DPharp Differential Pressure and Pressure Transmitters

Similar documents
User s Manual Absolute Pressure and Gauge Pressure Transmitters EJ 510, EJ 530, EJX610A and EJX630A

User s Manual Diaphragm Sealed Differential Pressure and Pressure Transmitters EJ 118 and EJ 438

User s Manual Flange Mounted Differential Pressure Transmitters EJX210A and EJA210E

General Specifications

User s Manual Diaphragm Sealed Differential Pressure and Pressure Transmitters EJ 118 and EJ 438

User s Manual Absolute Pressure and Gauge Pressure Transmitters EJ 510, EJ 530, EJX610A and EJX630A

YTA610 and YTA710 Temperature Transmitters (Hardware)

User s Manual EJX118A and EJX438A Diaphragm Sealed Differential Pressure and Pressure Transmitters

YTA610 and YTA710 Temperature Transmitter (Hardware)

Ex instruction manual. Rotamass Coriolis mass flow meter ATEX. IM 01U10X01-00EN-R_002, 2nd edition,

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

User s Manual. Manual Change No V-E. Please use the attached sheets for the pages listed below in IM 01F06F00-01EN (7th).

Ex instruction manual. Rotamass Coriolis mass flow meter. IECEx. IM 01U10X02-00EN-R_002, 2nd edition,

DPharp Fieldbus Communication Type (EJX A, EJA E)

DPharp Fieldbus Communication Type (EJX A, EJA E)

Power supply. Calibration. Surface finishing. Seal. Process connection

YVP110 Advanced Valve Positioner

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

User s Manual Model EJA510A and EJA530A Absolute Pressure and Gauge Pressure Transmitters [Style: S2]

OPTIWAVE 7300 C Supplementary instructions

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

User s Manual Model EJA118W, EJA118N and EJA118Y Diaphragm Sealed Differential Pressure Transmitters [Style: S2]

EJX and EJA-E Series Differential Pressure and Pressure Transmitters Installation Manual. Contents 1. Introduction. 3. Installation. 5.

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier

IP26 Series Current to Pneumatic Converter

YTA Series Temperature Transmitters (Hardware) [Style: S3]

IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

General Specifications

General Specifications

ATEX Installation Drawings and Instructions

General Specifications

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

General Specifications

General Specifications

General Specifications

User's Manual Model SE14 Magnetic Flow Converter

Certificate of Compliance

General Specifications

General Specifications

General Specifications

General Specifications

Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751

General Specifications

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

General Specifications

General Specifications

General Specifications

General Specifications

General Specifications

General Specifications

Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc

General Specifications

General Specifications

Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc

General Specifications

INSTRUCTION MANUAL (ATEX / IECEx)

General Specifications

General Specifications

General Specifications

General Specifications

R88000 T (including ATEX)

Safety Instructions Nivotester FTC625, FTC325

SOLENOID TYPE, CERTIFICATION & PROTECTION CONCEPTS

General Specifications

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

General Specifications

General Specifications

General Specifications

General Specifications

General Specifications

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

FM Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

General Specifications

Smart Pressure Transmitter

General Specifications

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers

General Specifications

Instruction Manual. Model EJA438W and EJA438N Diaphragm Sealed Gauge Pressure Transmitters. [Style: S2] IM 1C22J1-01E 10th Edition

General Specifications

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

General Specifications

Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model 3500 Transmitters

General Specifications

General Specifications

General Specifications

General Specifications

General Specifications

Instruction Manual. Model EJA118W, EJA118N and EJA118Y Diaphragm Sealed Differential Pressure Transmitters. [Style: S2] IM 1C22H1-01E 10th Edition

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

User manual. Load cell with one built in amplifier KOSD-FA KIMD-FA KEND-FA Load cell with two built in amplifiers KOSD-FAD KIMD-FAD KEND-FAD

User manual. Load cell with one built in amplifier KOSD-FA KIMD-FA KEND-FA Load cell with two built in amplifiers KOSD-FAD KIMD-FAD KEND-FAD

Model DY Vortex Flowmeter Model DYA Vortex Flow Converter Fieldbus Communication Type

Product manual wire programmable RTD transmitter

General Specifications

Rosemount 148 Temperature Transmitter

megablock series passive hubs for fieldbus networks

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

Transcription:

User s Manual DPharp Differential Pressure and Pressure s Manual Change No. 12-021-2 For the products of EJX and EJA-E series with any of the following option codes, please refer to this manual change for handling cautions of ATEX approval. Model EJX110A, EJX115A, EJX118A, EJX120A, EJX130A, EJX210A, EJX310A, EJX430A, EJX438A, EJX440A, EJX510A, EJX530A, EJX610A, EJX630A EJX110A, EJX115A, EJX118A, EJX120A, EJX130A, EJX210A, EJX310A, EJX430A, EJX438A, EJX440A, EJX510A, EJX530A, EJX610A, EJX630A, EJA110E, EJA115E, EJA118E, EJA120E, EJA130E, EJA210E, EJA310E, EJA430E, EJA438E, EJA440E, EJA510E, EJA530E Option code /KF21, /KS2 /KS26 Applicable part of this manual change ( I ) ( II ) Oct. 15, 2012

( I ) ATEX Certification (1) Technical Data a. ATEX Intrinsically Safe Type Caution for ATEX Intrinsically safe type. Note 1. Model EJX Series pressure transmitters with optional code /KS2 for potentially explosive atmospheres: No. KEMA 03ATEX1544 X Applicable Standard: EN 50014:1997, EN 50020:2002, EN 50284:1999, EN 50281-1-1:1998 Type of Protection and Marking code: EEx ia IIC T4 Group: II Category: 1G, 1D Ambient Temperature for gas-proof: 50 to 60 C Process Temperature (Tp.): 120 C max. Maximum Surface Temperature for dustproof: T85 C (Tamb.: 40* to 60 C, Tp.: 80 C) T100 C (Tamb.: 40* to 60 C, Tp.: 100 C) T120 C (Tamb.: 40* to 60 C, Tp.: 120 C) * 15 C when /HE is specified. Enclosure: IP66 and IP67 Note 2. Electrical Data In type of explosion protection intrinsic safety EEx ia IIC only for connection to a certified intrinsically safe circuit with following maximum values: Ui = 30 V, Ii = 200 ma, Pi = 0.9 W, Effective internal capacitance; Ci = 10 nf, Effective internal inductance; Li = 0 mh Note 3. Installation requirements. (Refer to the installation diagram) Note 4. Maintenance and Repair The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA Intrinsically safe Certification. Note 5. Special Conditions for Safe Use In the case where the enclosure of the Pressure is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded. Hazardous Location Nonhazardous Location Supply Safety Barrier *1 F0206.ai *1: In any safety barriers used the output current must be limited by a resistor R such that Imaxout-Uz/R. To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port. b. ATEX Flameproof Type Caution for ATEX flameproof type. Note 1. Model EJX Series pressure transmitters with optional code /KF21 for potentially explosive atmospheres: No. KEMA 07ATEX0109 Applicable Standard: EN 60079-0:2006, EN 60079-1:2004, EN 61241-0:2006, EN 61241-1:2004 Type of Protection and Marking Code: Ex d IIC T6...T4, Ex td A21 IP6x T85, T100, T120 Group: II Category: 2G, 2D Enclosure: IP66 and IP67 Temperature Class for gas-poof: T6, T5, and T4 Ambient Temperature for gas-proof: 50 to 75 C (T6), 50 to 80 C (T5), and 50 to 75 C (T4) Maximum Process Temperature (Tp.) for gas-proof: 85 C (T6), 100 C (T5), and 120 C (T4) Maximum Surface Temperature for dustproof: T85 C (Tamb.: 40* to 40 C, Tp.: 80 C) T100 C (Tamb.: 40* to 60 C, Tp.: 100 C) T120 C (Tamb.: 40* to 80 C, Tp.: 120 C) * 15 C when /HE is specified.

Note 2. Electrical Data Supply voltage: 42 V dc max. Output signal: 4 to 20 ma Note 3. Installation requirement. The cable entry devices shall be of a certified flameproof type, suitable for the conditions of use. Note 4. Operation Keep the label attached to the transmitter. : AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP. 65 C, USE HEAT-RESISTING CABLES 90 C. Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location. Note 5. Maintenance and Repair The instrument modification or part replacement by other than an authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA Flameproof Certification. To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port. (2) Electrical Connection A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as followed. Screw Size ISO M20 1.5 female ANSI 1/2 NPT female Marking M A or W (3) Installation requirements and the local electrical code. There is no need for conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory. (4) Operation OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER S MANUAL Take care not to generate mechanical sparking when access to the instrument and peripheral devices in a hazardous location. (5) Maintenance and Repair The instrument modification or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certification. (6) Name Plate Name plate Tag plate for flameproof type D No. KEMA 07ATEX0109 Ex d IIC T6...T4, Ex td A21, IP6X Enlcosure : IP66, IP67 TEMP. CLASS T6 T5 T4 MAX PROCESS 85 100 120 TEMP.(Tp.) C Tamb. -50 to 75 80 75 C T85 C(Tamb.:40 C, Tp.:80 C),T100 C(Tamb.:60 C, Tp.:100 C), T120 C(Tamb.:80 C, Tp.:120 C) Min.Tamb.:-40(-15) C(for Dust) AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP. 65 C, USE THE HEAT-RESISTING CABLES 90 C Location of the mark F0208.ai Tag plate for intrinsically safe type No. KEMA 03ATEX1544 X EEx ia IIC T4 IP66 and IP67 Tamb. -50 to 60 C MIN. Tamb.:-40(-15) C(for DUST) MAX. PROCESS TEMP.(Tp.) 120 C T85 C(Tp.:80 C), T100 C(Tp.:100 C), T120 C(Tp.:120 C) Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0 D F0209.ai

MODEL: Specified model code. STYLE: Style code. SUFFIX: Specified suffix code. SUPPLY: Supply voltage. OUTPUT: Output signal. MWP: Maximum working pressure. CAL RNG: Specified calibration range. NO.: Serial number and year of production* 1. TOKYO 180-8750 JAPAN: The manufacturer name and the address* 2. *1: The first digit in the final three numbers of the serial number appearing after NO. on the nameplate indicates the year of production. The following is an example of a serial number for a product that was produced in 2010: 91K819857 032 The year 2010 *2: 180-8750 is a zip code which represents the following address. 2-9-32 Nakacho, Musashino-shi, Tokyo Japan ( II ) ATEX Certification (1) Technical Data a. ATEX Intrinsically Safe Type Caution for ATEX Intrinsically safe type. Note 1. EJX/EJA-E series pressure transmitters with optional code /KS26 for potentially explosive atmospheres: No. KEMA 04ATEX1116 X Applicable Standard: EN 60079-0:2009, EN 60079-11:2007/EN 60079-11:2012, EN 60079-26:2007, EN 60079-27:2008, EN 61241-11:2006 Note 2. Ratings Type of Protection and Marking Code: Ex ia IIC/IIB T4 Ga Ex ia IIIC T85 C T100 C T120 C Db Group: II Category: 1G, 2D Ambient Temperature for EPL Ga: 40 to 60 C Ambient Temperature for EPL Db: 30* to 60 C * 15 C when /HE is specified. Maximum Process Temperature (Tp.): 120 C Maximum Surface Temperature for EPL Db. T85 C (Tp.: 80 C) T100 C (Tp.: 100 C) T120 C (Tp.: 120 C) Ambient Humidity: 0 to 100% (No condensation) Degree of Protection of the Enclosure: IP66 / IP67 Electrical Data When combined with Trapezoidal and Rectangular output characteristic FISCO model IIC barrier Ui = 17.5 V, Ii = 380 ma, Pi = 5.32 W, Ci = 3.52 nf, Li = 0 μh When combined with Linear characteristic barrier Ui = 24 V, Ii = 250 ma, Pi = 1.2 W, Ci = 3.52 nf, Li = 0 μh When combined with Trapezoidal or Rectangular output characteristic FISCO model IIB barrier Ui = 17.5 V, Ii = 460 ma, Pi = 5.32 W, Ci = 3.52 nf, Li = 0 μh

Note 3. Installation requirements. (Refer to the installation diagram) Note 4. Maintenance and Repair The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void DEKRA Intrinsically safe Certification. Note 5. Special Conditions for Safe Use In the case where the enclosure of the Pressure is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded. Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the generation of electrostatic charge, such as rubbing with a dry cloth on coating face of the product. In the case where the enclosure of the Pressure is made of aluminum, if it is mounted in an area where the use of category 2D apparatus is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided. To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port. When the lightning protector option is specified, the apparatus is not capable of withstanding the 500V insulation test required by EN60079-11. This must be taken into account when installing the apparatus. Note 6. Installation Instructions Safety Barrier SUPPLY Hazardous Location Non-Hazardous Location Pressure F0212.ai In the rating 1(*1), the output current of the barrier must be limited by a resistor Ra such that Io = Uo/Ra. In the rating 2(*2), the output of the barrier must be the characteristics of the trapezoid or the rectangle and this transmitter can be connected to Fieldbus equipment which are in according to the FISCO model. The terminators may be built in by a barrier. More than one transmitter may be connected to the power supply line. The terminator and the safety barrier shall be certified. Electrical data: Maximum Input Voltage Ui: 24 V Maximum Input Current Ii: 250 ma Maximum Input Power Pi: 1.2 W Maximum Internal Capacitance Ci: 3.52 nf Maximum Internal Inductance Li: 0 μh or Maximum Input Voltage Ui: 17.5 V Maximum Input Current Ii: 380 ma Maximum Input Power Pi: 5.32 W Maximum Internal Capacitance Ci: 3.52 nf Maximum Internal Inductance Li: 0 μh or Maximum Input Voltage Ui: 17.5 V Maximum Input Current Ii: 460 ma Maximum Input Power Pi: 5.32 W Maximum Internal Capacitance Ci: 3.52 nf Maximum Internal Inductance Li: 0 μh *1: Rating 1 *2: Rating 2

(2) Electrical Connection (6) Name Plate A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as follows. Name plate MODEL STYLE CAL RNG SUFFIX Screw Size ISO M20 1.5 female Marking M SUPPLY OUTPUT MWP ma DC V DC NO. Made in Japan TOKYO 180-8750 JAPAN : Refer to USER'S MANUAL. ANSI 1/2 NPT female N or W Tag plate for intrinsically safe type No. KEMA 04ATEX1116 X Ex ia IIC/IIB T4 Ga Ta:-40 to 60 C Ex ia IIIC T85 C T100 C T120 C Db Ta:-30(-15) to 60 C MAX PROCESS TEMP.(Tp.):120 C T85 C(Tp.:80 C), T100 C(Tp.:100 C), T120 C(Tp.:120 C) Enclosure: IP66/IP67 FISCO field device(iic/iib) Entity parameters Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0μH Location of the mark D F0214.ai POTENTIAL ELECTROSTATIC CHARTGING HAZARD - SEE USER'S MANUAL. (3) Installation requirements and the local electrical code. There is no need for a conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory. (4) Operation OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER S MANUAL Take care not to generate mechanical sparking when accessing the instrument and peripheral devices in a hazardous location. STYLE: Style code. SUFFIX: Specified suffix code. SUPPLY: Supply voltage. OUTPUT: Output signal. MWP: Maximum working pressure. CAL RNG: Specified calibration range. NO.: Serial number and year of production *1. TOKYO 180-8750 JAPAN: The manufacturer name and the address *2. F0213.ai *1: The first digit in the final three numbers of the serial number appearing after NO. on the name plate indicates the year of production. The following is an example of a serial number for a product that was produced in 2010: 91K819857 032 The year 2010 *2: 180-8750 is the Zip code for the following address. 2-9-32 Nakacho, Musashino-shi, Tokyo Japan (5) Maintenance and Repair The instrument modification or part replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certification.

User s Manual DPharp Differential Pressure and Pressure s Manual Change No. 12-023 Please correct the information on the following manual as listed below. IM 01C25T02-01E (12th) Page and Item P.2-10 c. ATEX Type of Protection n Note 1. P.2-10 c. ATEX Type of Protection n Note 2 P.2-10 P.2-11 (6) Name Plate Correct Information Applicable Standard: EN 60079-0:2009, EN 60079-15:2005 Electrical Data Ui=32 Vdc, Ci=3.52 nf, Li=0 μh See the picture ( I ) in below. See the picture ( II ) in below. ( I ) Non-Hazardous Locations (Zone2) Hazardous Locations U Associated apparatus Hand- held- Terminal Field Instruments (Passive) F0209.ai ( II ) Tag plate for type n protection Ex nl IIC T4 Gc ENCLOSURE IP66/IP67 Tamb. -30(-15) to 60 C MAX. PROCESS TEMP. 120 C Ui=32V, Ci=3.52nF, Li=0µH POTENTIAL ELECTROSTATIC CHARTGING HAZARD - SEE USER'S MANUAL. F0211a.ai Oct. 5, 2012