Benefits of SFRA - Case Studies

Similar documents
Chapter 7 Conclusion 7.1 General

REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

Effective maintenance test techniques for power transformers

Operational Management of Grid Transformers An Experience of POWERGRID

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

HOW TO SAFE GUARD THE TRANSFORMER..???

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Variation in SFRA plot due to design and external parameter

Transformers handling and transport

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

Matz Ohlen Director Transformer Test Systems. Megger Sweden

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Advanced Diagnostic Testing Services. Provides detailed and reliable results

Substation Preventive Maintenance

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Vallabh Vidyanagar, Anand, INDIA

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

PD Solutions. On-Line PD Measurement Devices

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

ABB Power Products Service

Fushun Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

TECHIMP Power Transformer Monitoring

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

TRANSFORMER TECHNOLOGY GPT

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

FRAX Series Sweep Frequency Response Analyzers

Problems connected with Commissioning of Power Transformers

Transformer Shunt Fault Detection using Two Techniques

Using the Frequency Response Analysis (FRA) In Transformers Internal Fault Detection

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding Fault

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Best Practice Reducing The Risk of Arc Flash Cross Over

Phase Shifting Transformers. Presented by

Transformer condition assessment with an integrated test van

Tap Changer Condition Assessment Using Dynamic Resistance Measurement

Welcome to the Session on. HT Distribution Network

Acoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

Onsite Mobile AC High Voltage Test System

Federal Power Transformers LLC based in Abu Dhabi, UAE

nical catalogue Tech

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

We can classify test failure modes in power transformers according to transformer components

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Autotransformer Condition Monitoring Systems

The Weidmann Conference The Aging of America s Transformers

Subject: Computer Aided Electrical drawing (CAED) Subject Code: 10EE65

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

EXPERIENCE WITH DETECTION AND IDENTIFICATION OF WINDING BUCKLING IN POWER TRANSFORMERS. Victor V. Sokolov and Boris V. Vanin ZTZ-Service Company

Transformer Protection

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Testing and Diagnostic of Power Transformers & Distribution Transformers

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

A Novel Technique to Precise the Diagnosis of Power Transformer Internal Faults

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

EI HIGH VOLTAGE INSULATION TESTING POLICY

Distribution Equipments - Technology and Applications. Training Module for DISTRIBUTION TRANSFORMER

Power Measurements and Basic Electrical Diagnostic Tests

Transformer Protection

POWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

SPAD 346 C Stabilized differential relay

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

Stabilized Differential Relay SPAD 346. Product Guide

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Power Transformer Condition Assessment Based on Standard Diagnosis

EE223D: Distribution Power Transformer

Importance of Transformer Demagnetization

Power transformers for Network, Rectifiers, Furnace

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Specialists in HV and MV test and diagnostics. Testing in Substations

Assesment of health of transformer: a survey

TECHNIQUES AND STANDARD

ECP HV INSULATION TESTING

Advanced Test Equipment Rentals ATEC (2832)

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

Field Measurement of Transmission Cable Dissipation Factor

FRAX Series Sweep Frequency Response Analyzers

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Transcription:

6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1

Outline Condition Monitoring in GETCO Why SFRA? Case study (1):SFRA - How it helped to find a fault in winding Case study (2): SFRA - How it helped to find a fault in core Case study (3): SFRA - How it helped to find a fault in core Conclusion 2

Condition Monitoring in GETCO Transformer Technology / Tool Online Offline Insulation Resistance and Polarisation Index Routine Low Voltage tests Capacitance & Tan δ measurements Infrared Thermograph (Bushing) Measurement of Moisture in Oil DGA SFRA Acoustic Partial Discharge Measurement moisture content in active parts of Transformer 3

Why SFRA? To assess mechanical integrity of a transformer To detect core displacement and winding deformation due to : Large electromagnetic forces from fault current Transformer transportation and relocation Winding shrinkage causing release of clamping structure To detect broken or loosened clamping structure Hoop Buckling Shorted turns and open winding 4

Case study (1): Location : 220 kv Kapadwanj S/s Rating : 220/66kV, 100 MVA Date : 22.01.2012 OSR relay operated due to LV side Isolator support insulator flash over Initially SFRA along with Low Voltage Test and DGA 5

Case study (1): APPLIED VOLTAGE LV MAGNETIC BALANCE ( Post fault Abnormal ) Tap 1 Tap 17 r - n y - n b - n r-n y-n b-n r n 255 V 255 0 0 255 0 0 y n 251 V 174 251 74 175 251 68 b n 256 V 27 225 256 24 226 256 DGA Results ( Post Tripping ) H2 O2 N2 CH4 C2H2 C2H4 C2H6 CO CO2 119 3657 14212 11 36 27 1 169 570 Nature of incipient fault Major Key Gas Minor Key Gas Arcing C 2 H 2, H 2 CH 4, C 2 H 4 Low voltage magnetic balance test found abnormal in R phase and DGA indicates arcing

Case study (1): HV N at Tap No.1 ( Post fault - Abnormal) 500Hz to 2MHz with +/- 3 db: Tap and Main winding HV R Phase HV R phase shifted -3dB with reference to other phase in main and tap winding portion 7

Case study (1): LV N at Tap No.17 ( Post fault - Abnormal) 500Hz to 2MHz with +/- 3 db: Tap and Main winding LV R Phase 20Hz 10KHz Core deformation/open ckt./ Shorted turns / residual magnetism LV R phase shifted widely with reference to other phase in main and tap winding portion. It seems like open circuit. 8

Case study (1): Analysis SFRA LV R phase found abnormal defect in tapped winding ( 500Hz to 2 MHz) and open winding ( 5Hz to 100kHz ) with +/- 3 db variation. Problem reflected in low voltage magnetic balance and DGA ( Arcing ) also. Based on above abnormal results, decided to internal inspection of this transformer. 9

Case study (1): Internal Inspection LV R phase connecting leads of preselector switch of OLTC and its fixing assembly burnt. Burned connecting leads Burnt link and fixing assembly replaced Re-insulation of leads Drying process with oil filtration Take SFRA and other supporting test 10

Case study (1): HV N at Tap No.1 ( Normal After rectification ) HV R Phase All phases are identical after rectification of problem 11

Case study (1): LV N at Tap No.17 ( Normal After rectification) LV R Phase All phases are identical after rectification of problem 12

Case study (1): LV MAGNETIC BALANCE ( Normal After rectification ) APPLIED VOLTAGE Tap 1 Tap 17 r - n y - n b - n r-n y-n b-n r n 255 V 255 224 30 255 225 25 y n 252 V 176 252 76 175 252 69 b n 255 V 28 226 255 26 226 255 Low voltage test found normal after rectification

Case study (1): Cause of failure The heavy fault current due to flash over of LV side isolator support insulator caused R phase pre-selector switch LV connection two nos. of leads between position 3 & 12 to burn. SFRA plays a role fault with other test. as a supporting test to confirm the 14

Case study (2): Location : 220kV Khanpur Substation Rating : 220/66kV, 100 MVA Date : 21.04.08 High key gases in routine DGA test Low voltage test - 15

Case study (2): DGA Results ( on 22.12.07, Normal ) H2 O2 N2 CH4 C2H2 C2H4 C2H6 CO CO2 7 3405 12150 21 Nil 48 15 34 292 DGA Results ( on 21.04.08, Abnormal ) H2 O2 N2 CH4 C2H2 C2H4 C2H6 CO CO2 355 2988 13928 472 <1 538 214 57 1085 Nature of incipient fault Major Key Gas Minor Key Gas Thermal Fault - Over heated oil CH 4, C 2 H 4 C 2 H 6, H 2 DGA indicates thermal fault as per high key gases method 16

Case study (2): Low voltage Test CURRENT MEASURED MAGNETIZING CURRENT ( Post fault - Normal) HV WINDING LV WINDING R 3.2 ma 29.3 ma Y 2.6 ma 26.3 ma B 4.1 ma 35.2 ma MAGNETIC BALANCE ( Post fault - Normal ) APPLIED VOLTAGE R - N Y - N B - N r-n y-n b-n R - N 255 V 255 193 56 87 65 18 Y - N 252 V 170 252 82 59 87 28 B - N 256 V 58 190 256 16 69 87 Low voltage test found normal after fault

Case study (2): Low voltage Test CURRENT MEASURED SHORT CIRCUIT CURRENT ( Post fault - Normal ) HV WINDING LV WINDING R 3.54 A 10.38 A Y 3.55 A 10.18 A B 3.48 A 10.41 A Low voltage test found normal after fault

Case study (2): HV - N ( Post fault - Abnormal) 20Hz 10KHz Core deformation/open ckt./ Shorted turns / residual magnetism HV B Phase B phase curve differ in core area in compare with other two phases which shows core related issue 19

Case study (2): HV - N ( LV Shorted ) ( Post fault - Abnormal ) HV B Phase LV short curve nullify effect of core, winding part seems identical and normal 20

Case study (2): LV N ( Post fault - Abnormal) 20Hz 10KHz Core deformation/open ckt./ Shorted turns / residual magnetism LV B Phase B phase curve differ in core dominated area, which shows problem in core area 21

Case study (2): Analysis SFRA showed abnormality in the core. IR between core, frame and earth was measured. Core to Frame : 2000MΩ Frame to Earth : 8000MΩ Core to Earth : 0.03MΩ As the Core to Earth insulation found quite low, internal inspection carried out but nothing seen abnormal. Further investigation was done by inserting a GI wire between core and bottom of the tank and along the core nut found under the B phase core limb which was touching core and bottom. 22

Case study (2): Schematic Diagram 23

Case study (2): Analysis After removing the nut, again IR between core, frame and earth was measured. Core to Frame : 2000MΩ Frame to Earth : 8000MΩ Core to Earth : 2000MΩ Normally core earthing provided on top of the tank. The nut was providing another earthing and it caused thermal fault due to circulating current between core and earth. 24

Case study (2): HV - N ( Normal After rectification) After attending the problem all phase curves found identical 25

Case study (2): HV - N ( LV Shorted ) ( Normal After rectification ) After attending the problem all phase curves found identical 26

Case study (2): LV N ( Normal After rectification) After attending the problem all phase curves found identical 27

Case study (2): Conclusion A metallic nut below the core at bottom of the tank was found out with the help of SFRA which created parallel path to earth and led to thermal fault. Such kind of unbelievable fault can be identified by SFRA. In this case SFRA played a vital role as a supporting tool with DGA to detect the faulty area and to reach up to the root cause of the fault. 28

Case study (3): Location : 66kV Chhala Substation Rating : 66/11.55kV, 10 MVA Date : 01.09.08 Tripped on differential relay due to failure of 66kV class Y phase bushing with reflected of 11kV feeder 29

Case study (3): Low voltage Test CURRENT MEASURED MAGNETIZING CURRENT ( Post fault - Abnormal ) HV WINDING LV WINDING R 1.8 ma 117.5 ma Y 13.5 ma 133 ma B 1.8 ma 135 ma MAGNETIC BALANCE ( Post fault - Abnormal ) APPLIED VOLTAGE R - Y Y - B B - R r-n y-n b-n R Y 433 V 433 388 176 41 37 16 Y B 431 V 230 431 296 21 40 38 B - R 437 V 309 296 437 19 38 41 Low voltage test found abnormal after fault 30

Case study (3): HV PH PH ( Post fault - Abnormal ) 20Hz 10KHz Core deformation/open ckt./ Shorted turns / residual magnetism R-Y Y-B B-R All three phases response are differ in core related area as mentioned frequency 31

Case study (3): HV PH PH ( LV Shorted ) ( Post fault Normal ) In LV short condition core area nullify and winding area curves are identical in all phases 32

Case study (3): LV PH N ( Post fault - Abnormal ) 20Hz 10KHz Core deformation/open ckt./ Shorted turns / residual magnetism R Y B All three phases response are differ in core related area as mentioned frequency 33

Case study (2): Analysis SFRA and low voltage revealed problem inside core area. Internal inspection carried out by removing top plate of transformer. 2 Nos. of bolts clamping the top channel with tank were loose and top yoke channel got lifted upwards by about 25mm which caused a little core deformation. 34

Case study (2): Internal Inspection Yoke Bolt Yoke Channel After attending the problem, SFRA was taken. 35

Case study (3): HV PH PH ( Normal After rectification ) All three phases response are identical in core dominated area after rectification of fault 36

Case study (3): HV PH PH ( LV Shorted ) ( Normal After rectification ) This response was identical from initially as problem was in core area after rectification of fault 37

Case study (3): LV PH N ( Normal After rectification ) All three phases response are identical now in core area after rectification of fault 38

Case study (3): Low voltage Test CURRENT MEASURED MAGNETIZING CURRENT ( Normal After rectification) HV WINDING LV WINDING R 2.4 ma 56.2 ma Y 1.9 ma 28.5 ma B 2.2 ma 55.6 ma MAGNETIC BALANCE ( Normal After rectification) APPLIED VOLTAGE R - Y Y - B B - R r-n y-n b-n R Y 442 V 442 365 79 41 35 6 Y B 450 V 256 450 189 23 42 17 B - R 445 V 44 396 445 4 37 41 Low voltage test found normal after rectification of fault 39

Case study (3): Cause of Failure Heavy reflected fault caused axial and radial forces exerted on transformer active part. Core structure got disturbed and it was reflected in SFRA plot. 40

Conclusion SFRA responses clearly indicate faulty conditions of transformer and it helped for root cause analysis. SFRA helps to detect fault by just compare with different phase with different task without having a initial results of same transformer or same design transformer. SFRA plays vital role as supporting test for final conclusion as its deliver diversity of information in only one test. SFRA is very useful tool to detect heavy through fault current leads to mechanical deformation of core or winding, internal connections and contacts inside transformer. GETCO has adopted such diagnosis tool while fault as well as in routine practice while shifting of transformer. 41

Thanks 42