Circuit Breaker. By Shashidhar kasthala Assistant Professor Indian Naval Academy

Similar documents
FUNCTIONS OF CIRCUIT BREAKERS

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

SWITCHGEAR PROTECTION

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

CIRCUIT BREAKERS: Principles, Assessment and Switching Transients

Interrupting Phenomena of High-Voltage

Chapter (2) Prof. Dr. Sayed A. Ward Eng. Essam M. Shaalan Page 26

EE 6702 PROTECTION AND SWITCHGEAR UNIVERSITY QUESTIONS AND ANSWERS UNIT 4. Part - A

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

General information 1 / 17

Manufacturing Process - I Dr. D. K. Dwivedi Department of Mechanical and Industrial Engineering Indian Institute of Technology, Roorkee

Basic Principles and Operation of Transformer

Single Line Diagram of Substations

Vacuum Interrupters for Medium Voltage

ELECTRICAL EQUIPMENT. Inspection. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

International Journal of Advance Engineering and Research Development A SURVEY ON ELECTRIC ARC MODEL FOR HIGH VOLTAGE CIRCUIT BREAKER BASED ON MAT LAB

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

HIGH VOLTAGE CIRCUIT BREAKERS

Unit 2. Single Line Diagram of Substations

EE 1402 HIGH VOLTAGE ENGINEERING

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

Grounding System Theory and Practice

Evaluation of High-Voltage Circuit Breaker Performance with Modified Schavemaker Arc Model

Surge Protection and Grounding Issues

Standards for MV switchgear rated for arc flash protection

EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

IMPORTANT TWO MARKS AND SIXTEEN MARKS QUESTION AND ANSWER

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

A TRAINING REPORT ON UTTAR PRADESH POWER CORPORATION LIMITED 33/11 KV SUBSTATION INDIRANAGAR SECTOR-25, LUCKNOW(UTTAR PRADESH).

IV/IV B.Tech (Regular) DEGREE EXAMINATION. Electrical &Electronics Engineering

CONTENTS. 1. Introduction Generating Stations 9 40

Vacuum circuit breakers

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING

# - - Internal * On Line Examination

Improved Arc Interruption of High Voltage SF 6 Circuit Breakers Using Modified Mayr s Differential Equation

Webinar: An Effective Arc Flash Safety Program

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

A controlled arc-flash, produced in a flashtube. Even though the energy level used is fairly low (85 joules), the low-impedance, low-inductance

Busbar and Modular Wiring Systems

Busbars and lines are important elements

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

Technical Seminar for Cathodic Protection to GOGC Design Unit Specialists. Dr. Nick Kioupis, Cathodic & Lightning Protection Section Head, DESFA

The Use of Vacuum Interruption at Transmission Voltages

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012

Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

INTRINSIC SAFETY BASIC PRINCIPLES

SECTION MECHANICAL IDENTIFICATION

HIGH VOLTAGE Insulation Coordination

Arrester Disconnector

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

Vacuum interrupters Introduction

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

Outdoor Installation 2: Lightning Protection and Grounding

Electric Arc model for High Voltage Circuit Breakers Based on MATLAB/SIMULINK

High Energy Rate Forming

Analysis and Modilization of Electric Arc Model for High Voltage Circuit Breaker Based on Matlab/Simulink

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

HIGH ENERGY RATE FORMING PROCESSES

Electrical Equipment Condition Assessment

CONTROL SYSTEM COMPONENTS

Electrical Power Systems

Copper Core & Coil Transformer

2 Grounding of power supply system neutral

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

In order to minimise distribution (11 and 22 kv) feeder breaker

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Cahier technique no. 193

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

EET 3390 COURSE OVERVIEW

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Earthing of Electrical Devices and Safety

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

CX-Series. Circuit Breaker

NON-TRADITIONAL MACHINING PROCESSES ULTRASONIC, ELECTRO-DISCHARGE MACHINING (EDM), ELECTRO-CHEMICAL MACHINING (ECM)

Welcome to the Session on. HT Distribution Network

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

3AV1FG 72.5 kv Prototype Vacuum Circuit Breaker (Case Study with Pilot Customers)

Transformer Protection

High Voltage Generation

High Voltage Engineering

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

4. Classification E: High capacity. 3. Terminal Form Blank: Tab terminals (#250 terminals) Tab terminals #250 SPST-NO

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

4.1.3: Shell Casting.

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Technical information related to the temperature control in electro-thermal applications

New Report Indicates AC Inductance/Electrodynamic Dust Detectors May Be Hazardous. Ron Dechene Auburn Systems, LLC Danvers MA 01923

ADVANCED CIRCUIT BREAKERS OPERATION AND MAINTENANCE SECTOR / ENGINEERING TECHNICAL & CERTIFICATE OF ATTENDANCE TRAINING COURSE

Transcription:

Circuit Breaker By Shashidhar kasthala Assistant Professor Indian Naval Academy

In power system, various circuits (e.g., transmission lines, distributors, generating plants etc.) will be switch on-off under both normal and abnormal conditions. It includes switches, fuses, circuit breakers, relays and other equipment.

FUSE

A fuse consists of a replaceable part (the fuselink) and a fuse holder The simplest fuse link is a length of wire. It is mounted by screw connections in a holder which partly encloses it. When an over current or short-circuit current flows, the wire starts to melt and arcing commences at various positions along it. The arc voltage causes the current to fall and once it has fallen to zero, the arcs are extinguished. The larger the wire cross section, the larger is the current that the fuse link will carry without operating.

The most common fuse link is the cartridge type. This consists of a barrel (usually of ceramic) containing one or more elements which are connected at each end to caps fitted over the ends of the barrel

If a high current breaking capacity is required, the cartridge is filled with sand of high chemical purity and controlled grain size. The entire fuse link is replaced after the fuse has operated and a fault has been disconnected. Cartridge fuses are used for a much wider range of voltages and currents than semi-enclosed fuses.

High-voltage and low-voltage cartridge fuse links (high-voltage fuse (top) and two low-voltage fuses showing a range of fuse sizes)

Fuselinks can be divided into current-limiting and noncurrent-limiting types. A sand-filled cartridge fuselink is of the current-limiting type; when it operates, it limits the peak current to a value which is substantially lower than the prospective current. A non-current-limiting fuse, such as a semi-enclosed fuse, does not limit the current significantly

Sectional view of cartridge fuse-link

Fuse can perform but it two disadvantages. 1. Firstly, when a fuse blows out, it takes quite sometime to replace it and restore supply to the customers. 2. A fuse cannot successfully interrupt heavy fault currents that result from faults on modern high-voltage and large capacity circuits.

Fuse diagram in Household

Melting occurs first at the notches when an over current flows and this results in a number of controlled arcs in series. The voltage across each arc contributes to the total voltage across the fuse, and this total voltage results in the current falling to zero. Because the number of arcs is limited, the fuse link voltage should not be high enough to cause damage elsewhere in the circuit.

The characteristic development of current and voltage during the operation of a fuse

Switches used to open or close an electrical circuit in convenient way It can be used under full-load or no-load conditions but it cannot interrupt the fault currents. When the contacts of a switch are opened, an arc is produced in the air between the contacts which is true for circuits of high voltage and large current capacity. The switches may be classified into (i) Air switches (ii) Oil switches

(i) Air-break switch

An air switch and designed to open a circuit under load To quench the arc that occurs on opening such a switch, special arcing horns are provided Arcing horns are pieces of metals between which arc is formed during opening operation. As the switch opens, these horns are spread farther and farther apart.

Consequently, the arc is lengthened, cooled & interrupted Air-break switches are generally used outdoor for circuits of medium capacity such as lines supplying an industrial load from a main transmission line or feeder.

Isolator or disconnecting switch

It is essentially a knife switch and is designed to open a circuit under no load. Its main purpose is to isolate one portion of the circuit from the other and is not intended to be opened while current is flowing in the line. These are generally used on both sides of CB in order that repairs and replacement of circuit breakers can be made without any danger. They should never be opened until the CB in the same circuit is opened and always be closed before the CB is closed.

Circuit Breaker A circuit breaker is a piece of equipment which can (i) Make or break a circuit either manually or by remote control under normal conditions (ii) Break a circuit automatically under fault conditions (iii) Make a circuit either manually or by remote control under fault conditions

Operating principle CB consists of fixed and moving contacts, called electrodes. Under normal operating conditions, contacts remain closed and will open automatically if the system is faulty. When a fault occurs the trip coils get energized and moving contacts are pulled apart opening the circuit.

When the contacts are separated, an arc is struck between them and current continues until the discharge ceases. The production of arc not only delays the current interruption process but also generates enormous heat The main problem in a circuit breaker is to extinguish the arc within the shortest possible time so that heat generated by it may not reach a dangerous value.

Behavior under fault conditions

Arc The arc has three parts: Cathode end ( ve): There is approximately 30 50 V drop due to emission of Electrons Arc column: Ionized gas, which has a diameter proportional to current. Temperature can be in the range of 6000 25 000 C Anode end (+ve): Volt drop 10 20 V

Arc Phenomenon When a short-circuit occurs, a heavy current flows through the contacts of the circuit breaker before they are opened by the protective system. At the instant when the contacts begin to separate, the contact area decreases rapidly and large fault current causes increased current density and hence rise in temperature. The heat produced in the medium between contacts (usually the medium is oil or air) is sufficient to ionise the air or vapourise and ionise the oil.

The ionised air or vapour acts as conductor and an arc is struck between the contacts. The p.d. between the contacts is quite small and is just sufficient to maintain the arc. The arc provides a low resistance path and consequently the current in the circuit remains uninterrupted so long as the arc persists. During the arcing period, the current flowing between the contacts depends upon the arc resistance.

Factors on which the arc resistance depends (i) Degree of ionisation the arc resistance increases with the decrease in the number of ionised particles between the contacts (ii)length of the arc the arc resistance increases with the length of the arc i.e., separation of contacts. (iii) Cross-section of arc the arc resistance increases with the decrease in area of X-section of the arc.

Principles of Arc Extinction (i) p.d. between the contacts: with a small contact separation, the p.d. between them is sufficient to maintain the arc. To extinguish the contacts are seperated such that p.d. becomes inadequate to maintain the arc. (ii) ionised particles between contacts: The ionised particles between the contacts tend to maintain the arc. If the arc path is deionised, the arc extinction will be facilitated. This can be achieved by cooling the arc or by removing the ionised particles from the space between the contacts.

Methods of Arc Extinction There are two methods of extinguishing the arc in circuit breakers 1. High resistance method 2. Low resistance or current zero method

(i) High resistance method Arc resistance is made to increase with time so that current is reduced to a value insufficient to maintain the arc The resistance of the arc may be increased by: (i) Lengthening the arc Arc resistance is directly proportional to its length. The length of the arc can be increased by increasing the gap between contacts (ii) Cooling the arc - Cooling helps in the deionisation of medium between the contacts (iii) Reducing X-section of the arc - If the area of X-section of the arc is reduced, the voltage necessary to maintain the arc is increased. (iv) Splitting the arc - The resistance of the arc can be increased by splitting the arc into a number of smaller arcs in series

When the arc comes in contact with the metal plates it divides into a number of shorter arcs that bum across a set of adjacent plates The voltage drop that is observed across each of these short arcs is usually about 30 to 40 volts, the majority of this voltage being due to the cathode and anode drop of each arc

Low resistance or Current zero method This method is employed for arc extinction in a.c. circuits only Here arc resistance is kept low until current is zero. Arc extinguishes naturally and is prevented from restriking inspite of the rising voltage across the contacts. All modern high power a.c. circuit breakers employ this method for arc extinction

The de-ionisation of the medium can be achieved by: (i) lengthening of the gap. The dielectric strength of the medium is proportional to the length of the gap between contacts. Therefore, by opening the contacts rapidly, higher dielectric strength of the medium can be achieved. (ii) High pressure. If the pressure in the vicinity of the arc is increased, the density of the particles constituting the discharge also increases. The increased density of particles causes higher rate of deionisation and consequently the dielectric strength of the medium between contacts is increased.

(iii) Cooling. Natural combination of ionised particles takes place more rapidly if they are allowed to cool. Therefore, dielectric strength of the medium between the contacts can be increased by cooling the arc. (iv) Blast effect. If the ionised particles between the contacts are swept away and replaced by unionised particles, the dielectric strength of the medium can be increased considerably. This may be achieved by a gas blast directed along the discharge or by forcing oil into the contact space.

Important Terms (i) Arc Voltage: It is the voltage that appears across the contacts of the circuit breaker during the arcing period. As soon as the contacts of the circuit breaker separate, an arc is formed. Its value is low except for the period the fault current is at or near zero current point. At current zero, the arc voltage rises rapidly to peak value and this peak voltage tends to maintain the current flow in the form of arc.

(ii) Restriking voltage. It is the transient voltage that appears across the contacts at or near current zero during arcing period.

At current zero, a high-frequency transient voltage appears across the contacts and is caused by the rapid distribution of energy between the magnetic and electric fields associated with the plant and transmission lines of the system. This transient voltage is known as restriking voltage The current interruption in the circuit depends upon this voltage. If the restriking voltage rises more rapidly than the dielectric strength of the medium between the contacts, the arc will persist for another half-cycle.

On the other hand, if the dielectric strength of the medium builds up more rapidly than the restriking voltage, the arc fails to restrike and the current will be interrupted. This voltage is given by the expression V = V(1-cos 1/ LC) The normal frequency rms voltage that appears across the breaker contacts after final arc extinction has occurred is called the recovery voltage.

(iii) Recovery voltage It is the normal frequency (50 Hz) r.m.s. voltage that appears across the contacts of the circuit breaker after final arc extinction. It is approximately equal to the system voltage. When contacts of circuit breaker are opened, current drops to zero after every half cycle. At some current zero, the contacts are separated sufficiently apart and dielectric strength of the medium between the contacts attains a high value due to the removal of ionised particles. At such an instant, the medium between the contacts is strong enough to prevent the breakdown by the restriking voltage. Consequently, the final arc extinction takes place and circuit current is interrupted.

Rate of Rise of Restriking Voltage (RRRV). RRRV is obtained by drawing a straight line through zero and tangential to the point of curve and expressed in volts per μs. The average RRRV = (Peak value of restriking voltage)/(time taken in attaining peak value)=(2v m )/(μ LC) RRRVMAX = VM/ LC

Classification of Circuit Breakers (i) (ii) Oil circuit breakers which employ some insulating oil (e.g., transformer oil) for arc extinction. Air-blast circuit breakers in which high pressure air-blast is used for extinguishing the arc. (iii) Sulphur hexafluroide circuit breakers in which sulphur hexafluoride (SF6) gas is used for arc extinction. (iv) Vacuum circuit breakers in which vacuum is used for arc extinction.

Oil Circuit Breakers

In oil circuit breakers, some insulating oil (e.g., transformer oil) is used as an arc quenching medium. The contacts are opened under oil and an arc is struck between them. The heat of the arc evaporates the surrounding oil and dissociates it into a substantial volume of gaseous hydrogen at high pressure.

The hydrogen gas occupies a volume about one thousand times that of the oil decomposed. The oil is, therefore, pushed away from the arc and an expanding hydrogen gas bubble surrounds the arc region and adjacent portions of the contacts

Advantages (i) It absorbs the arc energy to decompose the oil into gases which have excellent cooling properties (ii) It acts as an insulator and permits smaller clearance between live conductors and earthed components. (iii) The surrounding oil presents cooling surface in close proximity to the arc

Disadvantages (i) It is inflammable and there is a risk of a fire. (ii) It may form an explosive mixture with air (iii) The arcing products (e.g., carbon) remain in the oil and its quality deteriorates with successive operations. This necessitates periodic checking and replacement of oil.

Types of Oil Circuit Breakers (i) Bulk oil circuit breakers which use a large quantity of oil. The oil has to serve two purposes. Firstly, it extinguishes the arc during opening of contacts and secondly, it insulates the current conducting parts from one another and from the earthed tank. (ii) Low oil circuit breakers which use minimum amount of oil. In such circuit breakers, oil is used only for arc extinction; the current conducting parts are insulated by air or porcelain or organic insulating material.

Air-Blast Circuit Breakers These breakers employ a high pressure air-blast as an arc quenching medium. The contacts are opened in a flow of air-blast established by the opening of blast valve. The air-blast cools the arc and sweeps away the arcing products to the atomsphere. This rapidly increases the dielectric strength of the medium between contacts and prevents from re-establishing the arc.

Consequently, the arc is extinguished and flow of current is interrupted.

Advantages (i) The risk of fire is eliminated. (ii) The expense of regular oil replacement is avoided. (iii) The growth of dielectric strength is so rapid that final contact gap needed for arc extinction is very small. This reduces the size of the device. (iv) The arcing time is very small due to the rapid build up of dielectric strength between contacts. (v) Due to lesser arc energy, air-blast circuit breakers are very suitable for conditions where frequent operation is required. (vi) The energy supplied for arc extinction is obtained from high pressure air and is independent of the current to be interrupted.

Disadvantages (i) The air has relatively inferior arc extinguishing properties (ii) The air-blast circuit breakers are very sensitive to the variations in the rate of rise of restriking voltage. (iii) Considerable maintenance is required for the compressor plant which supplies the air-blast.

Sulphur Hexaflouride (SF6) Circuit Breakers In CB, sulphur hexaflouride (SF6) gas is used as the arc quenching medium. The SF6 is an electro-negative gas and has a strong tendency to absorb free electrons. The contacts of the breaker are opened in a high pressure flow of SF6 gas and an arc is struck between them. The conducting free electrons in the arc are rapidly captured by the gas to form relatively immobile negative ions. This loss of conducting electrons in the arc quickly builds up enough insulation strength to extinguish the arc. The SF6 circuit breakers have been found to be very effective for high power and high voltage service

Construction

It consists of fixed and moving contacts enclosed in a chamber (called arc interruption chamber) containing SF6 gas. This chamber is connected to SF6 gas reservoir. When the contacts of breaker are opened, the valve mechanism permits a high pressure SF6 gas from the reservoir to flow towards the arc interruption chamber.

The fixed contact is a hollow cylindrical current carrying contact fitted with an arc horn. The moving contact is also a hollow cylinder with rectangular holes in the sides to permit the SF6 gas to let out through these holes after flowing along and across the arc. The tips of fixed contact, moving contact and arcing horn are coated with copper-tungsten arc resistant material. Since SF6 gas is costly, it is reconditioned and reclaimed by suitable auxiliary system after each operation of the breaker.

Advantages 1. Due to the superior arc quenching property of SF6, such circuit breakers have very short arcing time. 2. Since the dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents. 3. The SF6 circuit breaker gives noiseless operation due to its closed gas circuit and no exhaust to atmosphere unlike the air blast circuit breaker.

4. The closed gas enclosure keeps the interior dry so that there is no moisture problem. 5. There is no risk of fire in such breakers because SF6 gas is non-inflammable. 6. There are no carbon deposits so that tracking and insulation problems are eliminated. 7. The SF6 breakers have low maintenance cost, light foundation requirements and minimum auxiliary equipment. 8. Since SF6 breakers are totally enclosed and sealed from atmosphere, they are particularly suitable where explosion hazard exists e.g., coal mines.

Disadvantages 1. SF6 breakers are costly due to the high cost of SF6 2. Since SF6 gas has to be reconditioned after every operation of the breaker, additional equipment is required for this purpose.

Vacuum Circuit Breakers (VCB)

Principle When the contacts of the breaker are opened in vacuum (10 7 to 10 5 torr), an arc is produced between the contacts by the ionisation of metal vapours of contacts. The arc is quickly extinguished because the metallic vapours, electrons and ions produced during arc rapidly condense on the surfaces of the circuit breaker contacts, resulting in quick recovery of dielectric strength. Vacuum is used as an arc quenching medium. As soon as the arc is produced in vacuum, it is quickly extinguished due to the fast rate of recovery of dielectric strength in vacuum.

Working When the breaker operates, the moving contact separates from the fixed contact and an arc is struck between the contacts The production of arc is due to the ionisation of metal ions and depends very much upon the material of contacts The arc is quickly extinguished because the metallic vapours, electrons and ions produced during arc are diffused in a short time and seized by the surfaces of moving and fixed members and shields. Since vacuum has very fast rate of recovery of dielectric strength, the arc extinction in a vacuum breaker occurs with a short contact separation

Advantages 1. They are compact, reliable and have longer life 2. There are no fire hazards 3. There is no generation of gas during and after operation 4. They can interrupt any fault current. The outstanding feature of a VCB is that it can break any heavy fault current perfectly just before the contacts reach the definite open position 5. They require little maintenance and are quiet in operation 6. They can successfully withstand lightning surges 7. They have low arc energy. 8. They have low inertia and hence require smaller power for control mechanism

Comparison of circuit Breaker 1.Insulating methods

2. Influence of Electrode gaps

3.Features of CB

Minatare circuit Breaker