 3.4.7.1). k. Type of barbed wire required (see 3.4.9) 1. Type of barbed wire support arms required (see 3. 5) m. When miscellaneous accessories are not the manufacturer s option and the accessories specified (see 3.6) 6.2 Accessories. Consult manufacturers or suppliers when ordering accessories since some accessories are furnished with all chain- link fencing. MILITARY CUSTODIANS : Army - ME Navy - YD Air Force - 99 Review Activity OL4 - Cs User Activities Army - CE Navy - MC, CG CIVIL AGENCY COORDINATING ACTIVITIES : CSA - FSS HHS - FEC INTERIOR - BLM USOA - AFS PREPARING ACTIVITY : Navy - YD (Project 5660-0091) Orders for this publication are to be placed with General Services Administration, acting as an agent for the Superintendent of Documents See section 2 of this specification co obtain extra copies and other documents referenced herein. 6