[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Similar documents
Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

A New Control Scheme for Power Quality Improvement with STATCOM

A Review on Improvement of Power Quality using D-STATCOM

Power Quality Enhancement of Grid Connected Non-Conventional Energy System using STATCOM with PI Controller

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Power Quality Improvement in Distribution System Using D-STATCOM

Mitigating Voltage Sag Using Dynamic Voltage Restorer

International Journal of Modern Engineering and Research Technology

STATCOM BASED ON REDUCTION OF PQ ISSUES IN MICRO GRID APPLICATION SYSTEMS

ISSN Vol.03,Issue.11, December-2015, Pages:

Power Quality enhancement of a distribution line with DSTATCOM

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Designing Of Distributed Power-Flow Controller

e-issn: p-issn:

Improvement in Power Quality of Distribution System Using STATCOM

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

D-STATCOM FOR VOLTAGE SAG, VOLTAGE SWELL MITIGATION USING MATLAB SIMULINK

Investigation of D-Statcom Operation in Electric Distribution System

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Volume I Issue VI 2012 September-2012 ISSN

Power Quality Compensation by using UPFC

SIMULATION OF D-STATCOM IN POWER SYSTEM

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Power Quality Improvement By Using DSTATCOM Controller

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Voltage Control and Power System Stability Enhancement using UPFC

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Analysis and Performance of PID Based STATCOM for Voltage Variations

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices

A New ISPWM Switching Technique for THD Reduction in Custom Power Devices

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Power Quality Improvement using Active shunt Power filter using PI Controller

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

Cascaded Two Level Electrical Converter-Based Multilevel STATCOM for High Power Utilization

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

POWER QUALITY IMPROVEMENT IN A GRID CONNECTED WIND ENERGY CONVERSION SYSTEM USING DYNAMIC VOLTAGE RESTORER

Performance of DVR & Distribution STATCOM in Power Systems

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

VSC Based HVDC Active Power Controller to Damp out Resonance Oscillation in Turbine Generator System

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

FUZZY LOGIC CONTROLLER BASED UPQC FOR POWER QUALITY MITIGATION IN GRID CONNECTED WIND ENERGY CONVERSION SYSTEM

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

Power Quality Improvement using Hysteresis Voltage Control of DVR

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

Comparative Analysis of Multiple-pulse VSC-Based STATCOM s for Voltage-Dip Mitigation

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Mitigation of Voltage sag and Harmonics in Grid connected Wind Energy System using STATCOM

ISSN: [Yadav* et al., 6(5): May, 2017] Impact Factor: 4.116

Level Shifted Pulse Width Modulation in Three Phase Multilevel Inverter for Power Quality Improvement

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

Mitigation of Faults in the Distribution System by Distributed Static Compensator (DSTATCOM)

Control of Shunt Active Power Filter for Improvement of Power Quality

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Power Control and Quality Management in DG Grid Interfaced Systems

Power Quality Improvement In Grid Connected Wind Energy System

Transcription:

IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech (Power System) Bharati Vidyapeeth Deemed University COE Pune. Electrical Engineering Dept. Bharati Vidyapeeth Deemed University COE Pune. ABSTRACT The wind generated power always vary irregularly due to its time varying nature and causing stability problems. This weak interconnection of wind generating source to the electrical grid affects the power quality and reliability. Here we have designed static compensator (STATCOM) using Voltage Source Inverter to reduce voltage sags, swells, transients, harmonics hence enhance power quality of the system. We have used Pulse Width modulation technique to control voltage source converter. The STATCOM is modeled and its performance is simulated and load, source voltages and currents waveforms are taken and Total Harmonic Distortion (THD) is calculated by using MATLAB simulation. The development of the grid co-ordination rule and the scheme for improvement in power quality norms as per IEC-standard on the grid has been presented. KEYWORDS: Wind energy, STATCOM, VSC, PWM, THD. INTRODUCTION In recent years, wind energy has become one of the most important and promising sources of renewable energy, which demands additional transmission capacity and better means of maintaining system reliability. To have sustainable growth and social progress, it is necessary to meet the energy need by utilizing the renewable energy resources like wind. The need to integrate the renewable energy like wind energy into power system is to make it possible to minimize the environmental impacts. Wind energy conversion systems are the fastest growing renewable source of electrical energy having tremendous environmental, social, and economic benefits. Power Quality is defined as power that enables the equipment to work properly. A power quality problem can be defined as any deviation of magnitude, frequency, or purity from the ideal sinusoidal voltage waveform. Good power quality is benefit to the operation of electrical equipment, but poor power quality will produce great harm to the power system. However, the generated power from wind energy conversion system is always fluctuating due to the fluctuation nature of the wind. Therefore injection of the wind power into an electric grid affects the power quality. The important factors to be considered in power quality measurement are the active power, reactive power, variation of voltage, flicker, harmonics, and electrical behavior of switching operation. In this proposed scheme Static Synchronous Compensator (STATCOM) is connected at a point of common coupling with a battery energy storage system (BESS) to mitigate the power quality issues. Therefore STATCOM provides Reactive Power support to wind generator and load. The battery energy storage is integrated to sustain the real power source under fluctuating wind power. The STATCOM control scheme for the grid connected wind energy generation system for power quality improvement. Power Quality (PQ) related issues are of most concern nowadays. The widespread use of electronic equipment, such as information technology equipment, power electronics such as adjustable speed drives (ASD), programmable logic controllers (PLC), energy-efficient lighting, led to a complete change of electric loads nature. These loads are simultaneously the major causers and the major victims of power quality problems. Due to their non-linearity, all these loads cause disturbances in the voltage waveform. [215]

In this seminar topic there will be the analysis of factors which are responsible for the power quality problems in the wind energy conversion system and implementation of proper control scheme for power quality improvement in the wind energy conversion system connected to the grid. The paper is organized as follows. The chapter 2 introduces the power quality standards, issues and its consequences of wind turbine. The chapter 5 introduces the grid coordination rule for grid quality limits. The chapter 6 describes the topology for power quality improvement. TOPOLOGY FOR PQ IMPROVEMENT The STATCOM based current control voltage source inverter injects the current into the grid in such a way that the source current are harmonic free and their phase-angle with respect to source voltage has a desired value. The injected current will cancel out the reactive part and harmonic part of the load and induction generator current, thus it improves the power factor and the power quality. To accomplish these goals, the grid voltages are sensed and are synchronized in generating the current command for the inverter. The proposed grid connected system is implemented for power quality improvement at point of common coupling as shown in Fig. 1. The grid connected system in Fig. 1, consists of wind energy generation system and STATCOM with VSC Fig. 1 STATCOM OPERATION The STATCOM (or SSC) is a shunt-connected reactive power compensation device that is capable of generating and/ or absorbing reactive power and in which the output can be varied to control the specific parameters of an electric power system. It is in general a solid-state switching converter capable of generating or absorbing independently controllable real and reactive power at its output terminals when it is fed from an energy source or energy-storage device at its input terminals. Specifically, the STATCOM considered in this chapter is a voltage-source converter that, from a given input of dc voltage, produces a set of 3-phase ac-output voltages, each in phase with and coupled to the corresponding ac system voltage through a relatively small reactance (which is provided by either an interface reactor or the leakage inductance of a coupling transformer). The dc voltage is provided by an energy-storage capacitor. A STATCOM can improve power-system performance in such areas as the following: a. The power-oscillation damping in power transmission systems. b. The dynamic voltage control in transmission and distribution systems. c. The transient stability. d. The voltage flicker control. GRID CO-ORDINATION RULE The rules for realization of grid operation of wind generating system at the distribution network are defined as-per IEC-61400-21. Voltage Rise (Δv): [216]

The voltage rise at the point of common coupling can be approximated as a function of maximum apparent power Smax of the turbine, the grid impedances R and X at the point of common coupling and the phase angle β given in Eq.1 Δv = Smax (Rcos β -Xsin β )/ V (1) Where, Δv voltage rise Smax maximum apparent power β phase difference. V nominal voltage of grid The limiting voltage rise value is < 2%. Voltage Dips (d): The voltage dips is due to startup of wind turbine and it causes a sudden reduction of voltage. It is the relative % voltage change due to switching operation of wind turbine. The decrease of nominal voltage change is given in Eq. 2. d=k u S n /S k (2) Where, d is relative voltage change, S n is rated apparent power. S k is short circuit apparent power. K u is sudden voltage reduction factor. The acceptance voltage dips limiting value is 3%. C. Harmonics : The harmonic distortion is assessed for variable speed turbine with an electronic power converter at the point of common connection. The total harmonic voltage distortion of voltage is given as in Eq. Where, V n is the nth harmonic voltage. V 1 is the fundamental frequency(50) Hz. The THD limit for 132 KV is 3%. THD of current I THD is given as in Eq. 5 Where, I n is the nth harmonic current. I 1 is the fundamental frequency (50) Hz. The THD of current and limit for 132 KV is <2.5%. CONTROL TECHNIQUE The aim of the control scheme is to maintain constant voltage magnitude at the point of common coupling(pcc), under system disturbances. The control system only measures the rms voltage at the load point, i.e., no reactive power measurements are required. The VSC switching strategy is based on a sinusoidal PWM technique which offers simplicity and good response. In fig.2 shows that the controller input is an error signal obtained from the reference voltage and the value rms of the terminal voltage measured. Such error is processed by a PI controller and the output is the angle d, which is provided to the PWM signal generator. An error signal is obtained by comparing the reference voltage with the rms voltage measured at the load point. The PI controller process the error signal and generates the required angle to drive the error to zero, i.e., the load rms voltage is brought back to the reference voltage. Fig. 2 [217]

The sinusoidal signal VCONTROL is phase-modulated by means of the angle δ. The modulated signal VCONTROL is compared against a triangular signal (carrier) in order to generate the switching signals for the VSC valves. The main parameters of the sinusoidal PWM scheme are the amplitude modulation index of signal, and the frequency modulation index of the triangular signal. The amplitude index is kept fixed at 1 p.u, in order to obtain the highest fundamental voltage component at the controller output. The modulating angle is applied to the PWM generators in phase A. The angles for phases B and C are shifted by 240 and 120 respectively. It can be seen in that the control implementation is kept very simple by using only voltage measurements as the feedback variable in the control scheme. The speed of response and robustness of the control scheme are clearly shown in the simulation results. The Simulink block diagram of SPWM generator is as shown in fig.3 SYSTEM MODELING MATLAB Simulink diagram: Fig.3 Simulink block diagram of SWPM generator System Parameters: Source voltage DC bus capacitance Inverter series inductance Source resistance Source inductance Fig.4 Simulink model 11 KV 15.5 mf 10 mh 0.1 Ohm 0.9 mh [218]

RESULTS This paper shows the simulation results without STATCOM and with STATCOM. First the model is run without connecting STATCOM and source voltage and load current is checked. Then after connecting STATCOM same waveforms are observed. Source voltage and current waveforms without STATCOM are shown fig.5 and fig.6 while Fig.7 and fig.8 shows load voltage and load current. Then after connecting STATCOM all the above observed parameters are shown in fig.9,10,11,12 respectively. THD in source voltage and current, load voltage and current is shown by FFT analysis done in MATLAB. Without STATCOM: Fig.5 Source Voltage Fig.6 Source Current Fig.7 Load Voltage [219]

With STATCOM: Fig.8 Load Current Fig.9 Source Voltage Fig.10 Load Voltage [220]

Fig.11 THD without STATCOM Fig.12 THD with STATCOM CONCLUSION In this paper we present static shunt compensator (STATCOM) connected in parallel to PCC between wind energy system and electrical grid. The control technique used is PWM to control voltage source inverter. The STATCOM is used to reduce power quality problems like voltage sags, swells, harmonics etc. The circuit is modeled in MATLAB- Simulink and results are taken. The results shows that voltage sag, swell is reduced in source and load voltage waveforms (Fig 9 and 10). From fig 11 and 12 it is observed that Total Harmonic Distortion (THD) is reduced from 3.5 % to almost 0.7 % and hence power quality is improved. REFERENCES [1] F. Z. Peng, Application issue of active power filters, IEEE Ind. Appl. Mag., vol. 4, no. 5, pp. 21 30, Oct. 1998. [2] B. Singh, K. Al-Haddad, and A. Chandra, A review of active filters for power quality improvement, IEEE Trans. Ind. Electron., vol. 46, no. 5, pp. 960 971, Oct. 1999. [3] M. El-Habrouk, M. K. Darwish, and P. Mehta, Active power filters: A review, IEE Proc. Electr. Power Appl., vol. 147, no. 5, pp. 403 413, Sep.2000. [4] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics Converters,Applications and Design, 3rd ed. Hoboken, NJ: Wiley, 2003. [5] M. H. Rashid, Power Electronics Circuit, Devices and Applications, 3rd ed. Upper Saddle River, NJ: Prentice Hall, 2003. [6] Roger C. Dugan, Mark F. McGranaghan Electrical Power System Quality 2 nd ed.tata McGraw Hill.2008 [7] J. Holtz, Pulse width modulation for electronic power conversion, Proc. IEEE, vol. 82, pp. 1194 1214, Aug. 1994. [221]