ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Similar documents
ATC s Mackinac Back to Back. Summary

High Voltage DC Transmission 2

Facilitating Bulk Wind Power Integration Using LCC HVDC

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

ELEMENTS OF FACTS CONTROLLERS

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Fundamental Concepts of Dynamic Reactive Compensation. Outline

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

PRECISION SIMULATION OF PWM CONTROLLERS

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Voltage Source Converter Modelling

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

CONNECTING to the TRANSMISSION GRID in TODAY S RTO WORLD

ESB National Grid Transmission Planning Criteria

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

HVDC High Voltage Direct Current

USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID

EH2741 Communication and Control in Electric Power Systems Lecture 2

VSC Based HVDC Active Power Controller to Damp out Resonance Oscillation in Turbine Generator System

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018

Wind Power Facility Technical Requirements CHANGE HISTORY

Overview of Actuation Thrust

Modelling of VSC-HVDC for Slow Dynamic Studies. Master s Thesis in Electric Power Engineering OSCAR LENNERHAG VIKTOR TRÄFF

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

Design and Simulation of Passive Filter

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

Quanta Technology Advancing the Grid. Flexible AC Transmission System (FACTS) BGE Technology - Application Cases January 4, 2008 Q U A N T A SERVI CES

Overview of Actuation Thrust

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

Reactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors

Experience with Connecting Offshore Wind Farms to the Grid

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

Planning the Next Nelson River HVDC Development Phase Considering LCC vs. VSC Technology

Fault Current Limiter Selection Considerations for Utility Engineers

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Introduction to HVDC VSC HVDC

CONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

VSC Transmission. Presentation Overview. CIGRE B4 HVDC and Power Electronics HVDC Colloquium, Oslo, April LCC HVDC Transmission

INDEPENDENT CONTROL OF MULTI-TERMINAL VOLTAGE SOURCE CONVERTER-BASED HIGH-VOLTAGE DIRECT CURRENT LINK ANALYZING FOR DIRECT CURRENT FAULTS

HVDC AND POWER ELECTRONICS INTERNATIONAL COLLOQUIUM

Recent trends in High Voltage Direct Current (HVDC)Transmission Systems Abstract

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Simulation Study of a Monopole HVDC Transmission System Feeding a Very Weak AC Network with Firefly Algorithm Based Optimal PI Controller

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

IMPORTANCE OF VSC IN HVDC

ABB Power Systems AB Sweden

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

SRI VIDYA COLLEGE OF ENGG AND TECH

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Importance of DC-DC Transformation in Grids of the Future

FACTS devices in Distributed Generation

International Journal of Emerging Technology in Computer Science & Electronics (IJETCSE) ISSN: Volume 8 Issue 1 APRIL 2014.

U I. HVDC Control. LCC Reactive power characteristics

Assessment of Saturable Reactor Replacement Options

AEIJST - July Vol 3 - Issue 7 ISSN A Review of Modular Multilevel Converter based STATCOM Topology

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

DYNAMIC PERFORMANCE OF THE EAGLE PASS BACK-TO-BACK HVDC LIGHT TIE. Å Petersson and A Edris ABB Power Systems AB, Sweden and EPRI,USA

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC

Interline Power Flow Controller: Review Paper

I. INTRODUCTION. Keywords:- FACTS, TCSC, TCPAR,UPFC,ORPD

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012

AORC Technical meeting 2014

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Feasible Series Compensation Applications using Magnetic Energy Recovery Switch (MERS)

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Modeling and Simulation of Wind Farm with STATCOM in PSCAD/EMTDC Environment

Power Quality Compensation by using UPFC

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur

Technical and Economic Analysis of Connecting Nuclear Generation to the National Electricity Transmission System via HVDC Technology.

Southern Company Interconnection Requirements for Inverter-Based Generation

HVDC Solutions for Integration of the Renewable Energy Resources

VSC Control Strategies for Strengthening of AC Systems. A Presentation at: HVDC and FACTS Sub-Committee Garth Irwin August 8, 2018

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Principles of HVDC Transmission

B.Tech Academic Projects EEE (Simulation)

Bipole III Transmission Project

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

FEASIBILITY STUDY REGARDING INTEGRATION OF THE LÆSØ SYD 160 MW WIND FARM USING VSC TRANSMISSION

Copyright 2012 IEEE. Paper presented at Power Africa, 9 July, Johannesburg, South Africa 2012.

Reactive Power Compensation Technologies: State-of-the-Art Review

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Koganti Sri Lakshmi, G.Sravanthi, L.Ramadevi, Koganti Harish chowdary

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Transcription:

21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas M. B. MARZ S. SANKAR* K. D. COPP J. S. RECTOR G. D. IRWIN A. C. MANTY P. M. FAIRLY Electranix American Transmission Co. Black & Veatch Canada USA USA SUMMARY The need for flow control between the upper and lower peninsulas of Michigan at Mackinac substation, near St. Ignace, Michigan, initiated a thorough investigation of available flow control technologies. This investigation determined that Back-to-Back Voltage Source Converter (VSC) HVDC technology best met American Transmission Company s (ATC) requirements. Prespecification studies identified the need for new control techniques due to weak system conditions on both sides of the Back-to-Back Converter Station. The Mackinac HVDC Converter Station is now under construction and expected to be in service in 2014.This paper describes how system characteristics and the capabilities of available flow control technologies determined the selection of VSC technology and the converter station specification. KEYWORDS Flow Control, Back-to-Back HVDC, Voltage Source Converter (VSC), Static Synchronous Compensator (STATCOM) INTRODUCTION The transmission systems in Michigan s eastern Upper Peninsula (UP) and northern Lower Peninsula (LP) were designed to serve load, not transfer power across the UP. However when the eastern UP, which had earlier been served radially from the LP via undersea cables across the Straits of Mackinac, was connected to the rest of the UP, power transfers across the UP became possible. For years, high impedances and a relatively low west to east energy flow bias meant these transfers were low and rarely caused thermal or voltage issues. When issues did arise, they were usually resolved by splitting the system to separate the eastern UP from the rest of the UP as shown in Figure 1. Figure 1: Eastern UP Transmission System Split *sankars@bv.com

West to east flow bias is increasing as the demand for low cost western generation and environmentally friendly sources such as hydro and wind grows to the south and east of Lake Michigan (Fig. 2). Most of this power follows the low impedance path south of Lake Michigan; however, a small portion flows through the higher impedance path north of the lake. Redispatching generation to avoid thermal and voltage issues caused by this northern flow is difficult and expensive because there are few strong sources in the area. Although undesirable because it creates reliability risk when transmission line outages are required for maintenance, splitting the UP to control flows, once an occasional requirement, has now become an all but permanent condition. Building additional higher voltage lines to relieve the thermal and voltage issues created by the flow across the UP was investigated and found to be prohibitively expensive and unachievable in the required timeframe, making flow control the preferred alternative. Figure 2: Flow Bias MACKINAC POWER FLOW CONTROLLER REQUIREMENTS In addition to other existing system constraints the power system near Mackinac also has a very low available short circuit current level. This requires the flow control technology implemented to operate under low fault conditions and not contribute to voltage control issues, or create the need for additional dynamic reactive support. It was also desired that whatever flow control technology was chosen, it should be a long term fix and system changes should not make the flow control device obsolete. Although the flow across the Straits of Mackinac is presently limited to less than 100 MW, the flow controller was designed for up to 200 MW to account for future growth and improvements. FLOW CONTROL TECHNOLOGIES Several flow control technologies were considered for the Mackinac Project [1]. They included (1) series reactors, (2) phase shifting transformers (PST), (3) variable frequency transformers (VFT), (4) Line Commutated Converter (LCC) HVDC (5) Capacitor-Commutated Converter (CCC) HVDC and (6) Voltage Source Converter (VSC) HVDC. Series Reactors Series reactors, more often applied on distribution systems, increase the impedance of one path to decrease the flow on that path. Their advantages include simplicity and cost. The disadvantages include (1) reactive losses and thereby requiring additional shunt reactive power compensation (2) a lack of adjustability (voltage regulation), and (3) potential obsolescence due to system changes. A fixed (or a variable tapped) series reactor solution is not a viable option at Mackinac because of the its limitation on the power flow controllability and in addition would add reactive losses in an area where low short circuit capability already makes voltage control challenging. A Unified Power Flow Controller (UPFC) was not considered as one of the alternatives. Phase Shifting Transformers (PST) PSTs control active power flow by changing the phase angle difference across the transformer. This is done by mechanical switches that change the tap on a regulating winding. These switches require periodic inspection, maintenance and total replacement after a given number of operations, which could be a concern if used to respond hourly to system 2

flows. Designed for a specific maximum angle deviation, multiple phase shifters in series might be necessary to achieve the phase shift required at Mackinac. Studies have shown that either additional phase shifters might be required or the control flexibility will be limited after several years due to increase in through flows. In addition, the PST would be slow to re-adjust the flows to avoid potential voltage collapse during major contingencies described later in this paper. Variable Frequency Transformers (VFT) A VFT is essentially a doubly fed electric machine with one connection to the stator and the other to the rotor [2]. Changing the rotor position changes the phase angle and power flow across the device making it act as a continuously adjustable phase-shifting transformer with the added benefits that it can smoothly ramp from one power level to another (no steps). While a VFT allows for reactive power flow, it cannot use reactive power to regulate voltage. Although a VFT has some unique advantages, it would require adding dynamic reactive power compensation to keep system voltage within a reasonable range at a part of the system as weak as Mackinac. A very limited number of projects using this technology are in commercial operation. Line Commutated Converter (LCC) HVDC LCC HVDC has been in commercial use since the 1950s, primarily to transfer power over long distances economically or on cables without the charging current and voltage control issues associated with AC cables. Modern LCC HVDC installations use thyristors that use a short-duration positive current pulse to the device gate to turn it on (provided it is in forward-blocking state). The device is turned off when the gate signal is removed and the current passing through the thyrister hits a zero-crossing. LCC HVDC can be expensive because it requires special converter transformers, consumes reactive power up to 50 percent of its rating and requires harmonic filtering. It also requires a minimum short circuit current capacity, at least twice the converter rating, at the point of interconnection. LCC HVDC is not an option in this case because the short circuit capacity at Mackinac is too low and would require additional synchronous condensers on both sides of the converter station which would increase project losses and costs. Capacitor-Commutated Converter (CCC) HVDC CCC HVDC was developed to address the short circuit limitations of LCC HVDC [3]. CCC uses series capacitors inserted into the AC line connections, either on the primary or secondary side of the converter transformer, to partially offset the commutating inductance of the converter and reduce fault current requirements. This also allows for a smaller extinction angle, reducing reactive power requirements. The ability of CCC HVDC to operate under very low short circuit conditions is limited and pushing this technology to its limits can create cost and reliability concerns. Also, the need for reactive power compensation, although reduced compared to LCC HVDC, would probably require additional dynamic reactive power compensation to maintain system voltage at an acceptable level at Mackinac. Voltage Source Converter (VSC) HVDC The development of high power self-commutating insulated gate bipolar transistors (IGBT) has led to the development of STATCOMs and flexible VSC HVDC devices [4]. VSC HVDC can independently control voltages at each HVDC terminal separate from the active power order; also, with the DC connection between the terminals out of service, it can be operated as two independent STATCOM devices. VSC HVDC has no minimum short circuit capacity requirements, can be used to black start one side from the other and does not require specially designed converter transformers. A DC bus fault creates a current path thru the anti-parallel diodes and the fault current is limited only by the system impedance and the converter transformer impedance. Also, when the VSC is energized under zero DC voltage, there would be in-rush currents and will have to be limited by pre-insertion resistors. IGBT controllability makes it possible to serve an island (a system whose only connection to the grid is through the HVDC) and has allowed for improved HVDC control methods to be developed. VSC HVDC converters use either series connected pulse width modulation techniques or multilevel switching to achieve lower losses, minimal distortion and an easily scalable design. VSC HVDC is generally more expensive than LCC or CCC HVDC, has increased control flexibility, and better control performance under very weak system conditions. 3

TECHNOLOGY DECISION Voltage Source Converter (VSC) HVDC technology was chosen for the Mackinac project. The decision was primarily driven by three conditions: (1) the low short circuit current available in the area, (2) the need to consider voltage regulation, power flow controllability and reactive power consumption, and (3) the robustness of the solution. The minimum Short Circuit Ratio (SCR) at Mackinac is about 0.6, which makes VSC HVDC more suitable than the other HVDC technologies. Other concerns included cost, maintenance requirements, operation under fault and outage conditions, and losses. No technology was best at meeting all of these issues and compromises, especially the cost, were necessary. Although it was one of the more costly solutions, VSC HVDC addressed all three major project concerns listed above. Maintenance, control complexity, weak system operation, interaction with other power electronic controls and potential sub-synchronous resonance interaction were still concerns. Maintenance is expected to be three to seven days annually. This could be reduced as more experience with the equipment is gained. Figure 3 shows the existing system and the proposed flow controller scheme. Figure 3: Existing and the proposed scheme VSC CONTROL CHALLENGES UNDER CONTINGENCIES The eastern UP power system is effectively connected to the rest of the ATC system via two 138 kv lines and one 69 kv line. Once the HVDC converter station is implemented between the UP and LP systems, any N-1-1 or N-2 outage of these circuits in the UP would make eastern UP either islanded (connected to the rest of the system only through the Mackinac HVDC) or quasi-islanded (connected to the rest of the system through the Mackinac HVDC and a single 69 kv connection). Extensive power flow, transient stability and PSCAD studies performed during the pre-specification stage indicated that the proposed VSC HVDC converters should have the functionalities to address the following issues associated with the islanding and quasi-islanding situations: For UP faults that result in a trip of 138 kv paths from the Converter Station to the western part of the UP, a high speed change in the VSC power order (which may result in a power reversal) based on the pre-fault 138 kv flows would be required to maintain stability and to avoid voltage collapse. Studies (with generic VSC models) indicated that where two or more 69 kv paths remain, the system showed acceptable performance providing the VSC real power flow is quickly modified to make up the pre-fault 138 kv power flow. Cases where only one 69 kv line remains after the 138 kv fault (connecting the eastern UP to the western UP) may show voltage instabilities until the Converter Station is converted to full island mode, after which acceptable recovery was demonstrated. 4

To implement the above functions, it was realized that extensive communication signals (circuit breaker statuses and power flow values) from many substations may be required so as to determine the DC power levels following contingencies. Alternatively, an automatic power reduction or reversal scheme based on power / angle characteristics emulating an AC line was also envisioned, which would use locally sensed signals and not dependent on the remote communication signals. Accordingly, during the bid stage, the bidders were encouraged to study the islanding and the quasi-islanding issues and offer solutions based on locally measured signals. CONVERTER STATION SPECIFICATION Mackinac HVDC converter station is designed for 200 MW bi-directional power transfer and also to provide reactive power (+/- 100 MVAR) for local voltage support during steady state and dynamic conditions. Figure 4 shows the P-Q capability of the VSC converters specified for the Mackinac project. Positive reactive power indicates the reactive power supplied by the converters and the negative reactive power indicates the reactive power absorbed by the converters. In addition, the converter station is being designed with the following features: When not transferring power, the two VSC converters can be operated as two individual STATCOM or as one STATCOM while the other converter is out of service. During certain contingencies, the converter connected to the UP side may be left connected to an islanded system with this converter designed to operate at fixed frequency / voltage mode with droop settings. Black start capability to start up a passive ac system network in UP 300 200 100 0 150 100 50 100 0 50 100 150 200 300 Reactive Power (MVAR) Power (MW) P Q Capability Figure 4: P-Q Capability of the VSC Converters DESIGN AND CONSTRUCTION PROGRESS A turnkey contract for Mackinac HVDC Converter Station was awarded to ABB in early 2012 and the project is expected to be in service by the third quarter of 2014. The voltage source converters are of symmetrical monopole type and a simplified one line diagram the converter station is shown in Figure 5. The design studies which involve new control concepts to avoid the need for complex communication signals are currently being finalized by ABB. These control designs will be reported in future publications. 5

Figure 5: Simplified One Line Diagram of Mackinac HVDC Converter Station (With permission from ABB) The project is located on a 40 acre site in the Upper Peninsula of Michigan, three miles north of the Mackinac Straits, in St. Ignace, Michigan. The station was designed for temperature extremes ranging from 102 F to -50 F and a snowfall up to 200" annually. The station will be unstaffed and controlled and monitored remotely at the ATC operations facilities in Pewaukee and Madison, WI. Local, trained technicians will provide first response troubleshooting and monthly inspection. The converter building housing the valves, reactors, cooling and control equipment is approximately 300 feet long, 100 feet wide, two stories tall, and is divided into four valve halls (a +DC and DC for each converter), two reactor halls and a control building. CONCLUSION The decision to use VSC HVDC technology to control the flow between the Upper and Lower Peninsulas of Michigan was made after a thorough evaluation of available flow control technologies and their compatibility with the system at Mackinac. While all of the technologies have advantages, disadvantages and applications that could make each the most appropriate choice, the unusual conditions at Mackinac made VSC technology the best choice for this application on mainly the technical advantages. The condition that drove the decision was primarily the weak system conditions at Mackinac, which precluded some of the flow control options and made the reactive power capabilities of the VSC particularly attractive. BIBLIOGRAPHY [1] M. B. Marz. Mackinac VSC HVDC Flow Control Project Design Minnesota Power Systems Conference, November 6-8, 2012. Available at: http://www.cce.umn.edu/documents/cpe- Conferences/MIPSYCON-Papers/2012/MackinacVscHvdcFlowControlProjectDesign.pdf [2] Merkhouf, A, Upadhyay, S, and Doyon, P, Variable Frequency Transformer An Overview, IEEE Power Engineering Society General Meeting, 2006. [3] Bahrman, M.P., HVDC Transmission Overview, IEEE Transmission and Distribution Conference and Exposition, 2008. [4] Flourentzou, N, Agelidis, V.G and Demetriades, G.D, VSC Based HVDC Power Transmission Systems: An Overview, IEEE Transactions on Power Electronics, Vol. 24, Issue 3, 2009. 6