Electromagnetic Flow Measuring System promag 33

Similar documents
Electromagnetic Flow Measuring System promag 35

Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 P

Electromagnetic Flow Measuring System Two-wire, loop-powered PROline promag 23 H

Technical Information Proline Promag 10P

Proline Promag 10P. Technical Information. Electromagnetic Flow Measuring System Flow measurement of liquids in chemical or process applications

Proline Promag 55S. Technical Information

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview

Coriolis Mass Flow Measuring System promass 40 E

Proline Promag 55S. Technical Information

Technical Information Proline Promag 55S

www. otech.com.sg EFS801 ELECTROMAGNETIC FLOWMETER

OPTIFLUX 5000 Technical Datasheet

OPTIFLUX 5000 Technical Datasheet

Flow Measurement SITRANS F M

Proline Promag 50W, 53W

Flow Measurement SITRANS F M. Transmitter TRANSMAG 2 with sensor 911/E 4/101. Overview

TIDALFLUX 2300 F Technical Datasheet

OPTIFLUX 1000 Technical Datasheet

Promag 55S. Technical Information. Electromagnetic Flow Measuring System Flow rate measurement of liquids with solids content or inhomogeneous liquids

Electromagnetic Flow Transmitter

SITRANS F flowmeters. SITRANS F System information MAGFLO electromagnetic flowmeters 4/9

Magnetic-inductive flow meter. PITe / UMF2. Technical Datasheet. Maintenance-free Nearly no pressure drop Robust design Easy installation and start-up

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters. 4/18 Siemens FI

Proline Promass 40E. Technical Information

FLOMID FX Electromagnetic Flowmeter

Magnetic-Inductive flow Meter fmi

Proline Promag 50P, 53P

Digital flow transmitter for continuous flow measurement

Digital inductive conductivity transmitter

INSERTION paddle wheel flowmeter for continuous flow measurement

Artisan Scientific is You~ Source for: Quality New and Certified-Used/Pre:-awned ECJuiflment

Ambient Conditions. Operating Conditions. Pressure

Digital flow ELEMENT transmitter for continuous flow measurement

Technical Information Proline Promag 10D

KFS. Flap-type flow meter. Design and range of application

Proline Promag 10W. Technical Information. Electromagnetic Flow Measuring System Flow measurement of liquids in water or wastewater applications

Technical Information Smartec CLD18

Electro-Magnetic Flowmeters COPA-XE

Design and applications

Proline Promag 55H. Technical Information

RTD Temperature Sensor omnigrad T -TSM 480, TR 480. Hygienic RTD sensor with Pt 100, class A TSM 480 with electronics programmable via PC

The transducer component converts the measured signal and displays the actual value.

Digital flow ELEMENT transmitter for continuous flow measurement

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview

Technical Information Smartec CLD18

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview

Flow Measurement SITRANS F M. Flow sensor MAG /49. Overview

INLINE flowmeter for continuous flow measurement

Flow Measurement SITRANS F M

Proline Promag 10D. Technical Information. Electromagnetic flow measuring system Flow measurement of liquids in water or wastewater applications

INLINE flowmeter for continuous flow measurement

Proline Promag 55H. Technical Information

INLINE flowmeter for continuous flow measurement

omnigrad T - TSM 480, TR 480. Technical Information. RTD Temperature Sensor Hygienic design TSM 480 with electronics programmable via PC

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

OPTIMASS 1000 Technical Datasheet

Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm

Technical Information Proline Promag 53E

Inductive conductivity measurement mypro CLM 431 / CLD 431 inductive

EN-2018 MAGNETIC FLOW METERS

prosonic T FMU230, FMU231

BATCHFLUX 5500 C Technical Datasheet

ABB MEASUREMENT & ANALYTICS DATA SHEET. HygienicMaster FEH630 Electromagnetic flowmeter

Proline Promag 50W, 53W

Technical Information Smartec CLD18

Radar Level Measurement micropilot FMR 130 for stilling wells

Proline Promass 40E. Technical Information

Conductive conductivity measurement mypro CLM 431 / CLD 431 conductive

Proline Promag 10H. Technical Information. Electromagnetic Flow Measuring System Flow measurement of liquids in hygienic, food or process applications

Digital flowmeter for continuous flow measurement

Technical Information Proline Promag L 400

Digital conductivity transmitter

Digital flowmeter for continuous flow measurement

Endress Hauser. SmarTec M CLD 133 Conductivity Measurement

Brief Operating Instructions Proline Promag 50

Technical Information Proline Promag W 400

Dosimass. Technical Information. Coriolis Mass Flow Measuring System For filling applications

VersaFlow Ultrasonic clamp-on Flowmeter Technical Datasheet. Specification. Applications. Highlights. Industries. 34-VF September 2009

Vortex Flow Measuring System prowirl 77

WATERFLUX 3070 Technical Datasheet

KFS-EM. Overall length. Al. PTFE coated Alu, painted Al. coated Methacrylate / acrylic nitrite

Technical Information Proline Promag 50H, 53H

Proline Promag 50H, 53H

Float Switches with Permanent Magnet For Vertical Installation Model RSM

Resistance thermometers for process technology

Operating Instructions Proline Promag 10 HART

Indumax CLS50/CLS50D. Technical Information

Conductivity measurement SmarTec S CLD 132

Coriolis Massflowmeter

JUMO flowtrans MAG S01

Measuring and Controlling Unit Multronic OC

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters 4/11

UFM 800 W, C Ultrasonic flowmeter for water and wastewater

Level Limit Switch nivotester FTL 370, FTL 372

Proline Promass 40E. Technical Information

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display

OPTIFLUX 2000 Technical Datasheet

SITRANS F M MAGFLO Electromagnetic Flowmeters Explore the Siemens Solution. sitrans f

Temperature Transmitter itemp RTD DIN rail TMT 127

4/11. Overview. Easier service Transmitter replacement requires no programming. SENSORPROM automatically updates all settings after initialization.

Transcription:

Technical Information TI 07D/06/en No. 50063743 Electromagnetic Flow Measuring System promag 33 Flexible System Wide choice of materials for process connections and measuring tube linings, compatible to the fluid Transmitter housing and display can be rotated to fit the orientation Operational Security ISO 9001 manufacturer High electromagnetic compatibility (EMC) High operating integrity through self-monitoring with alarm function Data protection with EEPROM on power failure (without batteries) Empty Pipe Detection (EPD) Measure Precisely Measured error: ± 0.5% or ± 0.% 00:1 operable flow range Excellent repeatability Install Anywhere Robust, shock-resistant aluminium housing, resistant to acids and caustics IP 67 protection for compact and remote versions (optional IP 68 sensor) Wide size range DN...00 ( 1 / 1...78") Flanged version with ISO meter lengths Hygienic sensor for food and pharmaceutical applications Ex versions for use in Ex Zones 1 and Easy to Operate Illuminated, double-spaced display Touch control: Operation from outside without opening the housing E+H operating matrix menudriven operation for all instrument parameters Interfaces: HART, PROFIBUS-PA, PROFIBUS-DP, Rackbus RS 485 Endress +Hauser Nothing beats know-how

Measuring System Fields of Application With the Promag 33 flowmeter most liquids can be measured provided they have a minimum conductivity of 5 µs/cm, e.g. acids, alkalis, pastes, pulps, drinking water, wastewater, sewage sludge, milk, beer, wine, mineral water, yoghurt, molasses, etc. A minimum conductivity of µs/cm is required for measuring demineralised water. Ex Versions Promag 33 is available in a number of Ex versions for use in Ex Zone 1 and. More information is given in the appropriate Ex documentation. Your E+H representative will be pleased to help you. Sensor Transmitter Promag A DN... Promag 33 Promag H DN...0 Compact version Remote version (with wall mounting) Promag F DN 15...300 Promag F DN 350...00 Electronics versions (communication): HART PROFIBUS-PA PROFIBUS-DP Rackbus RS 485 EEx i ti07y0 Measuring System The measuring system consists of: Promag 33 transmitter Promag A, H or F sensor The Promag 33 measuring system is mechanically and electronically designed for maximum flexibility with the transmitters and sensors being combined in any variation. The wide range of materials and process connections (fittings; flanges DIN, ANSI, JIS; Tri-Clamp, etc.) ensure that the measuring point can adjust to both plant and process conditions.

Function Measuring Principle According to Faraday's Law of Magnetic Induction, a voltage is induced into a conductor which moves in a magnetic field. With the electromagnetic measuring principle, the flowing fluid is the moving conductor. The induced voltage is proportionally related to the flow velocity and is fed to the measuring amplifier by a pair of electrodes. Using the pipe cross-sectional area, the flow volume is calculated. The DC magnetic field is generated by a switched direct current of alternating polarity. Together with the patented Integrated Autozero Circuit, this guarantees a stable zero point, and makes the measurement fluid-independent and insensitive to entrained solid particles. Every meter is factory calibrated with the most modern calibration rigs, traceable to national standards. Function of the Promag 33 The Promag transmitter converts the measured values coming from the sensor into standardised output signals. The following outputs are available for these signals: Current output Pulse / Frequency output Alarm output (Relay 1) Status output (Relay ) Promag 33 also has the following features: Relay 1 and are freely configurable Auxiliary input (positive zero return, totalizer reset, batching, dual range mode) Empty Pipe Detection (EPD) detects and indicates partially filled or empty measuring tubes. The special electrode cleaning circuitry (EEC) ensures accurate flow measurement even with conductive build-up in the measuring tube (e.g. magnetite). U e = B L v Q = v A U e = induced voltage B = magnetic induction (magnetic field) L = distance between measuring electrodes v = flow velocity Q = volume flow A = pipe cross-section ti07y01 3

Operation Display and Operation The Promag 33 measuring system is equipped with an illuminated, doublespaced LC display. This ensures that all important variables can be read off and controlled directly at the measuring point: Technical units Current output functions Totalizer functions Pulse and frequency output functions Relay functions Limit values Batching functions with integral preset counter Display parameters Creep suppression Empty pipe detection (EPD) Single and bidirectional measurement Auxiliary input Three operating keys are used for selecting and setting all functions of the instrument. The E+H operating matrix allows quick and easy access to all individual functions. 1 languages are selectable for the display text. A help function (diagnosis function) is available during programming. Infrared transmitting diode LC display: illuminated, double-spaced ENDRESS+HAUSER PROMAG >3s E - + Function symbols (from left to right) Access to the operating matrix Returning to HOME position Diagnosis function Infrared receiving diode 3 optical keypads ( Touch Control ): Access / leave operating matrix Select functions Set / store parameters ti07y03 Communication Depending on which module is fitted, Promag 33 has different interfaces for communication ability with higher level systems: HART protocol (SMART technology) is possible on the current output. Direct communication to a personal computer and the E+H Rackbus world is possible via the RS 485 interface. The PROFIBUS-PA version provides an indirect connection to process control systems via segment couplers. Promag 33 is also available as a PROFIBUS-DP version for connecting to a PROFIBUS-DP network. This communication feature enables operation and configuration of instruments which have no local display. 4

Diameter Selection As a rule, the pipe diameter determines the sensor nominal diameter. A necessary increase in velocity can be achieved through a reduction of the sensor diameter (see page 8). The higher installation expense is normally balanced by the lower sensor cost. The flow velocity (v) is also to be determined by the fluid's physical properties: v < m/s: with abrasive fluids, e.g. potter's clay, lime milk, ore slurry v > m/s: with fluids causing build up, e.g. wastewater slurry etc. The table below summarizes the minimum and maximum full scale values for the current output (incl. factory settings). DN Full scale values [m 3 /h] [mm] [inch] Minimum full scale at v = 0.3 m/s Factory setting at v ~.5 m/s Maximum full scale at v = m/s 4 8 15 3 50 65 80 1 / 1 " 5/ 3 " 5 / 16 " 1 / " 1" 1 1 / 4 " 1 1 / " " 1 / " 3" 0.0034 0.0136 0.0543 0.1908 0.5301 0.8685 1.357.11 3.584 5.49 0.083 0.1131 0.454 1.590 4.418 7.38 11.31 17.67 9.87 45.4 0.1131 0.454 1.8 6.36 17.67 8.95 45.4 70.69 119.5 181.0 0 1 4" 5" 6" 8.48 13. 19.09 70.69 1.5 159.0 8.7 441.8 636. 0 0 8" " 33.93 53.01 8.7 441.8 1130 1767 300 350 1" 14" 76.34 3.9 636. 865.9 45 3464 0 450 16" 18" 135.7 171.8 1131 1431 454 576 500 600 700 750 800 900 " 4" 8" 30" 3" 36" 1.1 305.4 415.6 477.1 54.9 687.1 1767 45 3464 3976 454 576 7069 179 13854 15904 18096 90 00 50 10 1350 0 1600 1700 1800 " 4" 48" 54" 56" 60" 64" 66" 7" 848. 935. 1 1546 1663 1909 17 451 748 7069 7793 179 188 13854 15904 18096 48 90 874 3117 715 51530 55418 63617 738 81713 91609 00 78" 3393 874 113097 5

Mounting In order to measure correctly and to prevent damage, please observe the following installation instructions. Mounting Position Vertical mounting: This is the recommended position with the flow upwards. Entrained solid particles sink and fatty components in the stationary fluid rise away from the measuring electrodes. This is the optimal position in empty pipe system and when using Empty Pipe Detection. ti07y04 Horizontal mounting: The axis of the electrodes must be horizontal, thus preventing brief insulation of the electrodes by entrained air bubbles. Measuring electrodes Electrode axis Electrode axis: The plane in which the electrode axis lies with regard to the transmitter is identical for the Promag A, H and F sensors. (Example Promag F) ti07y05 5 x DN x DN Inlet and Outlet Sections The sensor should be mounted away from fittings such as valves, T-pieces, elbows, etc. Inlet section: Outlet section: 5xDN xdn The inlet and outlet sections must be observed in order to maintain accuracy. ti07y06 Vibration The piping before and after the sensor should be securely fastened if there is excessive vibration. Information on shock and vibration resistance is found on page. Excessive vibration necessitates separate mounting of the sensor and transmitter. >m Mechanical support of the sensor is recommended for free runs of piping over m long. ti07y07 6

Mounting Location Correct measurement is only possible when the pipe is full. The following locations should therefore be avoided: No installation at the highest point (air accumulation). No installation immediately before an open pipe outlet in a downward line. alternatively The alternative installation, however, permits a correct measurement. h x DN ti07y08 5 x DN x DN ti07y09 Partly Filled Pipes For inclines a mounting similar to a drain should be adopted. Added security is offered by Empty Pipe Detection (EPD) in order to detect empty or partly filled pipes. Note! Danger of solids accumulation! Do not mount the sensor at the lowest point of the drain. A cleaning valve should also be installed. Venting valve Downward Pipe With the installation suggested opposite, partial vacuum is avoided even with a downward pipe > 5 m long (siphon, vent valve downstream of the sensor). >5m ti07y Installation of Pumps Do not mount the sensors on the suction side of pumps. This prevents low pressure and prevents possible damage to the lining of the measuring tube. Pulse dampers should be installed when using reciprocal, diaphragm or peristaltic pumps. ti07y11 7

Mounting Adapters The sensor can also be mounted in a pipe with a larger nominal diameter when suitable adapters (reducers and expanders) to DIN 8545 are fitted. The resultant increase in the rate of flow increases the accuracy of measurement with slowly moving fluids. The adjacent nomogram can be used to determine the pressure loss caused: 1. Determine the ratio of the diameter d/d.. From the nomogram read off the pressure loss at the flow velocity and d/d ratio. Pressure loss [mbar] Note! The nomogram applies to fluids with a viscosity similar to that of water. Diameter ratio d/d ti07y1 Remote Version Two different versions are available for the remote version: L max FS version The permissible cable length greater than meters is governed by the fluid conductivity (see Figure). Permissible cable length of max. meters if the instrument is equipped with an Empty Pipe Detection (EPD) electrode. The FS cable is recommended only for distances smaller than m. Remote version has to be mounted when: access is difficult space is restricted extreme process and ambient temperatures prevail (see page 4) there is severe vibration (see page ) Conductivity [µs/cm] 0 0 5 Permissible range FS FL 0 0 [m] Cable length L max ti07y13 FL version All fluids with a minimum conductivity of 5 µs/cm (demineralised water µs/cm) can be measured independent of the cable length. Empty Pipe Detection (EPD) is not available with this version. Please also note the following: Fasten the cable gland or lay it in a conduit. When the fluid conductivity is low, cable movements can cause serious changes in capacitance and thereby falsify the measuring signal. Do not run the cable in the vicinity of electrical machines or switching elements. Ensure potential equalisation between the transmitter and the sensor. 8

Electrical Connection Transmitter Fuse Power supply...55 V AC / 16...6 V DC:.5 A slow-blow / 0 V; 5. x mm Power supply 85...60 V AC: 1 A slow-blow / 0 V; 5. x mm 1 1 3 4 6 7 3 8 Supply cable Ground terminal for protective conductor Ground terminal for signal cable shield Signal cable The input and outputs are galvanically separated from the power supply and from each other. ti07y14 HART version 3 Ground connection (protective earth) 1 L1 L+ for AC power supply N L (+) 1 () (+) 3 () 4 (+) () 6 (+) 7 () Pulse / Frequency output Alarm output (Relay 1) Status output (Relay ) for DC power supply active/passive, f max = khz active: 4 V DC, ma (max. 0 ma/ ms) passive: 30 V DC, 0 ma can be configured max. 60 V AC / 0.5 A AC; max. 30 V DC / 0.1 A DC can be configured max. 60 V AC / 0.5 A AC; max. 30 V DC / 0.1 A DC Current output active, 0/4... ma, R L < 700 Ω (with HART: R L 0 Ω) 8 Ground connection (screening of signal cable) PROFIBUS-PA version 3 Ground connection (protective earth) 1 L1 L+ for AC power supply N L / 1 not used (+) Current output 3 () 4 / not used 6 (+) 7 () for DC power supply active, 0/4... ma R L < 350 Ω PROFIBUS-PA EN 50170 Volume, IEC 1158-8 Ground connection (screening of signal cable) PROFIBUS-DP version 3 Ground connection (protective earth) 1 L1 L+ for AC power supply for DC power supply N L not used 6 (+) Data B PROFIBUS-DP (RS 485 interface) 7 () Data A 8 Ground connection (screening of signal cable) 9

Electrical Connection Transmitter Fuse Power supply...55 V AC / 16...6 V DC:.5 A slow-blow / 0 V; 5. x mm Power supply 85...60 V AC: 1 A slow-blow / 0 V; 5. x mm 1 1 3 4 6 7 3 8 Supply cable Ground terminal for protective conductor Ground terminal for signal cable shield Signal cable The input and outputs are galvanically separated from the power supply and from each other. ti07y14 Rackbus RS 485 version 3 Ground connection (protective earth) 1 L1 L+ for AC power supply N L for DC power supply (+) 1 /) RS 485 interface or Auxiliary input A + / 3...30 V DC B / + (+) 3 () 4 (+) () 6 (+) 7 () Alarm output (Relay 1) Status output (Relay ) Current output or Pulse/frequency output can be configured max. 60 V AC / 0.5 A AC; max. 30 V DC / 0.1 A DC can be configured max. 60 V AC / 0.5 A AC; max. 30 V DC / 0.1 A DC active, 0/4... ma, R L < 700 Ω active/passive, f max = khz active: 4 V DC, ma (max. 0 ma/ ms) passive: 30 V DC, 0 ma 8 Ground connection (screening of signal cable) EEx i version 3 Ground connection PE (protective earth) 1 L1 L+ for AC power supply N L for DC power supply / 1 not used (+) 3 () Current output active, 0/4... ma, R L < 350 Ω (with HART: R L 0 Ω) 4 / not used 6 (+) 7 () Pulse/frequency output passive, f max = khz Can be used as NAMUR contact acc. to DIN 1934 8 Ground connection (screening of signal cable) Terminal compartment with: a special terminal block for intrinsically safe outputs and an IP cover for power supply terminals.

Electrical Connection Remote Version FS Version Promag 33 A Promag 33 H / F Transmitter Transmitter EPD EPD S1 E1 E S GND E S Coils S1 E1 E S GND E S Coils 6 5 7 8 4 37 36 3 4 41 6 5 7 8 4 37 36 3 4 41 brown white green yellow 1 brown white green yellow 1 4 6 5 7 8 37 36 4 41 6 5 7 8 4 37 36 3 4 41 GND S1 E1 E S E S Coils S1 E1 E S GND E S Coils EPD EPD Sensor Sensor FL Version Promag 33 A Promag 33 H / F Transmitter Transmitter E1 E GND V+ V- Coils E1 E GND V+ V- Coils 6 5 7 8 4 37 36 3 4 41 6 5 7 8 4 37 36 3 4 41 grey white brown yellow green 1 white grey green brown yellow 1 7 5 3 4 4 41 5 7 4 37 36 3 4 41 E E1 V+ V- GND Coils E1 EGND V+ V- Coils out-out+ Sensor Sensor ti07e01 11

Cable Specifications Remote Version FS Coil cable: x 0.75 mm PVC cable with common screen * Conductor resistance 37 Ω/km Capacitance: core/core, screen grounded 1 pf/m Permanent operating temperature:...+70 C Signal cable: 3 x 0.38 mm PVC cable with common screen * and separately screened cores With EPD (Empty Pipe Detection) 4 x 0.38 mm PVC cable Conductor resistance 50 Ω/km Capacitance: core/screen 4 pf/m Permanent operating temperature:...+70 C * braided copper screen: ~ 7mm Remote Version FL Coil cable: x 0.75 mm PVC cable with common screen * Conductor resistance 37 Ω/km Capacitance: core/core, screen grounded 1 pf/m Permanent operating temperature:...+70 C Signal cable: 5 x 0.5 mm PVC cable with common screen * Conductor resistance 37 Ω/km Capacitance: core/core, screen grounded 1 pf/m Permanent operating temperature:...+70 C * braided copper screen: coil cable ~ 7 mm; signal cable ~9mm Operation in Areas with Severe Electrical Interference The Promag 33 measuring system fulfils all general safety requirements according to EN 6 and electromagnetic compatibility (EMC) according to EN 50081 Part 1 and / EN 5008 Part 1 and when installed in accordance with the NAMUR recommendations. Note! To comply with the certificate of conformity, the signal and coil cables between the sensor and transmitter of the remote version must always be screened and grounded at both ends. Grounding is made using the ground terminals especially for this purpose on the inside of the connection housings. Keep stripped and twisted cable shield section to the ground terminal as short as possible. The cable must be resistant to an ambient temperature of max. +80 C if the Promag H sensor is operated at a process temperature of + C. 1

Potential Equalisation The sensor and the fluid must have roughly the same electrical potential to ensure that measurement is accurate and no galvanic corrosion takes place at the electrode. Normally the reference electrode in the sensor or the metal pipe ensures that the potentials are equalised. Reference electrodes: Promag A: Always with reference electrode Promag F: Optional, depending on material Promag H: No reference electrode, as there is always a metallic connection to the fluid. 1 Empty pipe detection electrode Measuring electrodes 3 Reference electrode(s) 3 1 If the reference electrode is correctly grounded and the fluid flows through metallic, non-lined and grounded piping, then it is sufficient to connect the grounding terminal of the Promag 33 transmitter housing to the potential equalisation line in order to prevent corrosion. The connection with the remote-mounted version is made at the ground terminal of the connection housing. Caution! Danger of permanent damage to the instrument! If the fluid cannot be grounded for operational reasons, ground disks are to be used. ti07y16 Isolating transformer Power supply 6 mm² Cu ti07y17 Potential Equalisation for Lined Pipes with Cathodic Protection When the fluid cannot be grounded for operational reasons, the measuring unit must be installed that it is potential-free. Ensure that components of the piping are connected to one another (copper wire, 6 mm ). All national regulations regarding potential free installation are to be observed (e.g. VDE 00). Ensure that the mounting material used does not result in a conductive bond with the measuring unit and that the material can withstand the tightening torque used. 13

Potential Equalisation Plastic or Lined Piping Ground disks must always be used with non-conductive piping materials if compensation currents flow through the fluid. They can irreparably damage the reference electrode within a short time due to electrochemical corrosion. 6 mm² Cu Such conditions occur especially if: the piping is insulated with electrically non-conductive materials and the piping is made of fibreglass or PVC through which flow highly concentrated acids and alkalis. Ground disks: appr. 3 mm thick ti07y18 Caution! Danger from damage due to electrochemical corrosion! Note the corrosion resistance of the ground disks. Note the electrochemical potential series in cases where the ground disks and the measuring electrodes are made of different material. Equalising Currents in Ungrounded Metal Pipes / Grounding in an Area with Severe Interference The fluid may be grounded. In order to make the most of the electromagnetic compatibility (EMC) of the Promag 33, it is advisable to provide two flange-toflange links and to connect them jointly with the transmitter housing to ground potential. 6 mm² Cu ti07y44 ti07y19 Wall mounting kit Promag A Wall mounting kit Promag A sensor A = 5 mm B = 5 mm C = 115 mm 14

Dimensions Promag 33 A Compact version ti07y Remote version FS version Weight: Compact version Promag 33 transmitter Promag A sensor * with blind version 5 kg (without process connections) 3 kg (5 kg for wall mounted version) kg FL version ti07y1 A Can be ordered separately as mounting set: Internal thread, external thread, PVC adhesive coupling, hose connection, welded nipples DN... 1" threaded stub (ISO 8) B Flange joints (mounted when delivered) Process connections Promag A (Dimensions: see page 16) Tri-Clamp (mounted when delivered) A B Mounting set: coupling nut on a 1" threaded stub Screw-in process connections (instead of threaded stub) DN... ti07y3 15

Process Connections Promag A Internal thread standard thread: ISO 8/DIN 999 DN L L1 Thread...15...15 45 45 18 18 1 / " / " NPT 1" 1" NPT External thread standard thread: ISO 8/DIN 999 DN L L1 di Thread...15...15 35 4 50 60 13..0 16.8.0 16.1 16.1.0.0 1 / " / " NPT 1" 1" NPT PVC adhesive coupling DN L D Pipe connection...15...15 19 66 69 69.0 1.5.0 3.0 33.5 / " 3.5 1" Hose connection DN L D di LW...15...15...15 30 30 30 14.5 17.5 1.0 8.9 1.6 16.1 13 16 19 LW = Internal diameter hose Welded nipple DN...15 DN L D s Pipe connection..15 1.3.6 1 / "..15 1.3.6 18 1 Welded nipple DN DN L D di Pipe connection 30 30 33.7 33.7.4 6.0 6.0.1 1" 8 1.4 1.6 / 1" Tri-Clamp Stainless steel 1.44/316L DN L D di Pipe connection..8 15...8 15 4 4 4 4 4.0.0 50.4 50.4 50.4 9.5 16.0.1.1.1 1 / " / 4 " 1" 1" 1" Flange to DIN 01, PN Flange Stainless steel 1.44/316L with joint dimensions to DIN 01/ANSI B16.5/JIS B DN...15: with DN 15 or 1 / " flanges DN : with DN or 1" flanges Flange PVDF with joint dimensions to DIN 01/ANSI B16.5/JIS B DN...15: with DN 15 or 1 / " flanges DN : with DN or 1" flanges Length: x L + 143 mm x L + 95 mm (for flanged or Tri-Clamp version) All dimensions in [mm] y-01... DN L D di LK...8 15 51.8 51.8 51.8 95 95 115 17.3 17.3 8.5 65 65 85 Flange to ANSI B16.5 Class Class 300 DN L D LK di L D LK...8 15 61.6 61.6 67.4 88.9 88.9 8.0 60.5 60.5 79. 15.8 15.8 6.6 61.6 61.6 73.8 95. 95. 13.9 Flange to DIN 01/ANSI B16.5/JIS B PN 16/Class /K DN L L1 D d di DIN LK ANSI LK...8 5.7 6 95 34 16. 65 60.5 15 5.7 6 95 34 16. 65 60.5 5.7 7 115 50 7. 85 79. Face-to-face length to DVGW (0 mm) 66.5 66.5 88.9 Flange to JIS B DN L D di LK...8 15 6.5 6.5 6.5 95 95 115 15 16 70 70 90 Face-to-face length to DVGW (0 mm) JIS LK 70 70 90 16

Dimensions Promag 33 H Compact version ti07y ti07y4 Remote version * with blind version DN DI 1) PN L A B B1 C K H M Weight ) [mm] [inch] [mm] DIN 6.0 16 1".6 16 1 1 / " 35.3 16 50 " 48.1 16 65 1 / " 59.9 16 80 3" 7.6 16 0 4" 97.5 16 1) Internal diameter of tube DIN [bar] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg] 1 1 1 1 1 0 0 318 318 318 343 343 393 393 4.0 4.0 4.0 66.5 66.5 91.5 91.5 158.5 158.5 158.5 171.0 171.0 196.0 196.0 64.0 64.0 64.0 76.5 76.5 1.5 1.5 18 18 18 153 153 3 3.5.5.5 47.5 47.5 97.5 97.5 M 6x4 M 6x4 M 6x4 M 8x4 M 8x4 M 1x4 M 1x4 6.0 6.0 6.5 9.0 9.0 19.0 18.5 Weight: Compact version ) Promag 33 transmitter Sensor connection housing see table above 3 kg (5 kg for wall mounted version) approx. 1 kg Process connections Promag H Tri-Clamp ISO 853 Welded nipple ISO 85 Process connections Promag H (Dimensions: see page 18) Flat gasket Silicone / EPDM DN 11851 SMS ti07y6 17

Process Connections Promag H Welded nipple y7-01...06 DN D G di 1) L L1 LK DIN DIN 50 50 DIN 65 65 DIN 80 80 DIN 0 0 DIN 75 79 9 9 5 5 11 11 147 147 168 168 7 31 43 55 55 66 7 79 87 4 6.6 6.0 35.3 38.0 48.1 50.0 59.9 66.0 7.6 81.0 97.5 0.0 4 4 4 4 4 4 4 4 4 4 4 4 19 19 19 19 19 19 1 1 4 4 4 4 56.0 60.0 71.0 71.0 83.5 83.5 0.0 0.0 11.0 11.0 141.5 141.5 DN di 1) G D L LK DIN 11851 50 65 80 0 6 38 50 66 81 0 5 x 1 / 6 " 65 x 1 / 6 " 78 x 1 / 6 " 95 x 1 / 6 " 1 x 1 / 4 " 130 x 1 / 4 " 79 9 5 11 147 168 68 7 74 78 83 9 60.0 71.0 83.5 0.0 11.0 141.5 DN ANSI di 1) G D L LK Tri-Clamp 50 65 80 0 1" 1 1 / " " 3" 4".1 34.8 47.5 60. 7.9 97.4 50.4 50.4 63.9 77.4 90.9 118.9 75 9 5 11 147 168 68.6 68.6 68.6 68.6 68.6 68.6 56.0 71.0 83.5 0.0 11.0 141.5 DN di 1) G D L LK SMS 1145 50 65 80 0.5 35.5 48.5 60.5 7.0 97.6 x 1 / 6 " 60 x 1 / 6 " 70 x 1 / 6 " 85 x 1 / 6 " 98 x 1 / 6 " 13 x 1 / 6 " 75 9 5 11 147 168 60 63 65 70 75 70 56.0 71.0 83.5 0.0 11.0 141.5 DN di 1) G D L LK ISO 85 50 65 80 0.6 35.6 48.6 60.3 7.9 97.6 50.5 50.5 64.0 77.5 91.0 119.0 75 9 5 11 147 168 68.5 68.5 68.5 68.5 68.5 68.5 56.0 71.0 83.5 0.0 11.0 141.5 ISO 853 DN di 1) G D L LK 50 65 80 0.6 35.6 48.6 60.3 7.9 97.6 37.1 50.6 64.1 77.6 91.1 118.1 75 9 5 11 147 168 61.5 61.5 61.5 61.5 61.5 61.5 56.0 71.0 83.5 0.0 11.0 141.5 Length: DN... 65 = x L + 136 mm DN 80...0 = x L + 196 mm 1) Please note the internal diameter (di, DI) when cleaning the piping with a scraper! 18

Dimensions Promag 33 F DN 15...300 Compact version ti07y8 Remote version * with blind version ti07y9 DN PN L 1) A B C K E F H B1 Weight ) [mm] [inch] DIN ANSI Class JIS [mm] [mm] [mm] [mm] [mm] [mm] DIN [mm] ANSI [mm] [mm] [mm] [kg] 15 3 50 65 80 0 1 0 0 300 1 / " 1" 1 1 / " " 3" 4" 6" 8" " 1" 16 16 16 16 16 K K K K K K K K K K K K K 0 0 0 0 0 0 0 0 0 300 350 450 500 3.5 3.5 3.5 3.5 3.5 390.5 390.5 390.5 471.5 471.5 56.5 576.5 66.5 6.5 6.5 6.5 6.5 6.5 81.5 81.5 81.5 31.5 31.5 346.5 371.5 396.5 84 84 84 84 84 9 9 9 180 5 30 1 1 1 1 1 180 180 180 60 60 34 0 460 94 94 94 94 94 94 94 94 1 1 156 156 166 14 16 18 18 18 4 4 6 8 8 11. 14. 17.5 19.1 3.9 3.9.4 8.4 30. 31.8 86 86 86 86 86 336 336 336 417 417 47 5 57 7 7 7 67 67 9 317 34 6.5 7.3 8.0 9.4.6 1.0 14.0 16.0 1.5.5 35.3 48.5 57.5 1) The length is always identical independently of the chosen pressure rating. Weight: Compact version ) Promag 33 transmitter Sensor connection housing see table above 3 kg (5 kg for wall mounted version) approx. 1 kg 19

Dimensions Promag 33 F DN 350...00 Compact version ti07y30 Remote version * with blind version ti07y31 DN PN L 1) A B C K E F H B1 Weight ) [mm] [inch] DIN [bar] ANSI [Class] AWWA [Class] [mm] [mm] [mm] [mm] [mm] [mm] DIN [mm] ANSI [mm] AWWA [mm] [mm] [mm] [kg] 350 0 450 500 600 700 750 800 900 00 50 10 1350 0 1600 1650 1800 00 14" 16" 18" " 4" 8" 30" 3" 36" " 4" 48" 54" 60" 66" 7" 78" 6 6 6 6 6 D D D D D D D D D D D D 550 600 650 650 780 9 975 1170 1300 1365 1560 1755 18 1950 80 145 3 600 738 790 8 891 995 1198 1198 141 1394 1546 1598 1796 1998 148 196 86 360 50 650 456.0 48.0 507.0 53.5 584.5 686.0 686.0 707.5 784.0 860.0 886.0 985.0 86.0 1161.0 1185.0 130.0 167.0 136.0 141.0 8.0 308.0 333.0 358.5 4.5 51.0 51.0 533.5 6.0 686.0 71.0 811.0 91.0 987.0 11.0 56.0 93.0 1188.0 138.0 564 616 666 717 81 4 4 67 1 137 144 16 184 1974 11 186 376 476 76 76 9 9 589 66 647 785 86 91 99 1 1 139 148 148 163 173 6 6 8 8 30 3 34 34 8 3 34 36 38 34.9 36.5 39.7 4.9 47.6 33.3 34.9 38.1 41.3 41.3 44.5 44.5 54.0 57. 63.5 66.7 69.9 683.5 735.5 785.5 836.5 9.5 1143.5 1143.5 1186.5 1339.5 1491.5 1543.5 1741.5 1943.5 93.5 141.5 31.5 305.5 495.5 95.5 1.5 47.5 45.5 478.0 530.0 631.5 631.5 653.0 79.5 805.5 831.5 930.5 31.5 16.5 1130.5 1175.5 11.5 1307.5 1357.5 1 130 170 30 350 450 450 600 7 50 10 1800 600 00 3700 3300 40 1) Thickness of the flange face includes sealing strip. The length is always identical independently of the chosen pressure rating. Weight: Compact version ) Promag 33 transmitter Sensor connection housing see table above 3 kg (5 kg for wall mounted version) approx. 1 kg

Material Load Curves (p-t-diagrams) Promag A Promag H DIN 413 and 05 Flange material: Steel 1.44/1.4435, PVDF, PVC [bar] 35 30 15 5 PN 1.44/14435 PN 16 PVC PN 16 PVDF Welded nipple material: [bar] 15 5 0 PN 16 1.4435 Steel 1.44/316L -60 - - 0 60 80 0 1 1 160 [ C] 0-60 - - 0 60 80 0 1 1 160 [ C] Promag F DIN 413 and 05 Flange material: Steel 37. [bar] 35 PN ANSI B16.5 Flange material: [bar] Steel A5 [psi] 30 60 870 PN 50 Class 300 7 580 15 PN 16 30 435 5 PN PN 6 Class 90 145 0 0 0-60 - - 0 60 80 0 1 1 160 [ C] -60 - - 0 60 80 0 1 1 160 [ C] DIN 413 and 05 Flange material: Stainless steel 1.4571 [bar] 35 PN AWWA C 7, Class D Flange material: Steel A5 30 [bar] 11 [psi] 159.5 PN 9 145 130.5 15 PN 16 8 116 PN 7 1.5 5 PN 6 9 0 0 0-60 - - 0 60 80 0 1 1 160 [ C] -60 - - 0 60 80 0 1 1 160 [ C] ANSI B16.5 Flange material: Steel 316L JIS B Flange material: SC / SUS 316L [bar] [psi] [bar] 60 870 30 50 7 Class 300 580 K 30 435 90 K Class 0-60 - - 0 60 80 0 1 1 160 145 0 [ C] 0-60 - - 0 60 80 0 1 1 160 [ C] ti07y35...43 1

Technical Data Application Instrument name Flow measuring system Promag 33 Instrument function Flow measurement of liquids in closed piping. Applications in measurement, control and regulation processes, for e.g. batching and dosing (> s), etc. Function and system design Measuring principle Electromagnetic flow measurement according to Faraday s law (generation of a voltage by induction in a magnetic field). Measuring system Instrument family Promag 33 consisting of: Transmitter: Promag 33 (with electronics versions HART, PROFIBUS-PA, PROFIBUS-DP, Rackbus RS 485 or EEx i) Sensor: Promag A (DN, 4, 8, 15, ) Promag H (DN,, 50, 65, 80, 0) Promag F (DN 15...00) Two versions are available: Compact version Remote version (FS or FL version) Input variables Measuring variable Measuring range Flow velocity (proportional to induced voltage, measured by two electrodes in the measuring tube) Measuring range of electronics within v = 0...1.5 m/s The full scale value for the current output can be selected within the following limits (see also page 5): Minimum full scale value at v = 0.3 m/s Maximum full scale value at v = m/s Operable flow range Over 00 : 1 When the flow is pulsating, the amplifier is not overloaded above its set full scale value even with peak velocities of 1.5 m/s. Flow is measured between 0.01...> m/s at the stated accuracy. Auxiliary input The auxiliary input is only available with a RS 485 communications module. U = 3...30 V DC, R i = 1.8 kω, galvanically isolated Configurable for: Positive zero return, totalizer reset, starting a batch cycle or dual range mode. Output variables Output signal Current output: active, 0/4... ma, galvanically isolated, R L (see page 3), time constant selectable (0.01...0 s), full scale value freely selectable, temperature coefficient: typical 0.005% o.r./ C; resolution: µa Pulse / frequency output: active/passive selectable, galvanically isolated active: 4 V DC, ma (max. 0 ma during ms), R L > 0 Ω passive: Open Collector, 30 V DC, 0 ma Frequency output: full scale frequency...000 Hz, pulse/pause ratio 1:1, pulse width max. s Pulse output: pulse value and pulse polarity selectable, pulse width adjustable (0.05... s) above a frequency of 1 / ( x pulse width) the pulse/pause ratio is 1:1 (continued on next page)

Output variables (continued) Output signal (continued) Alarm output (Relay 1): Either NC or NO via a jumper available (factory setting: NO contact) max. 60 V AC / 30 V DC; max. 0.5 A AC / 0.1 A DC, galvanically isolated. Configurable for: error message (failure), empty pipe detection (EPD), failure + EPD, full scale switching, batch precontact, direction of flow, limit value 1 and overflow (v > 1.5 m/s) Status output (Relay ): Either NC or NO via a jumper available (factory setting: NC contact) max. 60 V AC / 30 V DC; max. 0.5 A AC / 0.1 A DC, galvanically isolated. Configurable for: empty pipe detection (EPD), full scale switching, batch contact, direction of flow, limit value and overflow (v > 1.5 m/s) Signal on alarm Load (current output) Creep suppression Current output failsafe mode selectable Pulse/frequency output failsafe mode selectable Relay 1 output de-energised on failure or power supply failure Relay output de-energised on power supply failure R L < 700 Ω (HART current output and Rackbus RS 485 version) R L < 350 Ω (PROFIBUS-PA and EEx i version) R L 0 Ω (with HART) Switching points selectable Max. creepage depending on the nominal diameter at v = 1 m/s Hysteresis: 50% of set creepage Accuracy Reference conditions According to DIN 190 and VDI/VDE 641: Fluid temperature +8 C ± K Ambient temperature + C ± K Warm up period 30 minutes Mounting: Inlet section > x DN Outlet section > 5 x DN Transmitter and sensor are grounded. The sensor is build-in centered into the piping. Measured error Pulse output: ± 0.5% o.r. ± 0.01% o.f.s. (full scale value = m/s) Current output: additionally ± 5 µa (typical) o.r. = of reading o.f.s. = of max. full scale value 0.5% Measured error [% o.r.] 0.% (Option),5,0 1,5 1,0 0,5 0 0 4 6 8 Fluid velocity [m/s] ti07y3 Option: Promag 33 A and F: ± 0.% o.r. ± 0.005% of Q k Q k = desired reference flow quantity for calibration (v =... m/s). Q k has to be noted for ordering. Deviations in power supply voltage have no influence on the specified ranges. Repeatability ± 0.1% o.r. ± 0.005% o.f.s. o.r. = of reading o.f.s. = of max. full scale value (see table on page 5) 3

Technical Data Operating conditions Installation conditions Installation instructions Orientation: vertical or horizontal Restrictions and other recommendations see page 6 ff. Inlet and outlet sections Inlet section: 5 x DN Outlet section: x DN Connection cable length Remote FS version: 0... m min. conductivity 5 µs/cm (for liquids in general) 0... m min. conductivity µs/cm (for demineralised water)...0 m min. conductivity = f (L max ) Remote FL version: 0...0 m min. conductivity 5 µs/cm (for liquids in general) 0...0 m min. conductivity µs/cm (for demineralised water) Instrument equipped with empty pipe detection (EPD): max. cable length = m Conductivity [µs/cm] L max 0 Permissible range FS 0 ti07y33 5 FL 0 0 [m] Cable length L max Ambient conditions Ambient temperature...+60 C (Transmitter and sensor) An all-weather cover should be used to protect the housing from direct sunlight when mounting in the open. This is especially important in warmer climates and with high ambient temperatures. Due to the danger of the transmitter electronics overheating, the transmitter and sensor are to be mounted separately with high ambient and fluid temperatures (see Figure). Fluid temperature [ C] 1 1 0 80 60 0 - - Temperature range only for the remote version available. PTFE (Teflon) Soft rubber (EPDM) Hard rubber - - 0 60 80 Ambient temperature [ C] ti07y34 Storage temperature CIP cleanable...+50 C (preferably at + C) Promag A, H, F Yes (observe maximum temperature) 4

Operating conditions (continued) Ambient conditions SIP cleanable Promag A No Promag H Yes (observe maximum temperature) Promag F No Degree of protection (EN 6059) Shock and vibration resistance Electromagnetic compatibility (EMC) IP 67 (NEMA 4X) Option: IP 68 (NEMA 6P) for sensor A and F Accelleration up to g / h per day;...0 Hz According to EN 50081 Part 1 and (interference emission) / EN 5008 Part 1 and (interference immunity) as well as to NAMUR recommendations Process conditions Fluid temperature The fluid temperature range depends on the sensor lining: Promag A...+130 C PFA Promag H...+130 C PFA with EPDM gasket...+ C PFA with Silicone gasket Promag F...+130 C PTFE (Teflon), DN 15...600...+1 C Soft rubber (EPDM), DN...00 0...+ 80 C Hard rubber, DN 65...00 (see Fig. on page 4) Nominal pressure Promag A PN 16 for Tri-Clamp, PVC couplings PN for all other connections Promag H PN 16 Promag F DIN PN 6 (DN 10...00) PN (DN 0...00) PN 16 (DN 65...) PN (DN 15...50) PN (DIN 10...00, optional) PN 16/ (DN 0...00, optional) PN (DN 65..., optional) ANSI Class ( 1 /...4") Class 300 ( 1 /...6", optional) AWWA Class D (8...48") JIS K (DN 50...300) K (DN 15...) K (DN 50...300, optional) Material load curves (p-t-load diagrams) see page 1 Conductivity Minimum conductivity: 5 µs/cm for liquids in general µs/cm for demineralised water With the remote FS version the conductivity required also depends on the length of the cable see page 4 Connection cable length Pressure loss No pressure loss if sensor and piping have the same nominal diameter. Pressure loss specifications when using adapters e.g. reducers or expanders see page 8

Technical Data Mechanical construction Design / Dimensions Dimensions see pages 15 Weight See pages 15 Materials Transmitter housing: Powder-coated die-cast aluminium Sensor housing: Promag A 1.4435 incl. threaded stub Promag H 1.4301 Promag F DN 15...300: Powder-coated die-cast aluminium DN 350...00: Coated steel Process connections: Promag A DIN Stainless steel 1.44, PVDF ANSI 316L, PVDF JIS 316L, PVDF Threaded stub: 1.4435, PVC Promag H 1.44 / 316L Promag F DIN Stainless steel 1.4571, St. 37- ANSI A 5, 316L AWWA A 5, A 36 JIS SC, SUS 316L Electrodes: Promag A 1.4435; Platinum/Rhodium 80/; Titanium; Hastelloy C-; Tantalum Promag H 1.4435 Promag F 1.4435; Platinum/Rhodium 80/; Hastelloy C-; Tantalum Gasket material: Promag A Viton, Kalrez (optional), Silicone (aseptic version) Promag H EPDM, Silicone Promag F no gaskets (lining = 'gasket') Electrodes fitted Promag A Measuring, reference and empty pipe detection electrodes. As standard with: 1.4435, Hastelloy C-, Tantalum Option with: Platinum/Rhodium Promag H Promag F Measuring and empty pipe detection electrodes Measuring, reference and empty pipe detection electrodes. As standard with: 1.4435, Hastelloy C-, Tantalum Process connections Promag A: Internal and external thread, PVC adhesive coupling, hose connection, welded nipple, aseptic welded nipples for pipelines according to DIN 11850, Tri-Clamp, flange connection (DIN, ANSI, JIS). Promag H: Welded nipples for OD tube, SMS, JIS, ISO and DIN 11850 tubes, DIN 11851 thread, SMS thread, ISO 853 thread, Tri-Clamp, ISO 85 connection. Promag F: Flange connection (DIN, ANSI, JIS) Electrical connection Cable entries Wiring diagrams: see page 9 ff. Cable specifications: see page 1 Galvanic isolation: All circuits for inputs, outputs, power supply and sensors are galvanically isolated from one another. Power supply and signal cable (outputs): Cable glands PG 13.5 (5...15 mm) or threads for cable glands 1 / " NPT, M x 1.5 (8...15 mm), G 1 / " Coil current cable and signal cable (remote version) Promag A: Cable glands PG 11 (5...1 mm) or threads for cable glands 1 / " NPT, M x 1.5 (8...15 mm), G 1 / " Promag H: Cable glands PG 13.5 (5...15 mm) or threads for cable glands 1 / " NPT, M x 1.5 (8...15 mm), G 1 / " Promag F: Cable glands PG 13.5 (5...15 mm) or threads for cable glands 1 / " NPT, M x 1.5 (8...15 mm), G 1 / " 6

User interface Operation On-site operation with three optical keypads (E,, +) E+H operating matrix for all instrument functions Display Communication LC display: illuminated, double-spaced with 16 characters each Damping of flow display can be adjusted: 0...99 s SMART protocol (HART protocol via current output) PROFIBUS-PA / PROFIBUS-DP Rackbus RS 485 interface (Rackbus protocol) Power supply Supply voltage / Frequency Power consumption 85...60 V AC, 45...65 Hz... 55 V AC, 45...65 Hz 16... 6 V DC AC: <15 VA (incl. sensor) DC: <15 W (incl. sensor) Current at make (Promag 33 X / 4 V DC): max. 13.5 A (< 0 µs) max. 6 A (< 5 ms) Power supply failure Bridges minimum 1 power cycle ( ms) EEPROM saves measuring system data on power failure (no batteries required). DAT = replaceable data memory in which basic data of the sensor are stored: nominal diameter, SAPS (actual values), serial number, calibration factor, zero point, status EPD (yes/no), EPD calibration values. Certificates and approvals Ex approvals Sanitary version CE mark Information on Ex versions (e.g. ATEX/CENELEC, FM, CSA) can be supplied by your E+H sales center on request. All explosion protection data are given in separate documentation available on request. Sensor Promag A: 3A approval Sensor Promag H (hygienic version): 3A approval and EHEDG tested By attaching the CE mark, Endress+Hauser confirms that the Promag 33 measurement system has been successfully tested and fulfils all legal requirements of the relevant CE directives. Order information Accessories Supplementary documentation Post mounting set for transmitter (remote version): Order No. 50076905 Wall mounting kit for Promag A sensor: Order No. 50064550 System Information Promag (SI 0D/06/en) Operating Manual Promag 33 (BA 009D/06/en) Supplementary Ex documentation: ATEX/CENELEC, FM, CSA Other standards and guidelines EN 6059 EN 6 EN 50081 EN 5008 NAMUR Degree of protection by housing (IP code) Protection Measures for Electronic Equipment for Measurement, Control, Regulation and Laboratory Procedures Part 1 and (interference emission) Part 1 and (interference immunity) Association of Standards for Control and Regulation in the Chemical Industry 7

Subject to modification Endress+Hauser GmbH+Co. Instruments International P.O. Box D-79574 Weil am Rhein Germany Tel. (0761) 975-0 Tx 77396 Fax (0761) 975345 http://www.endress.com Endress +Hauser Nothing beats know-how TI 07D/06/en/04.99 CV 5.0