Mitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System

Similar documents
Effective Harmonic Mitigation with Active Filters

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Three-Phase Multi-Pulse Converter with Phase-Shifting Transformer

HARMONIC MITIGATIONCASE STUDY

Understanding Harmonics

Literature Review for Shunt Active Power Filters

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Electromagnetic Harmonic Filters Technical Guide

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Distortion Evaluations

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Technical Paper. Harmonic Distortion in Data Centers

Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3

22.0 Harmonics in Industrial Power Systems

NJWA - Harmonics and Drives Proper System Design

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

Alternators Reactance for Nonlinear Loads

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Harmonic Distortion Effects and Mitigation in Distribution Systems

Study of Harmonics and THD of Nine Phase PWM Inverter Drive with CLC Filter for motor drive applications

Unit 29 Three-Phase Transformers

Voltage and Current Waveforms Enhancement using Harmonic Filters

COMPARISON OF POWER QUALITY SOLUTIONS USING ACTIVE AND PASSIVE RECTIFICATION FOR MORE ELECTRIC AIRCRAFT

Power Quality improvement of a three phase four wire system using UPQC

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Analysis of Harmonic Distortion in Non-linear Loads

Understanding Input Harmonics and Techniques to Mitigate Them

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Harmonic Mitigation in AC DC Converters for Induction Motor Drives by Vector Controlled

Harmonic Reduction and Power Factor improvement in three phase three wire system by using Passive Filters

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number

IMPACT OF VARIABLE FREQUENCY DRIVES ON ELECTRICAL SYSTEM

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Power Quality Analysis in Power System with Non Linear Load

Harmonic Mitigating Transformer - Technical Guide

New power tools provide quality and efficiency By

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

AN EQUIVALENT CIRCUIT MODEL FOR A THREE PHASE HARMONIC MITIGATING TRANSFORMER

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

International Journal of Advance Engineering and Research Development. 18 Pulse Uncontrolled Rectifier

Harmonics Elimination Using Shunt Active Filter

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Selective Harmonic Elimination (SHE) for 3-Phase Voltage Source Inverter (VSI)

Thyristorised Automatic Power Factor

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Harmonic Filters for Single Phase Equipment

Study of Power Factor Correction in Single Phase AC-DC Converter

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

THE ANALYSIS OF MAGNIFICATION OF NEUTRAL CURRENT IN THE PRESENCE OF POWER QUALITY PROBLEMS

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter

Harmonic control devices. ECE 528 Understanding Power Quality

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 4 HARMONICS AND POWER FACTOR

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Alternator winding pitch and power system design

Thermal Imaging, Power Quality and Harmonics

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Harmonics, its Mitigation & Result of Case study of Spinning Mill

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

7/15/2002 PP.AFD.08 1 of 28

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Shunt Active Power Filter for Compensation of System Harmonics

International Journal of Research Available at

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Power Quality Improvement using Shunt Passive Filter

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Power Factor & Harmonics

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Tuningintobetter power quality

CHAPTER 3. NOVEL MODULATION TECHNIQUES for MULTILEVEL INVERTER and HYBRID MULTILEVEL INVERTER

International Journal of Engineering Research and General Science Volume 5, Issue 2, March-April, 2017 ISSN

Eyenubo, O. J. & Otuagoma, S. O.

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

Study and analysis of THD and content of Harmonics in Three Phase PWM Inverter with Filters.

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Power Quality Improvement in Induction Motor Drive using 24-Pulse AC-DC Converter Employing Pulse Multiplication Technique

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

Transcription:

Mitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System Muhammad Abid 1, Tehzeeb-ul-Hassan 2, Tehseen Ilahi 3 1 National University of Computer and Emerging Sciences, Lahore, Pakistan; muhammad.abid@nu.edu.pk 2 University of Lahore, Lahore, Pakistan; tehzibulhassan@gmail.com 3 University of Engineering & Technology, Lahore, Pakistan; engineer_tehseen@yahoo.com Abstract----Harmonics are present in power systems due to the rapid switching of nonlinear loads. These harmonics have several adverse effects on a power system infrastructure, such as saturation of transformers, overheating of neutral cables, reduction of torque in rotating machines, malfunctioning of switchgears and protective relays, etc. Thus, it is important to analyze and mitigate these harmonics. Several harmonic mitigation techniques (HMTs) have been proposed in the research literature. This paper presents the simulation and analysis of a phase shifting technique for harmonic mitigation. Results from MATLAB simulations of the proposed technique have been included as part of this paper. Keywords---total harmonic distortion; harmonic mitigation techniques; phase shifting techniques; triplens. I. INTRODUCTION Harmonics in power systems are sinusoidal components of periodic waveforms that have frequencies equal to an integral multiple of the fundamental frequency. The frequency of the harmonic component, f h, is related to the fundamental frequency by the following formula: f h = (h) (fundamental frequency) (1) where h is an integer. Due to the use of power electronic devices such as MOSFETs, IGBTs, GTOs, etc., the nonlinear load on a power system is increased. Nonlinear loads are those in which the current waveform does not resemble the applied voltage waveform [1]. Single-phase nonlinear loads produce harmonics of odd multiples of the fundamental frequency in which the most severe are the "triplen". Odd multiples of the 3 rd harmonic of the fundamental frequency are defined as triplen harmonics. Examples are the 3 rd, 9 th, 15 th, 21 st, etc., harmonics. Triplen harmonics are zero sequence harmonics, unlike the fundamental, which is a positive sequence. As a result, the magnitude of these currents on the 3 phases are additive in the neutral. Unless the neutral is sufficiently oversized, theses large currents can present a fire hazard because of overheating [2]. Three phase nonlinear loads primarily produce 5 th and 7 th harmonics. These harmonics are the main cause of distortion, overheating of the neutral conductor and malfunctioning of control devices [3]-[4]. Three phase harmonics also cause serious problems in the power system equipment, for example, increased losses in motors and transformers, poor power factor, skin effect in conductors and unexpected tripping of protection equipment, etc. II. RELATED WORK There are different harmonic mitigation methods available, each with technical advantages and disadvantages. Examples are harmonics filters (passive, active and hybrid), line reactors, and K-factor transformers. Passive filters are the cheapest form of filters applicable for fixed frequency [5]. Active filters are difficult to design and more expensive than passive filters, but have several advantages over passive filters [6]. Hybrid power filters are a combination of active and passive filters. They provide a suitable solution to mitigate harmonics and are suitable for heavy loads [7]. Line reactors and K-factor transformers may be used to overcome the problem of harmonics [8]. The connection type of a feeding transformer also helps in reducing the harmonics in a power system. The harmonics injected by nonlinear 123

loads may be canceled at the point of common coupling (PCC). The concept is to connect nonlinear loads through phase shifting transformer such as Dy 1, Dy 5, Dy 11 that are used with harmonic loads [9]-[10]. An excellent review of existing mitigation techniques can be found at [11]. Another interesting and relevant discussion is available at [12]. III. PHASE SHIFT CONCEPT FOR MITIGATION OF HARMONICS Fig. 2: Phasor diagram of a PST with load Mitigation of harmonics by employing phase shifting transformers (PSTs) has also been proposed in the literature [13]. One way is to connect the primary winding in delta and the secondary winding in star with a -30 phase shift (called a Dy11 transformer) [14]. Similarly a Dy1 transformer having primary winding connected as delta and the secondary as star connected with 30 phase shift, and a Dz0 transformer with primary winding delta and secondary winding in zigzag connected with 0 phase shift can be used as PSTs [13]. In Figure 2 above, the parameters are as follows: I Load current V s (a) Source voltage (advance) V s (r) Source voltage (retard) V L Load voltage when loaded * V L Load voltage (no-load condition) β Transformer load angle -α Phase angle shift (retard) +α phase angle shift (advance) The load phase angle β can be calculated using the following equation: U U - (3) 30 0 The load phase angles of the transformers α* ( a ) and α* ( r ) can be obtained as phase angle advance, defined as: V V W Fig. 1: Phase shift between source and load Figure 1 shows the vector representation of a phase shifting transformer with a 30 phase shift to eliminate harmonics. In this figure, U, V and W are the voltage vectors of a three phase balanced system and U, V and W are the vectors after a 30 phase shift. W α * ( a) = α- β (4) The load angle, as phase angle retard, is defined as: α * (r ) = -(α β ) (5) To achieve an advanced phase angle α * ( a) under load, the no load phase angle α has to be chosen properly taking into consideration the phase angle of the phase shifting transformer. A. Mitigation of +ve & -ve sequence harmonics Harmonics such as the 7 th, which rotate with the same sequence as the fundamental, are called positive sequence. Harmonics such as the 5th, which rotate in the opposite sequence as the fundamental, are called negative sequence. Triplen harmonics which do not rotate at all 124

because they are in phase with each other, are called zero sequence [15]. Positive sequence harmonics 7 th, 13 th and 19 th act against negative sequence harmonics 5 th, 11 th and 17 th to mitigate lower order harmonics. These positive sequence harmonics require a phase shift of 180 /7= 26, or approximately 30 to mitigate the 7 th order harmonics. In case of the 13 th order harmonics, 180 /13=14, or approximately a 15 phase shift is required. In the same way, a 30 phase shift is required for 5 th order harmonics of the negative sequence and a 15 phase shift is required for the 11 th order harmonics of the negative sequence.. B. Mitigation of zero sequence harmonics All triplens (3rd and multiple of third harmonics) are zero sequence harmonics. These harmonics act against each other in a three phase system to achieve mitigation. A 60 phase shift (180 /3=60 ) is required to mitigate lower order zero sequence harmonics in three phase power system. TABLE I. HARMONICS AND THEIR PHASE SEQUENCES IN A THREE PHASE SYSTEM Harmonics Order Fundamental (50Hz) Phase-I (R) 3 rd R 3 0 5 th R 5 0 7 th R 7 0 9 th R 9 0 11 th R 11 0 13 th R 13 0 Phase-II (Y) Phase-III (B) R Y B 0 120 240 Y 3 120 (360 = 0 ) Y 5 120 (600-720 = -120 ) Y 7 120 (840-720= 120 ) Y 9 120 (1080= 0 ) Y 11 120 (1320-1440 = - 120 Y 13 120 (1560-1440 = 120 B 3 240 (720 = 0 ) B 5 240 = 1200 (1200-1440 = -240 B 7 240 = 1200 (1650-1440 = 240 B 9 240 2160 = 0 B 11 240 (2640-2400 = 240 B 13 240 (3120-2880 = 240 Phase Sequence R-Y-B No Phase Rotation B-Y-R (-Ve) R-Y-B (+ Ve) No Phase Rotation B-Y-R (-Ve) R-Y-B (+ Ve) Table I illustrates that the three phases R-Y-B are 120 0 apart from each other in balanced three phase power system network. In a balanced three phase system, zero sequence harmonics have no phase rotation, 5 th & 11 th harmonics have negative phase sequence and 7 th & 13 th harmonics have positive phase sequence. So negative and positive sequences act against each other and cancel the unnecessary harmonics. Table I also shows that each phase R-Y-B acts against the similar phase with opposite angle to mitigate unnecessary harmonics. For example, phase Red of the 5 th harmonic acts against phase Red of the 7 th harmonic to cancel the undesired effects. The same applies to the Yellow and Blue phases. Figure 3 shows the schematic arrangement of the technique under study. Four motors are fed through variable frequency drives (nonlinear loads) and these VFDs are fed from the utility supply through phase shifting transformers or PSTs. Winding connections of phase shifting transformer are arranged as follows: PST-1 primary winding is delta connected and secondary winding is ig ag with phase shift. PST-2 primary winding is star connected and secondary winding is zigzag with a zero phase shift. Similar connections are required for PST-3 and PST-4. The phase shift between these transformers is 15 degrees. Fig. 3: Schematic diagram of proposed technique 125

IV. SIMULATION AND RESULTS Fig. 4: Simulation schematic of the proposed technique Figure 4 shows the MATLAB simulation model of the phase shifting technique under discussion. Four nonlinear loads are fed through four phase shifting transformers each having an appropriate phase angle. The desired phase shift is achieved by changing the vector group of the associated PST in the MATLAB model. Different configurations of phase shifting transformers for harmonic mitigation have been simulated such as Y-Δ, Y-Y/ Y-Δ, Zig-Zag/4Y & Zig-Zag/2Y- 2Δ. From this simulation model, it is clear that the implementation of a single phase shifting transformer with a particular load does not reduce harmonics. Harmonics are reduced when two or more phase shifting transformers are employed with similar nonlinear loads. The phase shifting is achieved by taking harmonics from different sources, shifting one source of harmonics 180 0 from other and then combining them; if the amplitude of harmonics is equal then the harmonics are cancelled. As shown in Figure 5 and Figure 6, the total harmonic distortion, or THD, is reduced up to 3.79%. All triplen harmonics are cancelled. 126 Fig. 5: Results of proposed simulation model Fig. 6: Graphical representation of harmonic spectrum

When two transformers with a -30 and 0 phase shift are used, the 3 rd harmonic currents are cancelled and the voltage distortion is reduced. TABLE II. COMPARISON OF RESULTS AT DIFFERENT PHASE ANGLES Harmonic THD-I THD-III Order (No Phase (Appropriate (Odd) Shift) Phase Shift) THD-II (180 0 Phase Shift) 3 9.07 % 0.01% 0.00% 5 6.79 % 12.69% 0.01% 7 3.79% 8.69% 0.01% 9 5.22% 0.01% 0.0.1% 11 2.42% 6.91% 0.01% 13 3.78% 5.16% 0.01% 17 1.01% 1.94% 0.01% 19 1.95% 1.42% 0.01% According to the analysis of the simulated results, it is clear that the most dominant harmonics, the 5 th and the 7 th, are cancelled at the point of common coupling (PCC) and not transferred to the power system network. Besides, since there are no 5 th & 7 th harmonics, the occurrence of the system resonance at these frequencies is avoided. Moreover, the results are the same for 17 th and 19 th harmonics, etc. The remaining harmonic components are below the recommended standard of IEEE 519 limits and IEC 61000-4-7. V. CONCLUSIONS In this research paper, the phase shifting technique for mitigation of harmonics is explored. The simulation results illustrate that mitigation of the lower order odd harmonics (5 th, 7 th, 11 th & 13 th ) is achieved in the system of Figure 4. The results also show that harmonics produced by nonlinear loads can be cancelled at the PCC by combining the waveforms after phase shift. The simulation results concur with the IEEE standards 519-1992 for harmonic limitation, i.e., THD V 3% for special application, 5% for general systems and 10 % for dedicated systems. REFERENCES [1] WAI-KAI CHEN EDITOR The Electrical Engineering Handbook [2] http://www.hersheyenergy.com/ harmonics.html 127 [3] Hussein A. Attia, M. El-Metwally and Osama M. Fahmy Harmonic Distortion Effects and Mitigation in Distribution Systems Journal of American Science, vol 6, pp 10, 2010. [4] Uma P Bala Raju, Bala Krishna Kethineni, Rahul H Shewale & Shiva Gourishetti, Harmonic Effects and its Mitigation Techniques for a Non-Linear Load International Journal of Advanced Technology & Engineering Research (IJATER), Volume 2, Issue 2, May 2012. [5] Sindhujah L. J. Parthasarathy and V. Rajasekaran, Harmonic mitigation in a rectifier system using hybrid power filter, International Conference on Computing, Electronics and Electrical Technologies (ICCEET), Kumaracoil,pp 483-484, March,2012. [6] Sekar, T. C. and Rabi, B.J. A review and study of harmonic mitigation techniques International Conference on Emerging Trends in Electrical Engineering and Energy Management (ICETEEEM), Chennai, pp 93-97, December, 2012 [7] Akagi H, (2005) "Active harmonic filters", Proceedings of the IEEE, vol. 93, No.12. [8] Xiaodong Liang Influence of Reactors on Input Harmonics of Variable Frequency Drives Industrial and Commercial Power Systems Technical Conference (I & CPS) IEEE, Baltimore, MD, vol. 47, No. 5, November, 2011. [9] G. M. Carvajal, G O Plata, W. G. Picon, J. C. C. Velasco, Investigation of Phase shifting transformers in distribution systems for harmonics mitigation, IEEE Power System Conference (PSC), pp 1-5, March 2014. [10] http://www.eng-tips.com/ viewthread.cfm?qid=51476. [11] Hussein A. Kazem, Harmonic Mitigation Techniques Applied to Power Distribution Networks, Advances in Power Electronics,

vol. 2013, Article ID 591680, 10 pages, 2013. doi:10.1155/2013/591680 [12] Skjong, E.; Molinas, M.; Johansen, T.A., "Optimized current reference generation for system-level harmonic mitigation in a diesel-electric ship using non-linear model predictive control," in Industrial Technology (ICIT), 2015 IEEE International Conference on, vol., no., pp.2314-2321, 17-19 March 2015. [13] Malagon Carvajal, G, Ordonez Plata, G.; Picon, W.G and Chacon Velasco, J.C. Investigation of Phase shifting transformers in distribution systems for harmonics mitigation IEEE, Power System Conference (PSC), Clemson, SC, 2014. [14] http://electrical-engineering-portal.com/ understanding-vector-group-transformer-1. [15] http://www.allaboutcircuits.com/ textbook/alternating-current/chpt- 10/harmonic-phase-sequences/ 128