Moment resistance of bolted timber connections with perpendicular to grain reinforcements

Similar documents
SCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS

Anti-check bolts as means of repair for damaged split ring connections

Connection and performance of two-way CLT plates

Investigations on the Effectiveness of Self-tapping Screws in Reinforcing Bolted Timber Connections

Moment-Resisting Connections In Laminated Veneer Lumber (LVL) Frames

Prediction of Reinforcement Effect by Screw on Triangular Embedment Perpendicular to the Grain with Variation of Screw Locations

Dowel connections in laminated strand lumber

Cyclic tests 1 of engineered shearwalls considering different plate washer sizes

NON-LINEAR CONNECTION MODELS IN TIMBER ENGINEERING

SELF-TAPPING SCREWS AS REINFORCEMENTS IN BEAM SUPPORTS. I Bejtka H J Blaß. Lehrstuhl für Ingenieurholzbau und Baukonstruktionen Universität Karlsruhe

Development of Wooden Portal Frame Structures with Improved Columns

Bolts and Set Screws Are they interchangeable?

Hanger bolts and solar fasteners in sandwich panels

Dowel-type fasteners. Timber Connections. Academic resources. Introduction. Deferent types of dowel-type fasteners. Version 1

Glued laminated timber beams repair.

Ductility of large-scale dowelled CLT connections under monotonic and cyclic loading

Design of structural connections for precast concrete buildings

Glulam Connection Details

APA Report T Shear Wall Lumber Framing: Double 2x s vs. Single 3x s at Adjoining Panel Edges APA - The Engineered Wood Association

STRUCTURAL TIMBER DESIGN

BauBuche Fasteners and connections

Available online at ScienceDirect. Procedia Engineering 114 (2015 )

Pull-compression tests on glued-in metric thread rods parallel to grain in different timber species and laminated veneer lumber

Engineering Research into Traditional Timber Joints

Experimental and numerical study of nailed laminated timber elements for in plane and transverse loading

The predictive model for strength of inclined screws as shear connection in timber-concrete composite floor

Connection and Tension Member Design

SCREWED JOINTS IN CROSS LAMINATED TIMBER STRUCTURES

Experimental Evaluation of Metal Composite Multi Bolt Radial Joint on Laminate Level, under uni Axial Tensile Loading

Mechanical behavior of fiberglass reinforced timber joints

Experimental investigation of the behaviour of pinned beam to column connections to pure shear monotonic and cyclic excitation

Connection Design Examples

Dowel type joints Influence of moisture changes and dowel surface smoothness. Erik Serrano and Johan Sjödin, Växjö University, Sweden

Please do not open this exam until you are told to do so.

1. Enumerate the most commonly used engineering materials and state some important properties and their engineering applications.

Use of grooved clamping plate to increase strength of bolted moment connection on cold formed steel structures

Chapter 1: Introduction

Cast-in Ferrule Connections Load/Displacement Characteristics in Shear

1/2/2016. Lecture Slides. Screws, Fasteners, and the Design of Nonpermanent Joints. Reasons for Non-permanent Fasteners

HO12 - Timber Construction Details. FRILO Software GmbH As of 13/12/2017

HPD Aerated concrete anchor. Approvals / certificates. Basic loading data (for a single anchor)

Space-frame connection for small-diameter round timber

Lawrence A. Soltis, M. and Robert J. Ross, M. 1

Load carrying capacity of dowelled connections

Structural Strength of Lapped Cold-Formed Steel Z-Shaped Purlin Connections with Vertical Slotted Holes

Three-dimensional finite element analysis of the Japanese traditional post-and-beam connection

Finite Element Analysis per ASME B31.3

Sliding shear capacities of the Asymmetric Friction Connection

Two way Spanning CLT Concrete Composite Slabs

TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM

PRO LIGNO Vol. 11 N pp

Tension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite.

Simplified analysis of timber rivet connections

Ph.D. Preliminary Qualifying Examination. Cover Page. Thermodynamic. January 17, 2013 (Thursday) 9:30 am 12:30 noon Room 2145 Engineering Building

SEISMIC BEHAVIOR OF BEAM-TO-COLUMN DOWEL CONNECTIONS: NUMERICAL ANALYSIS VS EXPERIMENTAL TEST

CH # 8. Two rectangular metal pieces, the aim is to join them

Tension testing of green oak connections FRAME 2003, St Fagans

Effect of Vertical Load under Cyclic Lateral Load Test for Evaluating Sugi CLT Wall Panel

Comparative Evaluation of Resistance Made Simple Shear Connection with Bolts and With Welding

EVALUATING ROLLING SHEAR STRENGTH PROPERTIES OF CROSS LAMINATED TIMBER BY TORSIONAL SHEAR TESTS AND BENDING TESTS

DESIGN OF MACHINE MEMBERS-I

NUMERICAL ANALYSIS OF SCREW ANCHOR FOR CONCRETE

STUDY OF THE STRUCTURAL BEHAVIOUR OF THE CONNECTION BETWEEN MULLIONS AND TRANSOMS IN WOOD-GLASS FACADES

Fire resistance tests on beam-to-column shear connections Pedro Palma, Andrea Frangi, Erich Hugi, Paulo Cachim and Helena Cruz

Pilot Research on Cold-formed Steel Framed Shear Wall Assemblies with Corrugated Sheet Steel Sheathing

5-axis clamping system compact

Module 10 : Improvement of rock mass responses. Content

Tensile strength of ASSY plus VG screws wood-wood (softwood)

EVALUATION OF SCREWS USED IN LAMINATED VENEER LUMBER ROCKING CONNECTIONS

4-Bolt Wood-to-Steel Connections

Connections in CLT Assemblies

Rigid Connections. Between Wood posts and concrete

CHARACTERISTICS OF LUMBER-TO-LUMBER FRAMING CONNECTIONS IN LIGHT-FRAME WOOD STRUCTURES

ADDENDUM (February 2014) 2012 NDS Changes John Buddy Showalter, P.E., Bradford K. Douglas, P.E., Philip Line, P.E., and Peter Mazikins, P.Eng.

WITHDRAWAL AND LATERAL STRENGTH OF THREADED NAILS

Verbindungselemente Engel GmbH Weltestraße Weingarten DEUTSCHLAND. Manufacturing plant 74437, , ,

Two basic types of single

Korean standards of visual grading and establishing allowable properties of softwood structural lumber

CONNECTIONS FOR CONTINUOUS FRAMING IN PRECAST CONCRETE STRUCTURES

NAILED MORTISED-PLATE CONNECTIONS FOR SMALL-DIAMETER ROUND TIMBER 1. Kug-Bo Shim* Ronald W. Wolfe. Marshall Begel

Cyclic tests of engineered shear walls with different bottom plate and anchor bolt washer sizes (Phase II)

Withdrawal Strength of Staples

Review on on-site splice joints in timber engineering

AN IMPROVED SHEAR TEST FIXTURE USING THE IOSIPESCU SPECIMEN

Effect of Masonry Infills on Seismic Performance of RC Frame Buildings

AMTS STANDARD WORKSHOP PRACTICE. Bond Design

ERECTION & CONSTRUCTION

COOLING TECHNOLOGY INSTITUTE AN INVESTIGATION OF PIN BEARING

a) If a bolt is over-tightened, which will fail first the bolt, or the plastic?

UNDERSTANDING TORQUE -ANGLE SIGNATURES OF BOLTED JOINTS

TECHNICAL MANUAL. TERADOWEL and ULTRADOWEL. Reliable Dowel System for Floor Joints

Technical Data Sheet. T E C H N I C A L D A T A S H E E T Superprop. Mass 25 Mass 50 M AT 125 Superprop. MU Bridging

Hours / 100 Marks Seat No.

Bolt Spacing and End Distance of Bolted Connection of Laminated Veneer Lumber (LVL) Sengon

ANALYSIS OF LATERAL STIFFNESS FOR INFILLED FRAME WITH OPENING

European Technical Assessment ETA-13/0029 of 11/07/2017

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the grade A325 structural bolt.

Effect of Pile Bending Stiffness on Static Lateral Behavior of a Short Monopile in Dry Sand

Connection Solutions for Wood-frame Structures. Copyright Materials. Learning Objectives

Comparison of behaviour of laterally loaded round and squared timber bolted joints

Transcription:

Moment resistance of bolted timber connections with perpendicular to grain reinforcements Frank LAM Ph.D. P.Eng., Professor The University of British Columbia Vancouver, BC, Canada Michael SchulteWREDE Visiting Student The University of British Columbia Vancouver, BC, Canada C.C. YAO Ph.D. Struct.Eng., Principal Read Jones Christoffersen Ltd Vancouver, BC, Canada James J. GU Ph.D. Structure Designer Read Jones Christoffersen Ltd Vancouver, BC, Canada Summary This paper reports the results of an experimental study to evaluate the contribution of selftapping screws as perpendicular to grain reinforcements for bolted glulam connections with slotted in steel plates. Test results of beamtocolumn connection specimens subjected to monotonic and reverse cyclic loading show that the connections reinforced with selftapping screws have an increased capacity by a factor of 2 and 1.7 when compared to unreinforced connections under monotonic and reverse cyclic loading, respectively. Retesting retrofitted failed unreinforced connections with selftapping screw reinforcements also show increase in the capacity by 1.87 and 1.53 times compared to the unreinforced case connections under monotonic and reverse cyclic loading, respectively. An extremely ductile failure mode was also observed with the reinforced connection. 1 Introduction It is well known that bolted timber connections with slotted in steel plates have poor ductility and low moment resisting capacity. Due to their simplicity and elegance, designers commonly use these connections to transfer shear forces and ignore the contribution of their moment carrying resistance. When subject to loading such as seismic forces, the connection may experience bending moments not intended in the design, and the connection could fail prematurely because it may not be able to provide the needed moment resistance as they are governed by the tension perpendicular to grain and longitudinal shear strengths of timber: the two weakest strength properties of wood. Blaß and Bejtka [1], Bejtka [2], Blaß et al. [3] reported past research on using the self tapping screws as perpendiculartograin reinforcements. This paper reports an experimental study demonstrating that bolted timber connections can be easily made into a strong and ductile moment resisting connection when reinforced with these self tapping screws.

Fig. 1: Example of a bolted beamcolumn connection with slottedin steel plate A commonly used beamtocolumn woodsteelwood bolted connection was considered in the study (see Figure 1). A total of 30 connection tests were conducted under monotonic ( M series) and reverse cyclic loading ( C series). To investigate improvements in performance and ductility, regular connection specimens were tested as unreinforced first the U series. A second set of specimens was reinforced with recently invented long, selftapping wood screws to prevent early brittle failure and then tested the R series. The reinforcing screws were installed directly into the wood members without pre drilling in the direction perpendicular to both the wood grain and the bolts. Finally, the prior tested unreinforced and broken specimens were retrofitted with the selftapping screws and retested to prove the versatility of the reinforcing method as a tool to retrofit existing, damaged structures the D series. The observed performance differences of reinforced and retrofitted connections as well as unreinforced connections during monotonic and reverse cyclic loading are presented in this paper. 2 Materials and Methods Canadian 24fE Douglas fir/larch Glulam members with a cross section of 304 mm x 130 mm were used to fabricate the connection specimens. The column and beam consisted of double and single members, respectively. Figures 2 and 3 show the schematics of the connection specimens. 95 115 95 95 115 95 210 140 115 95 190 105 304 130 130 12 5 140 190 105 47 304 Fig. 2: Side and top views of connection layout (all measurements in mm) The Hundegger K2 fully automated joinery machine in University of BC (UBC) was used to manufacture the specimens. The bolt holes were drilled with the available 19.1 mm diameter drill in the Hundegger machine which matched the bolt diameter without any extra oversize fabrication tolerance. The performance of the tightfitting connection is likely to be better than that with poorer tolerance but relative comparison between the examined connection types is still valid. The final

lengths of the wooden parts of the connection were 1000 mm for the column members and 820 mm for the beam members. The moisture content of each specimen element was measured prior to testing with a resistance moisture detector and they ranged from 11 to 14%. The steel bolts were SAE J429 Grade 5 Cap screws NC Plain, fabricated of medium carbon steel, quenched and tempered. The bolts applied in the column and the beam connections had lengths of 305 mm and 165 mm, respectively. Steel plates with dimensions of 675 mm x 300 mm and a thickness of 9.5 mm were used. In each plate, eight holes with a diameter of 19.1 mm were drilled according to the fastener group pattern (See Fig 2.). After every test, the used steel plate was visually examined for any hole bearing deformations. Very little deformation was noticed and reusing the steel plates was assumed to be of 3Hnegligible influence. Würth ASSY VG plus selftapping wood screws continuous threads were used to reinforce the connection specimens. The screws were 300 mm in length and 8 mm in diameter. The tread is galvanized and plasticcoated. For the design according to DIN1052:200408 and DIN V ENV 199511:199406, the characteristic value of the screws yield moment (M y,k ) is 17600 Nmm. The withdrawal resistance and further information concerning different loading conditions, spacing requirements and limitations on implementation may be obtained from DIBt [4]. Fig. 3: Test Set up All tests of this investigation were conducted at UBC Timber Engineering and Applied Mechanics Laboratory. A general view of the test setup is depicted in Figure 3. Six subseries with 5 replications each were tested. In monotonic tests, the connection specimens were pushed to failure first (i.e., load dropped to 80% of the peak load); after which the displacement was brought back to zero. In the reverse cyclic tests, the Consortium of Universities for Research in Earthquake Engineering (CUREE) displacement controlled reverse cyclic protocol was followed Krawinkler et al. [5]. Figure 4 shows the protocol with the reference deformation (Δ) taken as 60% of the monotonic displacement capacity Δ ultimate. Fig. 4: CUREE Deformation Controlled QuasiStatic Protocol

3 Results and Discussion Summary test results of the six test series are shown in Table 1. The results show a significant improvement of performance when the undamaged connections were reinforced with the selftapping wood screws as the average maximum capacity was increased and the coefficient of variance for the maximum capacity was decreased. The failure mode was changed from brittle to a very ductile mode. Table 1: Summary Statistics of test results Max Moment [knm] @ Rotation [ ] Failure Moment (80% Max moment) [knm] @ Rotation [ ] Yield Moment [knm] MU 31.49 (5.06) 2.97 (0.70) 25.19 (4.05) 3.00 (0.65) @ Rotation [ ] Elastic Stiffness [knm/ ] 13.73 (1.32) Ductility Ratio [] MR 65.88 (2.12) 16.59 (0.06) 41.20 (1.58) 2.80 (0.26) 14.54 (1.16) >5.97 (0.62) MD 58.85 (4.36) 13.29 (2.00) 47.08 (3.49) 14.42 (1.96) 41.16 (7.36) 3.87 (1.55) 12.38 (3.81) 4.21 (1.50) CU 35.70 (1.63) 4.01 (0.17) 28.83 (1.85) 5.15 (1.24) 34.29 (0.30) 2.22 (0.01) 14.96 (0.69) CR 62.54 (1.55) 15.90 (0.17) 41.83 (0.83) 3.00 (0.20) 14.02 (0.77) CD 54.54 (3.27) 12.65 (1.26) 41.14 (2.33) 11.96 (0.39) 45.49 (1.70) 5.90 (0.40) 9.33 (0.84) The unreinforced specimens tested under monotonic loading (MU) showed a maximum moment resistance ranging between 25.07 knm and 38.21 knm with maximum rotations ranging from 2.2 to 4.1. The failures were brittle with rapid decrease in capacity after crack formation was developed from tension perpendicular to grain and/or longitudinal shear stresses in the beam member (Figure 5). Limited wood crushing in the dowel holes and virsually no bolt bending was observed in the connection. A yield point could not be determined from monotonic load curves of the MU specimens, as splitting failure occurred before the curve flattened enough to match the second tangent line. MU Series CU Series Fig. 5: Typical examples of failed unreinforced specimens Therefore, no ductility ratios could be determined for the unreinforced connections affirming the very brittle behaviour. In the unreinforced specimens under reverse cyclic loading CU, splitting failure occurred at an overall rotation between 2 and 3 in cycles on either side. As bearing of the beam member s bottom end occurred on the column member on both sides, the beam member sheared up to its top end at two planes through the left and right vertical bolt lines. The peak loads of the trailing cycles were generally much lower. One reason for this was that the driven displacement was only 75% of the respective primary cycle. The second reason was that with the wood crushing during the primary cycle, resistance did not increase until higher rotation levels. Typical MU and CU momentrotation plots are shown in Figure 6. The CU momentrotation plots exhibit higher rotations in the negative quadrant. During negative rotation of the beam member, when the crack opened on the opposite side where the string pots were measuring the horizontal

displacements, the split off part was tilted more towards the vertical compared to the rest of the member, so the recorded values led to a higher rotation. In a positive cycle, the crack diverged on the other side, hence did not influence the string pot recording. Visually no bolt bending was observed after disassembly. Therefore, ductility ratios derived from the envelope curves may not be as meaningful as in the monotonic tests evaluation. Fig. 6: Typical momentrotation plot of the unreinforced connection The undamaged specimens tested under monotonic loading with reinforcing screws (MR) showed moment capacities ranging between 62.26 knm and 67.86 knm with maximum rotations ranging between 16.51 and 16.66. These levels of deformation reached the stroke limit of the actuator; hence, some reserve capacities may still be available in the connections (at higher rotations). Splitting did not occur in any specimen. The only visually detectable damage of the connection was a plug shear failure on the tension side of the beam member under the bolt towards the bottom end (Figure 7). This indicates the screws have the capacity to carry the imposed stresses in the perpendicular to grain direction, thereby changing the failure mode to parallel to grain axis failures. Disassembling the failed specimens showed Mode I (Johanson Yield Model) type failure in the beam members with heavy wood crushing through the whole length in some of the dowel holes. In some cases, the transition to Yield Mode II was smooth as the bolts showed significant bending with one plastic hinge in the middle where they bore on the hole in the steel plate. Bolt bending and associated Yield Mode II was observed in the column connection. Here, different from the heavy wood crushing on the inside plane adjacent to the steel plate, no wood crushing was noticed at the specimens outer surface. The self tapping screws were also removed after testing and showed no elongation when compared to unused ones. CR Series MR Series Figure 7: Tested reinforced connection specimens MR and CR series

The momentrotation plots do not show any significant load drop up to the maximum possible rotation (Figure 8). Although the plot of yield region appeared to be almost linear, determination of the yield point except for 4 th specimen of MR series was done by matching the second tangent line to the curves with a slope of 1/6 of the initial stiffness. Because there was no point of failure (the load never dropped below 80% of its maximum), a corresponding failure rotation for the ductility ratio calculation could not be determined. In the CR series, the mean value of maximum resistances attained at the maximum possible displacement increased by 72% in the positive and 78% in the negative side compared to the CU resistances. Brittle failure did not occur even when the maximum actuator stroke to either side was reached, at rotations of around 16. Instead, the connections showed explicit yielding. In the beam members, a combination of Yield Mode I and II was noticed, with wood crushing in every dowel hole all the way up to the members outer surface and bolt bending with one plastic hinge at the steel plate plane. The column member yielded according to Mode II, with visible dowel hole deformations only at the inner surface and severe bolt bending with one plastic hinge. Some axial rotation of the bent bolts in their holes could also be observed during testing when the load was reversed. Furthermore, the CR tests marked the only series of this investigation where the bolts were stressed to their limit, as in two specimens, and although fabricated of mild steel, bolt #3 broke at the plastic hinge because of material fatigue. Fig. 8: Typical momentrotation plot of the reinforced connection Specimens for the MD and CD series were prepared using the the heavily damaged specimen from the MU and CU series. The original crosssection of the damaged specimens was first restored by clamping the beam members with screwclamps and closing the cracks. Then, three reinforcing screws per side member were installed with an identical pattern as the MR and CR series. The same bolts were employed that had been used in the U series, as they were almost not deformed. The observed failure modes were quite different between the D and R series. Two D series specimens showed little damage at the point of maximum rotation, with some plug shear failures and little relative shifting along the existing shear plane on the compression side (Figure 9). Here the screws not only prevented crack opening but also reinforced the shear capacity up to a certain level. The other three specimens failed similar to the MU series with opening of the preexisting crack on the tension side. As the already separated wood could not contribute to any load resistance and distribution, the forces perpendicular to the grain were concentrated on the middle and bottom screws which were eventually bent and gradually pulled through the outer lamellae.

MD Series CD Series Figure 9: Tested retrofitted connection specimens MD and CD series After disassembly, the bolts showed deformations according to Yield Mode I and II with noticeable bending deflections in some bolts. This fact and observations of the momentrotation plots (Figure 10) proved that connections which had been damaged and restored with screws behaved in a ductile manner. Even after crack opening, the curves of the respective specimens did not instantly drop to failure level which can be explained by as the fact the screws maintained some tension resistance perpendicular to the wood grain. The variation of and an initial slip in the MD load deformation plot is dependent on the different initial damage levels of the connections. Fig. 10: Typical momentrotation plot of the retrofitted connections MD and CD series The mean maximum moment in the CD series increased by over 50% on the positive and negative side compared to the mean value of the CU series. Although every specimen failed before the maximum possible displacement as limited by the actuator stroke was reached, the ductility still improved which can be derived from a distinct plastic segment of the envelope curves. Displacement along the existing damaged shear planes in the beam members was observed in early cycles. This movement could not be totally prevented by the screws, which showed some buckling deformations when they were removed after the tests. However, the peak loads of the following cycles kept increasing, and definitive yielding of the bolts could be noticed. Similar to previous reinforced test series, the highest bolt bending moment according to Yield Mode II took place in the column members, while the stocky bolts in the beam members almost remained straight but enlarged the dowel holes according to Yield Mode I. 4 Conclusions The primary focus of this investigation was to ascertain whether long length selftapping wood screws employed as reinforcements can improve the performance of bolted timber connections subjected to a moment load. Test results of a representative connection layout subject to monotonic and reverse cyclic loading show that the connections reinforced with selftapping screws have an increased moment capacity by a factor of 2 and 1.7 when compared to unreinforced connections

under monotonic and reverse cyclic loading, respectively. Retesting retrofitted failed unreinforced connections with selftapping screw reinforcements also show increase in the capacity by 1.87 and 1.53 times compared to the unreinforced connections under monotonic and reverse cyclic loading, respectively. A ductile failure mode was achieved with the reinforced connections. 5 References [1] Blaß, H.J.; Bejtka, I., Selbstbohrende Holzschrauben und ihre Anwendungsmöglichkeiten. Institut für Ingenieurholzbau, Universität Karlsruhe, Germany, 2004. [2] Bejtka, I., Verstärkungen von Bauteilen aus Holz mit Vollgewindeschrauben. Dissertation, Lehrstuhl für Ingenieurholzbau und Baukonstruktionen, Universität Karlsruhe, Germany, 2005. [3] Blaß, H.J.; Bejtka, I.; Uibel, T., Tragfähigkeit von Verbindungen mit selbstbohrenden Holzschrauben mit Vollgewinde. Karlsruher Berichte zum Ingenieurholzbau 4, Universität Karlsruhe, Germany, 2006. [4] DIBt, Allgemeine Bauaufsichtliche Zulassung, Würth ASSY VG plus Vollgewindeschrauben als Holzverbindungsmittel. Deutsches Institut für Bautechnik, Berlin, 2006. [5] Krawinkler, H., Parisi, F., Ibarra, L., Ayoub, A., and Medina, R., "Development of a testing protocol for wood frame structures." Rep. W02, CUREECaltech Woodframe Project, Stanford Univ., Stanford, Calif., 2001.