PRE-RENOVATION INSPECTION: ASBESTOS & LEAD PAINT. Stantec. Site: 308 Oak Street Slinger, WI. Work Area: Pre-Renovation

Similar documents
PRE-RENOVATION INSPECTION: ASBESTOS & LEAD PAINT. Stantec. Site: 310 Oak Street Slinger, WI. Work Area: Pre-Renovation

LEAD-BASED PAINT SCREENING REPORT

Harris Apartments 836 South 500 East Salt Lake City, Utah. May 1, Submitted to:

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

Central Michigan University

March 12, Monica Estavillo San Jacinto Unified School District 905 Industrial Way San Jacinto, CA 92583

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation.

Lead Safety for Renovation, Repair, and Painting Module Overview

CENTRAL MICHIGAN UNIVERSITY

ASBESTOS BUILDING SURVEY REPORT

All bids must be submitted in a sealed envelope and plainly labeled on the outer most package RFP CDBG Housing

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

SAINT PAUL PUBLIC SCHOOLS Six Month Periodic Surveillance Report for Riverview Elementary 271 Belvidere Street East Saint Paul, MN Key

DATE SENT: RESPONSE NEEDED: YES NO SUBJECT: Risk Assessment(s)

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

If the address on this form is different than the address of the building, submit a written explanation.

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

LIMITED LEAD-BASED PAINT (LBP) EVALUATION

If the address on this form is different than the address of the building, submit a written explanation.

Housing and Neighborhood Services of Rock Hill SCOPE OF WORK BID TAB. Job # BID-CDBG #16

If the address on this form is different than the address of the building, submit a written explanation.

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

THREE-YEAR RE-INSPECTION and ASBESTOS MANAGEMENT PLAN for the

Limited Lead-based Paint Inspection City of Hermosa Beach Building Assessment Project Multiple Buildings Hermosa Beach, CA 90254

BUILDING PLANS. BUILDING INSPECTIONS DEPARTMENT

If the address on this form is different than the address of the building, submit a written explanation.

Material List for Log Complete Packages

November 30, Courtney Wilton Portland Public Schools 501 North Dixon Portland, OR 97227

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS:

LEAD-BASED PAINT EVALUATION AND DISCLOSURE. Determining the Presence of Lead-Based Paint. Disclosure of Lead-Based Paint Information

Material Description Qty Units Cost Total SQUARE FOOTAGE TOTAL Area 1692 sqft

BUILDING PLANS. BUILDING DEPARTMENT

HowtoPlans..org. 10'x10' Storage Shed Plan

Estimated Cost of Project Contractor License No. Contractor Qualifier No.

March 1, Courtney Wilton Portland Public Schools 501 North Dixon Portland, OR 97227

SERIES 300 SINGLE HUNG WINDOW INSTALLATION

Installation Instructions for Standard Lap and Self-Aligning Lap Siding

Carpentry/Carpenter CIP Task Grid

INSTALLATION GUIDE WOOD PIVOTING CIRCLE/ OVAL

Painting Hard Co. Inc.

Chicago Public Schools 6 Month Asbestos Surveillance Fall

Chicago Public Schools 6 Month Asbestos Surveillance Fall

Installation Instructions for Panel Siding and Soffit

Vinyl Windows and Doors Manufactured by VPI Quality Windows

Strands & Standards CARPENTRY 2

SERIES 300 SINGLE HUNG WITH FIN WINDOW INSTALLATION

MAGNUM. I N S P E C T I O N S Inc. ROOF Walked on roof, crawled attic where accessible.

Entry Level Assessment Blueprint Carpentry

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding

KNOXVILLE HISTORIC ZONING COMMISSION STAFF REPORT CERTIFICATE OF APPROPRIATENESS APPLICATION

INVITATION TO TENDER ITT / NO. PS CONSTRUCTION SERVICES FOR THE VANCOUVER SOUTH TRANSFER STATION ODOR AND DUST CONTROL SYSTEM IMPROVEMENTS

8/7/ HP SWING DOOR INSTALLATION INSTRUCTIONS

Entry Level Assessment Blueprint Carpentry

SPECIFICATIONS PROPOSAL & BID DOCUMENT

Addendum #1 - Bid Package #

PAST EXAM PAPER & MEMO N3 ABOUT THE QUESTION PAPERS:

ADDENDUM #1. April 29, 2009

ADDENDUM NO. 1 November 10, 2016

Tools required by installer: Materials required by installer:

ASBESTOS OPERATIONS AND MAINTENANCE PROGRAM. Prepared for: FALMOUTH PUBLIC SCHOOLS FALMOUTH, MASSACHUSETTS. Prepared by:

LEAD DESIGN SPECIFICATIONS

Installation Instructions for TruWood Reversible Trim

HowtoPlans..org. Apollo 10'x12' Storage Shed Plan

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

HowtoPlans..org. 14'x8' Garden Shed Plan

Building Wrap and Flashing

HowtoPlans..org. 10'x16' Storage Shed Plan

Installation Guide for E-Series/Eagle Clad Mechanically Fastened Windows

Dear Contractor, I am glad that you are interested in our window rebate program.

1.04 QUALITY ASSURANCE

Quick Reference Guide For MoistureFree Certified Inspectors and Contractors

Address: South Elgin, IL Phone: ( ) - Fax: ( ) - Cell: ( ) - Contractor Type: Phone: ( ) - Fax: ( ) - Cell: ( ) - Contact Type:

STACKING MULTI-SLIDE DOOR SYSTEM

EVALUATION REPORT GAF Materials Corporation 1361 Alps Road, Building 7-3 Wayne, NJ 07470

SPARTAN DAY CAMP 4814 FREEDOM RING RD

ROOFING City of Grand Rapids Building Safety Division

Building Wrap and Flashing

HowtoPlans..org. Luxe 12'x6' Garden Shed Plan

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

HowtoPlans..org. Skyline 10'x14' Garden Shed Plan

HowtoPlans..org. 12'x20' Garden Shed Plan

Vinyl Windows Manufactured by VPI Quality Windows

HowtoPlans..org. 8'x10' Storage Shed Plan

Architrave: The molded from or ornament surrounding a window, door or other rectangular opening.

HowtoPlans..org. 8'x12' Storage Shed Plan

Installation Recommendations for Finless Frame Doors

Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications.

HowtoPlans..org. 6'x8' Storage Shed Plan

The Carving Studio. A Woodworker s Paradise

4' x 12' Walk-In Chicken Coop Plan. Designed for 3-5 chickens

Transcription:

PRE-RENOVATION INSPECTION: ASBESTOS & LEAD PAINT Stantec Site: Work Area: Pre-Renovation Inspection Date: February 22, 2016 Report Date: March 10, 2016 NorthStar No. 160-064 Submitted By: NorthStar Environmental Testing, LLC.

March 10, 2016 Stantec 12075 Corporate Parkway Suite 200 Mequon, WI 53092 Reference: Pre-Renovation Inspection NorthStar Environmental Testing, LLC was contracted by Stantec to complete a pre-renovation inspection to identify the presence of materials containing asbestos and building components with leadbased paint from throughout the property located at in. The inspection was conducted by Aaron Stroud of NorthStar Environmental Testing, LLC (NorthStar) on February 22, 2016. Asbestos materials were identified in window glazing (metal frame), pipe insulation, pipe fitting debris, 9 floor tile, transite box, gray sink undercoating and black rolled roofing. Electrical panels are assumed to contain asbestos and should be sampled if/when necessary. Lead-based paint was also identified in some areas. Please review the report in its entirety for more detailed information. Prepared by: NorthStar Environmental Testing, LLC. 1835 E. Edgewood Drive Suite 10542 Appleton, WI 54913 Provided to: Stantec 12075 Corporate Parkway Suite 200 Mequon, WI 53092 Date of Site Visit: February 22, 2016 NorthStar Environmental Testing, LLC. David Barrett Owner, Senior Project Manager Aaron Stroud Operations Manager NorthStar No. 160-064

TABLE OF CONTENTS INSPECTION SUMMARY.. Page 1 ASBESTOS SAMPLING SUMMARY.. Page 1 ASBESTOS MATERIAL SUMMARY Page 2 ASBESTOS RECOMMENDATIONS Page 3 SURVEY LIMITATIONS. Page 3 ANALYTICAL DISCUSSION. Page 3 REMARKS... Page 4 APPENDICES A) Asbestos Sample Log... 2 Pages B) Lead Paint Testing Report... 6 Pages C) NorthStar Certifications.. 4 Pages NorthStar No. 160-064

March 10, 2016 Stantec 12075 Corporate Parkway Suite 200 Mequon, WI 53092 Project: Asbestos Inspection Site Address: Work Area: Pre-Renovation Survey Date: February 22, 2016 NorthStar No: 160-064 NorthStar Environmental Testing, LLC (NorthStar) was authorized by Stantec to conduct a prerenovation survey for the presence of accessible suspect asbestos containing materials (ACM) for the following site: INSPECTION SUMMARY: Site Address: County: Washington County Structure Type: Commercial Bldg Age: 1933 (with additions) Size (ft²): 5,400 ft² (approximate) Floors: 2 # of Structures: 1 Inspector: Aaron Stroud Cert: AII-108183 Asbestos Company: CAP-925800 Survey Date: February 22, 2016 Comments: The building consists of a concrete slab foundation, wood interior/exterior walls (north), concrete block interior walls and vinyl siding exterior (south), and sloped asphalt roofing materials. SAMPLING SUMMARY: Number of Samples: 32 Number Analyzed: 32 Point Count Analysis: 1 Analysis Date: March 1, 2016 Asbestos Material: Window Glazing (metal frame) Pipe Insulation Pipe Fitting Debris 9 Floor Tile Transite Box Gray Sink Undercoating Black Rolled Roofing Assumed ACM: Electrical Panels Laboratory: CEI Labs, Inc. NVLAP: 101768-0 Analysis Date: February 26, 2016 The attached Bulk Sample Log-in contains complete sample analysis data. NorthStar No. 160-064 Pre-renovation Inspection Page 1 of 4

ASBESTOS MATERIAL SUMMARY: Confirmed ACBM, or presumed ACBM that will require abatement if these materials will be impacted by the intended renovation: Material Building Area Quantity Comment/Condition (approx) Window Glazing (metal frame) Plating Room 3 ft 2 (3 each) Cat II non-friable / approximately 3 x 3 Pipe Insulation Main Room (south center) 6 linear feet under raised floor / Friable Pipe Fitting Debris Main Room (northwest) 2 ft 2 debris on pipe near ceiling / Friable 9 Floor Tile Second Floor: Office 270 ft 2 on wood / CAT I non-friable Transite Box Second Floor: Mezzanine 6 ft 2 CATII non-friable Gray Sink Undercoating Second Floor: Office 4 ft 2 CAT II non-friable Black Rolled Roofing Roof 3,300 ft 2 on wood / CAT I non-friable Electrical Panels Throughout 14 ft 2 (14 each) assumed / CATII non-friable Material quantities are listed according to visible estimates at the time of the survey. It is recommended that all quantities be further verified by the building owner or an abatement contractor prior to project design, bidding, budgeting and/or DNR notification purposes. The following materials were found to be non-asbestos or less than 1% by PLM analysis: white door caulk tan asphalt shingles ceramic floor tile adhesive kiln fire brick 2 x4 pinhole crater ceiling tile 2 x4 textured ceiling tile cream vinyl sheet flooring & adhesive 2 x4 pinhole fissured ceiling tile foundation texture black flooring underlayment Material tan blown-in insulation tar paper roofing felt ceramic floor tile grout kiln skim coating tar paper 4 cream vinyl baseboard & adhesive coating on 2 x2 ceiling tile brown asphalt shingle window glazing (wood frame window) The attached Bulk Sample Log-in contains complete sample analysis data. The following areas were inaccessible or excluded at the time of inspection and may contain additional quantities of suspect asbestos containing materials: Area Electrical interiors were inaccessible and may contain additional suspect asbestos materials. These areas should be assumed to contain asbestos unless sampled and proven otherwise. NorthStar No. 160-064 Pre-renovation Inspection Page 2 of 4

ASBESTOS RECOMMENDATION: All friable ACBM as well as non-friable ACBM that would likely be made friable by the intended renovation or demolition processes are required to be abated prior to disturbance. Non-friable ACBM (confirmed or assumed) remaining during demolition must be disposed of properly as demolition debris at an approved landfill. Non-friable materials typically require abatement prior to any material recycling procedure. For any building that will be subject to burning, all confirmed and presumed ACBM must be removed. Abatement shall be performed by an abatement company utilizing trained and certified worker/supervisor and further licensed as an asbestos company by the Wisconsin Company of Health Service (DHS), asbestos regulation 159. Refer to Wisconsin Company of Natural Resources (WDNR) 447; and DHS 159 for complete information on requirements for asbestos abatement and asbestos material disposal. SURVEY LIMITATIONS: Sample results, quantities and recommendation are limited to areas that were accessible to us during the investigation. Additional presumed-acbm that may have been located in spaces not accessible during our investigation, hidden from view, or not sampled at the client s request may require additional sampling prior to disturbance by renovation or demolition activity. Typical areas that may be inaccessible during an investigation include: wall or ceiling cavities; electrical components/wiring, equipment interiors; chimneys/flues/stacks; spaces requiring confined space entry procedures. Additional materials not accessible during a typical building materials survey include items such as miscellaneous caulkings, sealants and construction adhesives that are not readily accessible to sampling as they are often located between layers of building components. These materials are typically non-friable in nature but may require further sampling to confirm or deny the presence of asbestos. Additional presumed ACBM encountered during renovation or demolition activity, that differs from materials sampled or described during this survey must be assumed to contain asbestos and be abated or be sampled to determine asbestos content prior to disturbance. Material quantities are listed according to visible estimates at the time of the survey. It is recommended that all quantities be further verified by building owner or abatement contractor prior to project design, bidding and/or DNR notification purposes. ANALYTICAL DISCUSSION: Bulk sample analysis for asbestos was performed by polarized light microscopy (PLM); method EPA 600/r- 93-116. Samples showing a result of "None Detected" were found to contain no asbestos in any analyzed portion of the sample. USEPA defines an ACBM as one that contains greater than one percent asbestos. For a sample result showing less than one percent (<1%) of asbestos, the material can be may be treated as a non-asbestos containing material. The building owner or client should be aware that exposure to asbestos is still possible following disturbance of material with a trace or <1% of asbestos present and that worker protection procedures may be necessary. NorthStar No. 160-064 Pre-renovation Inspection Page 3 of 4

REMARKS: The survey and subsequent report has been performed according to applicable regulations and generally accepted industry standards and practices in this locality under similar conditions. Information provided to us by building owner/occupant, client or other interested party that may have been utilized in the performance and reporting of the survey was accepted in good faith and can only be assumed to be accurate. The findings and recommendations made are representative of our professional opinion based on currently available information, no other warranty is implied or intended. Please contact us if you have any questions regarding the presented information or the project in general. Sincerely, NorthStar Environmental Testing, LLC. David Barrett Senior Project Manager Aaron Stroud Operations Manager NorthStar No. 160-064 Pre-renovation Inspection Page 4 of 4

Appendix A ASBESTOS SAMPLE LOG Stantec February 2016

ASBESTOS BULK SAMPLE LOG-IN CLIENT: Stantec NORTHSTAR NO. 160-064 LOCATION: - DATE COLLECTED: 2/22/16 WORK AREA: Pre-Renovation TECH: Aaron Stroud Sample ID Level Room / Area Info Sample Info Asbestos Content 308-1 1 Plating Room White Door Caulk None Detected (west wall, south) 308-2 1 Plating Room Window Glazing 3% Chrysotile (west wall) (metal frame window) 308-3 1 Plating Room Tan Blown-in Insulation None Detected (north wall) 308-4 1 Plating Room Window Glazing <1% Chrysotile (north wall) (wood frame window) 308-5 1 Plating Room Tan Asphalt Shingle None Detected (attic) 308-6 1 Plating Room Tar Paper Roofing Felt None Detected (attic) 308-7 1 Restroom Ceramic Floor Tile None Detected Adhesive 308-8 1 Restroom Ceramic Floor Tile Grout None Detected 308-9 1 Tall Room Kiln Fire Brick None Detected 308-10 1 Tall Room Kiln Skim Coating None Detected 308-11 1 Tall Room 2 x4 Pinhole Crater None Detected Ceiling Tile 308-12 1 Main Room Pipe Insulation 65% Chrysotile (under raised floor) 308-13 1 Main Room Pipe Fitting Debris 65% Chrysotile (northwest, near ceiling) 308-14 1 Main Room Tar Paper None Detected (under raised floor) 308-15 1 Locker Room 2 x4 Textured Ceiling None Detected Tile 308-16 2 Restroom 4 Cream Vinyl None Detected Baseboard 308-17 2 Restroom Tan Baseboard Adhesive None Detected 308-18 2 Restroom Cream Vinyl Sheet Flooring None Detected Lab Info: CEI Labs, Inc. Date Analyzed: 2/26/16 Page: 1 of 2

CLIENT: Stantec NORTHSTAR NO. 160-064 LOCATION: - DATE COLLECTED: 2/22/16 WORK AREA: Pre-Renovation TECH: Aaron Stroud Sample ID Level Room / Area Info Sample Info Asbestos Content 308-19 2 Restroom Tan Flooring Adhesive None Detected 308-20 2 Restroom Coating on 2 x2 Ceiling None Detected Tile 308-21 2 Office 2 x4 Pinhole Fissured None Detected Ceiling Tile 308-22 2 Office 9 Light Gray Floor Tile 10% Chrysotile 308-23 2 Office 9 Dark Gray Floor Tile 10% Chrysotile 308-24 2 Office Black Flooring None Detected Underlayment 308-25 2 Office Gray Sink Undercoating 10% Chrysotile 308-26 2 Mezzanine Transite Box 20% Chrysotile 308-27 Roof Main Roof (top layer) Brown Asphalt Shingle 308-28 Roof Main Roof Black Rolled Roofing (second layer) 308-29 Ext Exterior: South Window Glazing (second floor) (wood frame window) 308-30 Ext Exterior: North Foundation Texture (on foam) 308-31 Ext Exterior: East Foundation Texture (on foam) 308-32 Ext Exterior: East Foundation Texture (on foam) None Detected 10% Chrysotile 2% Chrysotile Point Count: 0.27% None Detected None Detected None Detected Lab Info: CEI Labs, Inc. Date Analyzed: 2/26/16 Page: 2 of 2

Appendix B LEAD PAINT TESTING REPORT Stantec February 2016

March 10, 2016 Stantec 12075 Corporate Parkway Suite 200 Mequon, WI 53092 Project: Site Address: Lead Paint Inspection (limited) Pre-Renovation Work Area: Site Date: February 22, 2016 NorthStar No: 160-064 NorthStar Environmental Testing, LLC (NorthStar) was authorized by Stantec to perform limited, nondestructive inspection for the presence of lead in paint on designated surfaces prior to potential disturbance by specific renovation activity. Testing for lead based paint was limited to representative areas. A surface-by-surface visual assessment of painted components was conducted at the property to determine which areas/substrates to test. TESTING SUMMARY (XRF): Testing Date: February 22, 2016 Building/Site: Building Contact: Chris Hatfield (Stantec) Phone: 262.643.9171 Work Area: Pre-Renovation Materials Tested Pre-Renovation: Representative painted surfaces (primarily floors, walls, ceilings, window components, and door components) Lead Paint for Renovation Items: Lead paint was identified primarily on exterior components and in some isolated interior areas. Visual Assessment: Deteriorated lead paint was noted on the exterior of the building and on the door & ceiling of the break room (second floor). Sampling Tech: Aaron Stroud Cert No.: LRA-108183 Lead Company: HFS-925800 Expiration Date: 08/01/2017 Testing Equipment: RMD LPA-1 XRF analyzer, Serial Number: 3499 Comment: Sampling was limited to representative surfaces within accessible areas of the building. Any additional items not specifically sampled should be assumed to contain lead unless additional testing proves otherwise. NorthStar No. 160-064 Lead Paint Inspection Page 1 of 3

LEAD PAINT SUMMARY: Testing for lead-based paint analyzes all layers of paint on a particular surface area simultaneously. The testing does not specifically identify which layer or color of paint contains lead. A positive testing location entails that some layer of paint on that particular surface contains lead in paint in excess or equal to 1.0 mg/cm². Reading No Wall Structure Location Member Paint Condition Substrate Color Lead (mg/cm2) Exterior Room 001 Niphos 101 A Soffit Poor Wood Tan 4.6 102 A Fascia Poor Wood Tan 5.2 105 B Wall L Lft Poor Wood Tan 4 106 B Window Lft Lft casing Poor Wood Tan 3.6 107 B Window Lft Sash Poor Wood Tan 2.8 108 C Wall L Rgt Poor Wood Tan 4.2 109 C Soffit Poor Wood Tan 4.8 111 C Window Lft Lft casing Poor Wood Tan 3.8 112 D Window Rgt Lft casing Poor Wood Tan 3.5 113 D Wall L Rgt Poor Wood Tan 4.1 Interior Room 001 Plating Room 14 C Wall U Ctr Intact Wood Gray >9.9 15 C Window Ctr Lft casing Intact Wood Orange 4.6 16 C Window Ctr Sash Intact Wood Black 3.8 17 C Door Lft Lft casing Intact Wood Orange 4.3 18 C Door Lft Lft jamb Intact Wood Orange 3.9 Interior Room 002 Garage 21 C Wall L Ctr Intact Wood White >9.9 Interior Room 005 Main Room 45 C Wall L Rgt Intact Wood Tan 4.2 46 D Wall L Lft Intact Wood Tan 3.9 47 C Window Rgt Lft casing Intact Wood Blue 2.6 48 C Ceiling Intact Wood Tan 1.7 50 D Door Lft Lft jamb Intact Wood Blue 1.1 51 D Door Lft U Ctr Intact Wood White 3.7 Interior Room 007 Break Room 65 C Wall U Lft Intact Wood White 4.1 67 B Door Lft U Ctr Poor Wood White 3.8 68 C Door Lft U Ctr Intact Wood White 4.3 69 C Ceiling Poor Wood White 1.2 Summary: Lead-based paint (LBP) was identified on the exterior of the original building structure. This includes the interior north wall of rooms 01 Plating Room & 02 Garage. LBP was also identified in the northeast corner of room 05 Main on wood wall/ceiling paneling and window components. Similarly, LBP was found on the wood paneling (C wall & ceiling) and doors of the second floor 07 Break Room. * Wall A is the South side of the building. Walls B/C/D are determined clockwise from Wall A. * All similar materials with the same paint history are to be categorized in the same manner. For example if a window sill on side A is positive for lead-based paint, then all similar window sills are assumed to contain lead-based paint. NorthStar No. 160-064 Lead Paint Inspection Page 2 of 3

DISCUSSION: The testing performed was limited in scope and does not constitute a full lead paint inspection. Demolition activity beyond the anticipated work scope specified at the time of our site visit may require additional testing prior to disturbance. The United States Federal Government through the Environmental Protection Agency (EPA) and Housing and Urban Development (HUD) defines lead-based paint as equal to or greater than 1.0 mg/cm ² measured by XRF analysis, or 0.5% (5000 ppm) measured by weight through laboratory analysis. The State of Wisconsin has adopted the same definition of lead bearing paint (mainly for residential HUD applications) as that which is equal to or greater than 1.0 mg/cm 2 or 0.5% (5000 ppm) respectively. Our non-destructive testing by x-ray fluorescence has been performed in an attempt to screen for areas with quantifiable lead above regulatory limits on painted substrates. The reportable limit of detection is essentially 1.0 mg/cm ² by XRF analysis and therefore paint chip analysis would be recommended for a more accurate determination of lead in paint below this level or for results to rule out lead in any quantifiable amount. The testing equipment is calibrated against a known standard before and after actual substrate testing. For worker exposure applications, lead in any quantifiable amount, and disturbance of the material creating dust and/or fumes and subsequent potential worker exposure would be regulated by the OSHA lead in construction standard (29 CFR 1926.62). REMARKS: The testing and subsequent report has been performed according to applicable regulations and generally accepted industry standards and practices in this locality under similar conditions. Information provided to us by the building owner/occupant, client or other interested party that may have been utilized in the performance and reporting of the testing was accepted in good faith and can only be assumed to be accurate. The findings and recommendations made are representative of our professional opinion based on currently available information; no other warranty is implied or intended. Please contact us if you have any questions regarding the presented information or the project in general. Submitted By, NorthStar Environmental Testing, LLC. David Barrett Senior Project Manager Aaron Stroud Operations Manager Attach: testing data NorthStar No. 160-064 Lead Paint Inspection Page 3 of 3

LEAD PAINT XRF TESTING DATA CLIENT: Stantec NORTHSTAR NO. 160-064 LOCATION: SITE DATE: February 22, 2016 WORK AREA: Pre-Renovation TECH: A Stroud Reading No Wall Structure Location Member Paint Condition Substrate Color Lead (mg/cm2) Interior Room 999 Calibration 1 1.1 2 1 3 1 4 0 Exterior Room 001 Niphos 101 A Soffit Poor Wood Tan 4.6 102 A Fascia Poor Wood Tan 5.2 103 B Wall L Rgt Intact Conc Block Tan -0.3 104 B Door Ctr U Ctr Poor Metal Tan 0.1 105 B Wall L Lft Poor Wood Tan 4 106 B Window Lft Lft casing Poor Wood Tan 3.6 107 B Window Lft Sash Poor Wood Tan 2.8 108 C Wall L Rgt Poor Wood Tan 4.2 109 C Soffit Poor Wood Tan 4.8 110 C Stairs Ctr Stringer Poor Metal Tan 0.3 111 C Window Lft Lft casing Poor Wood Tan 3.8 112 D Window Rgt Lft casing Poor Wood Tan 3.5 113 D Wall L Rgt Poor Wood Tan 4.1 Interior Room 001 Plating Room 5 B Floor Poor Concrete Orange 0.2 6 A Wall L Ctr Intact Conc Block Orange 0 7 A Wall U Ctr Intact Conc Block Yellow -0.3 8 B Wall U Lft Intact Conc Block Yellow -0.4 9 B Wall L Lft Intact Conc Block Orange -0.2 10 D Wall L Ctr Intact Conc Block Orange 0 11 D Wall U Ctr Intact Conc Block Yellow -0.1 12 D Horz Beam Ctr Poor Metal Yellow 0.1 13 D Horz Beam Ctr Poor Metal Yellow 0.2 14 C Wall U Ctr Intact Wood Gray >9.9 15 C Window Ctr Lft casing Intact Wood Orange 4.6 16 C Window Ctr Sash Intact Wood Black 3.8 17 C Door Lft Lft casing Intact Wood Orange 4.3 18 C Door Lft Lft jamb Intact Wood Orange 3.9 Interior Room 002 Garage 19 C Door Rgt U Ctr Intact Wood Varnish -0.5 20 C Door Rgt Lft casing Intact Wood White -0.1 21 C Wall L Ctr Intact Wood White >9.9 22 B Wall U Ctr Intact Conc Block White -0.4 23 A Wall U Ctr Intact Conc Block White -0.5 24 A Floor Intact Concrete Orange 0.2 * Wall A is the South side of the building. Walls B/C/D are determined clockwise from Wall A. Page 1 of 3

Reading No Wall Structure Location Member Paint Condition Substrate Color Lead (mg/cm2) Interior Room 003 Tall Room 25 A Wall U Ctr Intact Wood White -0.1 26 B Wall U Lft Intact Wood White -0.2 27 B Window Lft Lft casing Intact Wood Orange 0.1 28 B Window Lft Sill Intact Wood Orange -0.3 29 B Window Lft Sash Intact Wood Orange 0 30 B Door Lft Lft casing Intact Wood Tan -0.4 31 B Floor Intact Wood Tan -0.2 32 B Wall U Rgt Poor Wood Tan 0.1 33 C Wall L Ctr Poor Wood Tan -0.1 34 D Wall L Ctr Poor Wood Tan 0.1 35 D Door Rgt Lft casing Intact Wood Orange -0.3 36 D Door Rgt U Ctr Intact Wood White 0 37 D Ceiling Poor Wood White -0.3 Interior Room 005 Main Room 38 A Wall L Ctr Intact Wood White 0.1 39 B Wall L Ctr Intact Wood Tan 0.1 40 B Window Rgt Lft casing Intact Wood Blue -0.1 41 B Window Rgt Sash Poor Wood White -0.1 42 C Wall L Lft Intact Wood Tan -0.3 43 D Chimney Lft Poor Brick White 0.3 44 C Floor Poor Concrete Orange 0.1 45 C Wall L Rgt Intact Wood Tan 4.2 46 D Wall L Lft Intact Wood Tan 3.9 47 C Window Rgt Lft casing Intact Wood Blue 2.6 48 C Ceiling Intact Wood Tan 1.7 49 C Baseboard Ctr Intact Concrete White -0.4 50 D Door Lft Lft jamb Intact Wood Blue 1.1 51 D Door Lft U Ctr Intact Wood White 3.7 52 D Floor Intact Wood Tan -0.1 53 D Wall L Rgt Intact Wood White -0.2 54 D Ceiling Intact Wood White -0.2 55 A Stairs Lft Risers Poor Wood White -0.4 56 A Stairs Lft Treads Poor Wood Tan -0.1 57 D Window Rgt Lft casing Intact Wood Tan -0.3 58 D Window Rgt Sash Intact Wood Tan -0.2 59 A Window Ctr Lft casing Intact Wood Orange 0 60 A Window Ctr Sash Intact Wood Orange 0.1 Interior Room 007 Break Room 61 A Window Rgt Lft casing Intact Wood Tan -0.2 62 A Window Rgt Sash Poor Wood Tan 0.1 63 A Wall L Rgt Intact Wood White -0.4 64 B Wall L Lft Intact Wood White -0.2 65 C Wall U Lft Intact Wood White 4.1 66 D Wall U Ctr Intact Wood White -0.3 67 B Door Lft U Ctr Poor Wood White 3.8 68 C Door Lft U Ctr Intact Wood White 4.3 69 C Ceiling Poor Wood White 1.2 70 C Floor Poor Wood Brown -0.2 * Wall A is the South side of the building. Walls B/C/D are determined clockwise from Wall A. Page 2 of 3

Reading No Wall Structure Location Member Paint Condition Substrate Color Lead (mg/cm2) Interior Room 008 Office 71 A Wall U Ctr Intact Wood White -0.5 72 B Wall U Ctr Intact Wood White -0.2 73 C Wall U Ctr Intact Wood White -0.4 74 D Wall U Ctr Intact Wood White -0.1 75 C Window Lft Lft jamb Poor Wood White -0.1 76 C Window Lft Sash Poor Wood White -0.1 Interior Room 009 Restroom 77 A Door Ctr Lft jamb Intact Wood Varnish -0.4 78 A Door Ctr U Ctr Intact Wood Varnish -0.6 Interior Room 010 Storage 79 A Wall U Ctr Intact Wood White 0.1 80 B Wall U Ctr Intact Wood White -0.2 81 C Wall U Ctr Intact Wood White 0 82 D Wall U Ctr Intact Wood White -0.3 83 D Ceiling Intact Wood White -0.1 84 A Floor Intact Wood Brown -0.2 85 B Window Rgt Lft casing Intact Wood Orange 0.1 86 B Window Rgt Sash Intact Wood White 0 87 D Door Rgt U Ctr Intact Wood White 0.1 88 D Door Rgt Lft casing Intact Wood Orange 0.1 Interior Room 011 Mezzanine 89 D Floor Poor Wood Gray -0.1 90 A Wall U Lft Intact Wood Tan -0.2 91 C Wall U Rgt Intact Wood Tan -0.3 92 D Wall U Ctr Intact Wood Tan -0.1 93 D Horz Beam Ctr Poor Wood White -0.3 94 D Vert Beam Ctr Poor Wood White -0.2 95 D Door Ctr Rgt casing Intact Wood White -0.3 96 D Door Ctr U Ctr Intact Wood White -0.4 Interior Room 012 Dark Room 97 A Wall U Lft Intact Wood Black -0.5 98 B Wall U Rgt Intact Wood Black -0.5 99 C Wall U Lft Intact Wood Black -0.4 100 D Wall U Rgt Intact Wood Black -0.2 Interior Room 999 Calibration 114 0.9 115 1 116 0.9 117-0.3 - The State of Wisconsin defines lead bearing paint as that which is equal to or greater than 1.0 mg/cm 2. - Readings with a negative value (i.e. -0.1) are equivalent to 0.0 * Wall A is the South side of the building. Walls B/C/D are determined clockwise from Wall A. Page 3 of 3

Appendix C CERTIFICATIONS NorthStar Environmental Testing, LLC.

Copy

Copy