Digital Input Output Module for Zone 2 Series 9470/33

Similar documents
Digital Input Output Module for Zone 1 Series 9470/32

Digital Input Output Module for Zone 2 Series 9470/33

Analog Universal Module HART for Zone 2 Series 9468/33

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Temperature Input Module for Zone 1 Series 9482/32

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

Remote I/O. 74 Remote I/O. Remote I/O System

Binary Output without Power Supply Series 9176

Binary Output Series 9175

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

Isolators A3/1.

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolating Repeater Input Series 9163

Fieldbus Isolating Repeater Series 9185/11

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Digital I/O Coupler (4-wire) Series 9413/21

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Isolators A3/1.

Single-Channel Safety Barriers Series 9001

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC

Assembly. Front view. HiC2441. SL2 1b. Termination Board

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP

Inductive sensor slot-type SI2-K08-AP7

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

Data Sheet KFD2-UFC-EX1.D. Supplied by. .com. Call us on +44 (0)

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

EP-5111, EP-5112, EP-5212, EP-5261, EP-5311, EP-5422, EP-5442

Technical Data. General specifications. Rated operating distance s n 3 mm

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Assembly. Front view. Switch Power Rail

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

Field indicator for current loops with HART communication Models DIH50, DIH52

Rail mounted Temperature Transmitter TH102/TH102-Ex

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Assembly. Front view. Switch Power Rail

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Temperature transmitter itemp PCP DIN rail TMT 121

Safety Instructions Nivotester FTC625, FTC325

Assembly. Front view. Parametrization interface. Power Bus

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

Head mounted Temperature Transmitter TF02/TF02-Ex

PRetrans Table of contents

onlinecomponents.com

A6500-UM Universal Measurement Card

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

Field indicator for current loops with HART communication Models DIH50, DIH52

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

Signal Beacon - LED Series 6162

Control Unit Series 8208

Motor Protection Circuit Breaker Series 8146/5-V27

ISOLATING SWITCHING AMPLIFIERS POWER SUPPLIES

Positioner with HART Communication Type 3780

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator

0 2 1 â Ó. itemp HART TMT182. Technical Information

SINEAX TI 807 Passive DC signal isolator

Assembly. Front view. LED yellow: Relay output I. LED red: LB/SC channel I. LED yellow: Relay output II. LED red: LB/SC channel II

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:

Technical Information Barrier RB223

Certificate of Compliance

Temperature Transmitter itemp RTD DIN rail TMT 127

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

MACX MCR-EX-SL-RPSSI-I-UP(-SP)

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview

D1072. SIL 2 Temperature Signal Converter, Duplicator, Adder/Subtractor DIN-Rail Models D1072S, D1072D. Front Panel and Features:

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN

SINEAX TV809, 1 channel Programmable Isolating Amplifier

Assembly. Front view. LED yellow: Relay output I. LED red: LB/SC channel I. LED yellow: Relay output II. LED red: LB/SC channel II

Incremental encoders Blind hollow shaft or cone shaft pulses per revolution

Actuators Series 8602/3

Rudder or propeller angular position transmitter KINAX WT720

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

0 2 1 â Ó. itemp HART TMT182. Technical Information

SITRANS F flowmeters SITRANS F US. SONOFLO SONO 3000 transmitter. 4/152 Siemens FI Overview

MACX MCR-EX-SL-RPSSI-I

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

Operating Manual. isolate501

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Rotary Measuring Technology

General Specifications

BAR-ANT-N-N-EX. Antenna barrier for the hazardous area. Data sheet. 1 Description

Incremental encoders Redundant sensing, isolated blind hollow shaft ø mm, cone shaft ø17 mm pulses per revolution

SALES SERVICE +358 (0)

Transcription:

www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used as frequency/counter input; with rotation direction recognition > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in the hazardous area under power (hot swap) 15233E00 The Digital Input Output Module is used for connecting of up to 16 intrinsically safe digital signals to the IS1 Remote I/O system. All can be parameterised in pairs as input for connection of passive contacts or NAMUR proximity switches (EN 60947-5-6) or as output for connection of low power solenoid valves. Up to 8 inputs can be used as frequency inputs or counters up to 20 khz, in operating mode "Rotation direction recognition" and "Forward/backward counter" up to 4 inputs. The Ex i inputs or outputs are short-circuit proof and galvanically separated from the system. Compatible spare for IS1 I/O modules: Series 9470/12, 9470/22, 9475/12-08-41 ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone 0 1 2 20 21 22 Zone 0 1 2 20 21 22 Division 1 2 1 2 1 2 Ex interface x x x x x x Ex interface x x x x x x Ex interface x x x x x x Installation in x x x Installation in x x x Installation in x x x WebCode 9470D Remote I/O /1

Explosion Protection Global (IECEx) Gas and dust IECEx DEK 12.0044X Ex na ia [ia Ga] IIC T4 Gc [Ex ia Da] IIIC Europe (ATEX) Gas and dust DEKRA 12ATEX0099X E II 3 (1) G Ex na ia [ia Ga] IIC T4 Gc USA (FM) Certifications and certificates Certificates Ship approval Further parameters Installation Further information Safety data Max. voltage U o Max. internal inductance L i 1 channel Max. current I o Max. power P o Max. internal capacity C i Max. connectable inductance L o/capacity C o IIC E II (1) D [Ex ia Da] IIIC in preparation ATEX, IECEx, Brazil (INMETRO), India (PESO), Canada (cfm), Kazakhstan (TR), Rusia (TR), Serbia (SRPS), USA (FM), Belarus (TR) ABS, CCS, ClassNK, DNVGL, LR, RINA, RS in Zone 2, Zone 21, Zone 22 and in the safe area for further interconnections (4, 8 or 16 ), see operating instructions and certificates 9.8 V negligible 10.4 ma 25.5 mw 2.5 nf L o [mh] 280 100 50 20 10 5 2 1 0.5 0.2 0.1 0.02 C o [μf] Ð 0.49 0.56 0.64 0.72 0.81 0.96 1.1 1.3 1.6 2 3.3 IIB/IIIC L o [mh] 1000 100 50 20 10 5 2 1 0.5 0.2 0.1 0.01 C o [μf] Ð 2.6 2.8 3.3 3.7 4.2 5.1 6 7.2 9.3 12 23 2 in parallel Max. current I o Max. power P o Max. internal capacity C i Max. connectable inductance L o/capacity C o IIC 20.8 ma 51 mw 5 nf L o [mh] 100 50 20 10 5 2 1 0.5 0.2 0.1 0.02 C o [μf] 0.3 0.44 0.57 0.67 0.77 0.93 1.1 1.3 1.6 2 3.3 IIB/IIIC L o [mh] 270 100 50 20 10 5 2 1 0.5 0.2 0.1 0.01 C o [μf] Ð 2.3 2.6 3.1 3.6 4.1 5.1 6 7.2 9.3 12 23 Selection Table Version Description Installation Order number Weight kg Digital Input Output Module Note 16 with adjustable parameters for contacts, NAMUR proximity switches or low-power solenoid valves Zone 2 9470/33-16-10 0.275 Please order 2 terminals separately - see Accessories /2 Remote I/O

Technical Data Electrical data Ex i inputs/outputs Number of Inputs Min. input signal ON Max. input signal OFF Operating point Supply voltage Internal resistance Signal Frequency input Max. switching frequency Min. pulse width 16 (in pairs with adjustable parameters as input or output) 16 2.1 ma 1.2 ma 1.65 ma 8.2 V 1 kω EN 60947-5-6 (NAMUR) 8 20 khz (at frequencies > 1 khz the maximum conductor length is reduced, e.g. at 5 khz to approx. 75 m) 25 μs Measuring range 0.1 Hz 600 Hz 1 Hz 3 khz 1 Hz 20 khz Resolution 0.01 Hz 0.05 Hz 0.5 Hz Accuracy 0.1 % 0.1 % 0.1 % Counter Counting range Rotation direction recognition, forward/ backward counter Function Resolution Outputs Application Open-circuit voltage Max. output current Internal resistance Rated operation Output characteristic 8 0... 65535 als UINT16 4 (each two inputs switched in parallel) Up/down counter; Frequency with direction 16 bit / 32 bit 16 Ex i low-power solenoid valves 8.2 V 8.2 ma 1 kω 6 V / 2 ma 9470/3. - Output U[V] 8 7 6 5 4 3 2 1 0 0 2 4 6 8 I[mA] 15284E00 Remote I/O /3

Technical Data Electrical data Signal transmission Max. delay from signal / internal bus Max. delay from frequency input / internal bus < 1 мс Filter without small medium large Frequency 0.1 Hz ( f < 1 Hz 1/f + 1 ms 2/f 3/f 6/f 1 Hz ( f < 10 Hz 1/f + 1 ms 4/f 9/f 18/f 10 Hz ( f < 100 Hz 1/f + 1 ms 8/f 27/f 54/f 100 Hz ( f < 1 khz 1/f + 1 ms 16/f 81/f 162/f 1 khz ( f < 1960 Hz 1.5 ms 32/f 243/f 486/f 1960 Hz ( f < 10 khz 1.5 ms 16.5 ms 124 ms 248 ms 10 khz ( f < 20 khz 1.5 ms 33 ms 372 ms 744 ms f ) 20 khz 1.5 ms 66 ms 372 ms 744 ms Galvanic separation Test voltage acc. to standard EN 60079-11 Between auxiliary ) 1500 V AC power / system components Between two I/O ) 500 V AC modules Between I/O ) 500 V AC / system components Between I/O ) 500 V AC / ground (PA) Electromagnetic Tested to the following standards and regulations: compatibility EN 61326-1 (2006) IEC 61000-4-1 6, NAMUR NE 21 Electrical connection Power supply BusRail Types 9494 Ex i field signals Pluggable, blue terminals, 16-pole, 2.5 mm 2, screw- or spring-type versions with lock Auxiliary power Version Intrinsically safe Ex ia via BusRail Max. current 120 ma consumption Max. power 2.5 W consumption Max. power dissipation 2.5 W Device-specific data Settings Module Diagnostics ON / OFF message Signal Signal type Input / output*) Pulse extension / 0 s / off; 0.6 s / small; 1.2 s / medium; 2.4 s / large *) frequency filter Inverting input/ normal / inverted*) output Line fault ON / OFF monitoring Behaviour in case Replacement value '0'; replacement value '1'; hold (initial value 0); hold (initial value 1) of error Operating mode Counter 16 bit; 0.1... 600 Hz; 1 Hz... 3 khz; 1 Hz... 20 khz; 1 Hz... 20 khz with direction; counter/frequency up/down counter 16 bit; up/down counter 32 bit*) Counter control Run, Stop, Reset Counting event positive slope; negative slope*) *) setting is made for channel pairs /4 Remote I/O

Technical Data Ambient conditions Ambient temperature -40 +75 C (observe operating instructions) Storage temperature -40 +80 C Maximum relative 95 % (without condensation) humidity Semi-sinusoidal shock 15 g (3 shocks per axis and direction) (IEC EN 60068-2-27) Sinusoidal vibration 1 g in the frequency range 10... 500 Hz (IEC EN 60068-2-6) 2 g in the frequency range 45... 100 Hz Mechanical data Degree of protection IP20 (IEC 60529) Module enclosure polyamide 6GF Fire resistance (UL 94) V2 Pollutant class corresponds to G3 Dimensions L = 128 mm, W = 96.5 mm, H = 67 mm Indication LED indication Module requires LED "M/S", blue maintenance Operating state LED "RUN", green Group error LED "ERR", red Function indication Retrievable Manufacturer, Type, hardware revision, software revision, serial number parameters Error indication Module status and Internal bus error primer / redundant alarms No response from IOM Configuration does not correspond to the module Hardware error Excess temperature Slot error Module requires maintenance Signal errors for each channel Signal status bit "0" = signal disturbed; "1" = signal valid Wire breakage < 50 μa input/output Short circuit input/ output < 100 O Note: Contacts require circuitry with 1.2 kω in series and 15 kω in parallel for wire breakage/short-circuit detection. For outputs, wire breakage/short-circuit detection is only possible in the ON state. Mounting / Installation Mounting orientation horizontal or vertical (observe operating instructions) Mounting type on 35 mm DIN rail NS 35/15 (DIN EN 60715) Dimensional drawings (all dimensions in mm / inches) - subject to modifications 68 [2,68] 64 [2,52] 70 [2,76] 128,5 [5,06] 98 [3,86] 96,5 [3,8] 15254E00 Remote I/O /5

Accessories and Spare Parts Designation Figure Description Art. no. Pluggable terminal Labelling strips 02079E00 02077E00 2.5 mm 2 with lock, 16-pole, screw connector, blue, for connecting 162702 the field signals to I/O modules, for intrinsically safe field circuits Labelling: 1... 16 Attention: An additional terminal is necessary for I/O module Series 9470 and 9480. Designation: 17... 32 2.5 mm 2 with lock, 16-pole, screw connector, blue, for connecting 162718 the field signals to I/O modules, for intrinsically safe field circuits Labelling: 17... 32 2.5 mm 2 with lock, 16-pole, spring clamp connection, blue, 162695 for connecting the field signals to I/O modules, for intrinsically safe field circuits, incl. test jacks Labelling: 1... 16 Attention: An additional terminal is necessary for I/O module Series 9470 and 9480. Designation: 17... 32 2.5 mm 2 with lock, 16-pole, spring clamp connection, blue, 162716 for connecting the field signals to I/O modules, for intrinsically safe field circuits, incl. test jacks Labelling: 17... 32 "FB Addr... Mod No..." for pluggable terminal, sheet with 26 strips 162788 05869E00 DIN sheet For label plate on I/O modules; 6 labels on each sheet; print-out using IS Wizard; packaging unit = 20 sheets 162832 09900E00 Partition For mounting between intrinsically safe and non-intrinsically safe connections of the I/O modules, in order to adhere to the required 50 mm distance 220101 Warning sign 15196E00 "Clean modules only with a damp cloth." 162796 05872E00 Resistor error message suppression 17310E00 Resistance value: 5K6 / 0.5 W Suitable for: AIM 9468; DIOM 9470; DIOM 9471; DIOM 9472; DOM 9475 For intrinsically safe circuits (simple apparatus according to EN 60079-11) 244911 We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding. /6 Remote I/O