A Resonant Integrator Based PLL and AC Current Controller for Single Phase Grid Connected PWM-VSI

Similar documents
CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Chapter 2 Shunt Active Power Filter

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

A controller design method for 3 phase 4 wire grid connected VSI with LCL filter

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

A Grid Simulator to Evaluate Control Performance of Grid-Connected Inverters

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Synchronization Algorithms for Single Phase System

ABSTRACT I. INTRODUCTION

Investigation of D-Statcom Operation in Electric Distribution System

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Control of grid connected inverter system for sinusoidal current injection with improved performance

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

A LOW POWER SINGLE-PHASE UTILITY INTERACTIVE INVERTER FOR RESIDENTIAL PV GENERATION WITH SMALL DC LINK CAPACITOR

Power Quality Improvement using Shunt Passive Filter

Comparison of Control Algorithms for Shunt Active Filter for Harmonic Mitigation

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Multiple PR Current Regulator based Dead-time Effects Compensation for Grid-forming Single-Phase Inverter

Simulation And Comparison Of Space Vector Pulse Width Modulation For Three Phase Voltage Source Inverter

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

ISSN Vol.03,Issue.07, August-2015, Pages:

Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Grid disturbances

UTILITY interactive inverters converting dc power sources

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

Improved PLL for Power Generation Systems Operating under Real Grid Conditions

A Single-Stage Active Damped LCL-Filter-Based Grid-Connected Photovoltaic Inverter With Maximum Power Point Tracking

Indirect Current Control of LCL Based Shunt Active Power Filter

A Modified Direct Power Control Strategy Allowing the Connection of Three-Phase Inverter to the Grid through LCL Filters

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Literature Review for Shunt Active Power Filters

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Protection from Voltage Sags and Swells by Using FACTS Controller

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INDIRECT CURRENT CONTROLLED SINGLE PHASE SHUNT ACTIVE FILTER

IMPORTANCE OF VSC IN HVDC

Chapter 2 MODELING AND CONTROL OF PEBB BASED SYSTEMS

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant

Design of a Single Phase Power Converter for Battery Characterization

AC Voltage and Current Sensorless Control of Three-Phase PWM Rectifiers

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

Grid Power Quality Analysis of 3-Phase System Using Low Cost Digital Signal Processor

Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

2.4 Modeling and Analysis of Three Phase Four Leg Inverter

Delhi Technological University (formerly DCE) Delhi-42, India

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Power Quality improvement of a three phase four wire system using UPQC

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Performance of DVR under various Fault conditions in Electrical Distribution System

Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Correction

Performance Comparison of Sensor and Sensorless Active Damping LCL Filter for Grid Connected of Wind Turbine

Switching Loss Characteristics of Sequences Involving Active State Division in Space Vector Based PWM

DigSILENT Modelling of Power Electronic Converters for Distributed Generation Networks

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Virtual Instrumentation Applied to Calculation of Electrical Power Quantities in Single-Phase Systems

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

Harmonic Distortion in an Off-Grid Renewable Energy System with Different Loads

Resonance Damping in a Higher Order Filter (LCL) in an Active Front End Operation

On-Line Control of 1ph. She-Pwm Voltage Source Inverter for Statcom Applications

Kalman Filter Based Unified Power Quality Conditioner for Output Regulation

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

COMPARATIVE INVESTIGATION OF SHUNT ACTIVE POWER FILTERS IN 25kV AC ELECTRIFIED SYSTEMS

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Performance Analysis of DSOGI PLL under Balanced and Unbalanced Conditions

IMPROVED CONTROL STRATEGY OF GRID INTERACTIVE INVERTER SYSTEM WITH LCL FILTER USING ACTIVE AND PASSIVE DAMPING METHODS

ISSN Vol.04,Issue.07, June-2016, Pages:

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

Synchronous Current Control of Three phase Induction motor by CEMF compensation

Power Quality enhancement of a distribution line with DSTATCOM

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

Field Programmable Gate Array-Based Pulse-Width Modulation for Single Phase Active Power Filter

Integration of Phase-Locked Loop Based Real-time Oscillation Tracking in Grid Synchronized Systems

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Simulation And Hardware Analysis Of Three Phase PWM Rectifier With Power Factor Correction

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

A Nested Control Strategy for Single Phase Power Inverter Integrating Renewable Energy Systems in a Microgrid

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

CHAPTER 4 DESIGN OF DC LINK VOLTAGE CONTROLLER FOR SHUNT ACTIVE POWER FILTER

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS

EE 560 Electric Machines and Drives. Autumn 2014 Final Project. Contents

SCOTT TRANSFORMER AND DIODE CLAMPED INVERTER FED INDUCTION MOTOR BASED ON FOC

Low Speed Position Estimation Scheme for Model Predictive Control with Finite Control Set

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

AT present three phase inverters find wide range

Modeling and Simulation of STATCOM

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Application of Fuzzy Logic Controller in Shunt Active Power Filter

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Transcription:

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 31 A Resonant Integrator Based PLL and AC Current Controller for Single Phase Grid Connected PWM-VSI D. Venkatramanan Department of Electrical Engineering Indian Institute of Science Bangalore, Karnataka-560012 Email: venkat86ram@gmail.com Vinod John Department of Electrical Engineering Indian Institute of Science Bangalore, Karnataka-560012 Email: vjohn@ee.iisc.ernet.in Abstract Grid connected PWM-VSIs are being increasingly used for applications such as Distributed Generation (DG), power quality, UPS etc. Appropriate control strategies for grid synchronisation and line current regulation are required to establish such a grid interconnection and power transfer. Control of three phase VSIs is widely reported in literature. Conventionally, d- q control in Synchronous Reference Frame(SRF) is employed for both PLL and line current control where PI-controllers are used to track the DC references. Single phase systems do not have defined direct (d) and quadrature (q) axis components that are required for SRF transformation. Thus, references are AC in nature and hence usage of PI controllers cannot yield zero steady state errors. Resonant controllers have the ability to track AC references accurately. In this work, a resonant controller based single phase PLL and current control technique are being employed for tracking grid frequency and the AC current reference respectively. A single phase full bridge converter is being operated as a STATCOM for performance evaluation of the control scheme. I. INTRODUCTION Now a days, grid connected pulse width modulation based voltage source inverters (PWM-VSIs) are becoming exceedingly popular for applications such as DG, power quality, UPS etc. Filters are invariably required to bring down the current and voltage distortions caused by harmonics injected by the VSI into the grid. Many a times, a transformer is also employed after the filter stage to adjust the output voltage level to that of the grid. It is a well known fact that power transfer can take place between two active sources only if their frequencies are matched. In the present case, the two active sources are the grid and the power converter respectively. To establish power transfer between them, grid frequency must be accurately known. Typically, a Phase Locked Loop (PLL) is employed for the purpose of tracking grid frequency. Also, for the overall control, current regulated PWM methods are preferred to voltage controlled PWM methods due to high dynamic performance requirements [4].Thus a current controller is required to regulate the converter line current. Fig. 1. Grid interface scheme of a full bridge power converter through a filter and a transformer for a single phase STATCOM The control of three phase VSI is widely reported in literature [5]. Typically, d-q control/vector control technique is employed where the AC quantities are transformed to DC through Synchronous Reference Frame (SRF) transformation. Consequently, all references become DC in nature and conventional PI controllers would suffice to yield zero steady state errors. The design of PI controllers and PLL implementation (for grid synchronisation) are quite straightforward and well discussed in literature [1]. However, for single phase systems, SRF transformation is not feasible as direct and quadrature axes are not defined. All references in this case are AC in nature [9]. As a result, usage of PI controllers cannot yield zero steady state errors [6]. Its performance may be acceptable if the system bandwidth is very high. But many a times, bandwidth is limited especially at higher power levels. Again, single phase PLL implementation is not as straightforward as the three phase case. In this work, to address these problems, a resonant integrator is being employed for both single phase PLL implementation and line current regulation. The control scheme is implemented on a 3kVA, 240V single phase full bridge converter which is being operated as a STATCOM. Grid interfacing is done through an integrated higher order filter-transformer. The controller design for the system is explained in section-ii.

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 32 II. RESONANT INTEGRATOR A resonant integrator is a generalised AC second order integrator with a tuned resonant frequency ω 0 [3], [8]. The construct of a resonant integrator is shown in Fig.2 and its transfer function is given by Eq.(1). The gain of the resonant controller is infinite at the tuned resonant frequency. H(s) = p(s) e(s) = k is s 2 + ω 2 0 When ω 0 is set to zero, it reduces to a simple integrator or an integral controller. An Integral controller offers infinite gain only at DC. This essentially means for DC references, the loop gain of a system with a PI controller becomes infinity and thus steady state error is forced to zero. For a reference of any other frequency, loop gain is finite and hence steady state error is also finite. (1) Fig. 4. A single phase PLL based on three phase dq-pll in section-iii(a). In case of a three phase PLL, a set of three grid voltages are available as input, and the required stationary frame orthogonal vectors (V α and V β ) are generated by conventional three phase to two phase transformation. Once the orthogonal vectors are found, SRF transformation can be applied to obtain the corresponding d-q components of the grid voltage spacer. SRF transformation is given by, Fig. 2. A resonant integrator with resonant frequency ω 0 and gain k i On the contrary, a proportional-resonant (PR) controller makes the system loop gain infinite at the tuned resonant frequency ω 0 and thereby eliminating any steady state error at that frequency. This can be shown by using internal model principle [6]. For a grid connected application, ω 0 could be appropriately set corresponding to grid frequency (50Hz) such that line current tracks the AC reference. Fig. 3. Frequency response of a resonant controller III. SINGLE PHASE PLL A PLL structure is a feedback control system that automatically adjusts the phase of a locally generated signal to match the phase of an input signal. A general single phase dq-pll structure shown in Fig.4. This scheme is based on a three phase dq-pll except for the orthogonal vector generation scheme. Details of orthogonal vector generation is explained [ Vd Fig. 5. PLL voltage phasor diagram ] [ ] [ ] cos (φ) sin (φ) Vα = V q sin (φ) cos (φ) V β which finally yields the required governing equation, [ ] [ ( Vd cos 3 ] = 2ωt φ) V q sin ( 3 2ωt φ) Now, by suitably setting the references, the grid voltage spacer could aligned along either d or q axis. For instance, to align the grid spacer along q-axis, it is required to set V d to zero. Information about the grid voltage peak is not required. Once this alignment is done, q-axis would correspond to real power axis and d-axis would stand for reactive power. Method of symmetrical optimum may be used to calculate the PLL s PI controller gains [1]. In case of a single phase PLL, the two orthogonal vectors must be generated from the single available grid voltage. Various single phase PLL schemes such as transport delay method [2], pure integrator method, all-pass function method, inverse Park transformation method [2] etc. are available. Each differs from the other in the way of generation of these orthogonal vectors. In this work, the required orthogonal vectors are generated with the help of a resonant integrator [3]. (2) (3)

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 33 A. Orthogonal vector generation Fig.6 represents a scheme for generating two orthogonal sine waves. Fig. 8. Bode plot for V qd (s) V g(s) Fig. 6. Resonant integrator based orthogonal vector generation scheme for single phase PLL It uses two integrators connected back to back. V g represents the grid voltage. Here, ω 0 is set corresponding to 50Hz. The structure offers infinite gain to error (which is at 50Hz at the start) and ensures that it quickly converges to zero. Thus, V ph is always made to follow the 50Hz component of V g. This is exemplified by Fig.7 and Eq.(4). It can be seen that the introduced in the sensor stage and/or in the analog to digital conversion process in the digital controller. Fig. 9. Simulated response of V ph and V qd for a DC offset in Vg Fig. 7. Bode plot for V ph(s) V g(s) structure inherently has filtering property for input frequencies other than 50Hz. V ph (s) V g (s) = ω o s s 2 + ω o s + ωo 2 (4) Fig.8 shows the frequency response of the quadrature component V qd. V qd (s) V g (s) = ωo 2 s 2 + ω o s + ωo 2 (5) It can be clearly seen that the DC gain of Eq.(5) is unity. This means, if the grid voltage V g happens to have a DC offset, it would directly get reflected in V qd. But this is not the case with V ph. V d and V q are no longer DC quantities due do the DC offset present in V qd and this introduces ripples in the PI controller output of the PLL. These DC offsets may be To deal with this, the error (which again contains the same DC offset as V g ) is filtered (using a low pass filter LPF) and subtracted from V qd to get V qd, which is the required orthogonal vector. Now V ph and V qd are used as the stationary frame orthogonal vectors for the single grid voltage V g. Now, SRF transformation may be applied to yield corresponding V d and V q. Once V d is made zero by the PI controller, grid voltage would align along q-axis and V q would then represent the peak of grid voltage. With θ available from the PLL, the sine and cosine unit vectors may be obtained by using appropriate method. IV. SINGLE PHASE CLOSED LOOP CONTROL A single phase full bridge power converter is being operated as a STATCOM. The power circuit of the system is shown in Fig.1. The overall control structure to operate the power converter as a single phase STATCOM is shown in Fig.10. For closed loop control, an outer voltage loop for DC bus voltage maintenance and an inner current loop for converter line current regulation are required. A PI controller would suffice for outer voltage loop. For the current loop, a PR controller is being employed. The inner current loop is designed to be

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 34 Fig. 10. Overall control structure for single phase STATCOM operation faster than the outer voltage loop. The control loop bandwidths used in the design are, f BW (outer) f BW (inner) 10 f BW (inner) f SW 10 A. DC bus voltage determination Before closing the control loop, it is essential to know the desired boost level of DC bus voltage so as to set reference for the outer voltage control loop. This value for the STATCOM, depends on the maximum amount of leading reactive current that needs to be drawn from the grid for a given value of filter inductance. Fig. 11. STATCOM phasor diagram To begin with, a 10% drop across the filter inductance may be assumed. (6) (7) V i(peak) = V dcbus = V g(peak) + ωli g(peak) (8) B. Control strategy = 240 2 + 0.1 240 2 373V (9) Assume V dcbus = 400V (10) In a conventional three phase case where d-q control is employed, I q and I d represent real current and reactive current reference respectively (in synchronous reference frame), provided the grid spacer is aligned along q-axis [5]. For brevity, same notation is being followed here. However, in this case they represent the actual peak values of real and reactive current references respectively in stationary reference frame. In the three phase case, SRF transformation enables decoupling of active and reactive currents and hence makes independent control active and reactive power possible. In the present case, such an isolation is achieved with the help of PLL which produces sinusoidal unit vectors in phase and quadrature with the grid voltage. Since the active power requirement in the system is directly reflected as fall in the DC bus voltage, the output of the outer voltage loop is taken as the peak of active current reference denoted as Iq as shown in Fig.10. The corresponding active AC current reference is obtained by merely multiplying the inphase unit vector with Iq. On similar lines, the reactive current reference is obtained by merely multiplying the quadrature unit vector with Id [10]. Desired I d may be set externally in the controller. But this is not the case with Iq, as it is set by the voltage controller. Feed-forward essentially helps in improving the dynamic performance of the system and completes the decoupling of active and reactive currents. In the present case, the inductive drop feed-forward terms for the current loop can be obtained from the phasor diagram shown in Fig.11. V gf F represents the grid voltage feed-forward term. C. Current controller design PR controller gains can be obtained from the gains selected for the equivalent PI controller (DC compensation network)

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 35 for the system. Then, it is transformed into an equivalent AC compensation network [9].The so obtained regulator gains for the PR controller are, k p P R = k p P I (11) k i P R = 2 k i P I (12) The design procedure here is similar to that of the three phase case [5]. The relevant plant transfer function is given by, G(s) = i i(s) V i (s) = 1 R f + sl f (13) P rated 3kVA V rated 240V I rated 12.5A V dc bus 400V f sw 10kHz f bw(inner) 600Hz k p 4.68 k i 35286 f bw(outer) 8Hz k v 2.5 T v 120ms TABLE I SYSTEM SPECIFICATIONS AND CONTROL LOOP DESIGN DATA Fig. 12. Inner current control loop model G(s)H(s) = 1 = k p (14) st bw st c R f T c = L f Rf The desired PI controller constants are, (15) k p = L f T bw, k i = k p ω bw (16) Therefore, the corresponding constants for PR-controller are, k p = L f T bw, k i = 2k p ω bw (17) D. Voltage controller design For DC bus voltage controller design, the gain of inner current loop can be assumed to be unity (from Eq.(6) and Eq.(7)). To begin with, the same design methodology as that Fig. 13. of a three phase case is adopted. Outer voltage control loop model k = I dc I ac = V l l(rms) 2Vdc (18) kk v sc = 1 (19) st v 2CVdc k v = (20) V l l(rms) T v The voltage controller gains were slightly varied from design values to achieve satisfactory system response. The design values are listed in Table.I Fig. 14. CH1(Yellow,200V/div): Grid voltage; CH2(Blue,5V/div): PLL enable signal; CH3(Pink,5V/div): Quadrature unit vector; CH4(Green,5V/div): In phase unit vector V. EXPERIMENTAL RESULTS A 3kVA IGBT based single phase full bridge power converter was operated as a STATCOM. Sine-triangle comparison PWM technique was employed for switching the IGBTs of the power converter. FPGA based digital platform with ALTERA CYCLONE EP1C12Q240C8 chip was employed for control implementation. Experimental results pertaining to PLL responses are shown in Fig.(14-15) and those pertaining to current controller performance are shown in Fig.(16-17). Fig.14 shows the response of the PLL at start-up. The PLL is able to track the grid voltage within half a cycle. Fig.15 shows that the PLL continues to track the grid voltage even with 40% sag. Fig.16 shows the current feedback and reference signals in the digital controller and the measured output current and voltage at 2.5 kva leading p.f steady state operation. Fig.17 shows the measured output current and grid voltage for a reactive leading reference current change from 10% to 90% in the digital controller. Fig.18 gives a close up view of the output current transient for a leading reactive reference current change from 10% to 90%. It can be noticed that the inverter current starts tracking the reference within a quarter cycle. VI. CONCLUSION A single phase full bridge grid interactive power converter has been designed and tested. A resonant integrator based PLL

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 36 Fig. 15. CH3(Pink,2V/div): Sensed grid voltage; CH2(Blue,5V/div): Enable signal; CH4(Green,5V/div): In phase unit vector; when there is a sudden dip in grid voltage Fig. 18. CH1(Yellow,200V/div): Grid voltage; CH2(Blue,10A/div): Inverter current; CH3(Pink,10V/div): Enable signal; CH4(Green,5V/div): Reference current signal changed from 10% to 90% and AC current controller has been designed for fast transient response of less than a quarter cycle. Experimental results pertaining to STATCOM mode of operation with reactive power reference have been furnished. This type of a power converter control finds application in DG, power quality, UPS etc. Fig. 16. CH1(Yellow, 200V/div): Grid voltage; CH2(Blue,10A/div): Inverter current; CH3(Pink,5V/div): Current feedback signal; CH4(Green,5V/div): Current reference signal; under 90% leading current reference, at steady state 2.5kVA operation REFERENCES [1] V.Kaura, and V.Blasko, Operation of a phase locked loop system under distorted utility conditions, IEEE trans. On Industry Applications, vol.33 n0.1, pp.58-63, 1997. [2] M. Ciobotaru, R. Teodorescu and F. Blaabjerg, Improved PLL structures for single-phase grid inverters, Proc. of PELINCEC05, 6 pages, paper ID 106, 2005. [3] M. Ciobotaru, R. Teodorescu and F. Blaabjerg, A new single-phase PLL structure based on second order generalized integrator, IEEE PESC 2006, Jeju, Korea, p. 1511-1516.B [4] Muhammad.H Rashid, Power Electronics Handbook, Academic press, 2001. [5] J. S. Sivaprasad, T. Bhavsar, R. Ghosh and G. Narayanan, Vector control of three phase AC/DC front-end converter, SADHANA Academy Proceedings in Engineering Sciences, Vol. 33(5), pp 591-613, October 2008. [6] Fukuda S, Yoda T, A novel current-tracking method for active filters based on a sinusoidal internal model, IEEE Transactions in Industrial Applications, vol.37(3), 2001. [7] R. Teodorescu, F. Blaabjerg, M. Liserre and P.C. Loh, Proportionalresonant controllers and filters for grid-connected voltage-source converters, IEE Proc.-Electr. Power Appl., Vol. 153, No. 5, September 2006. [8] Yuan. X, Merk. W, Stemmler. H, Allmeling. J, Stationary-frame generalized integrators for current control of active power filters with zero steady-state error for current harmonics of concern current under unbalanced and distorted operating conditions, IEEE Trans. Ind. Appl., 38(2), 2002. [9] Daniel Nahum Zmood, Donald Grahame Holmes, Stationary Frame Current Regulation of PWM Inverters with Zero Steady-State Error, IEEE Transactions on Power Electronics, vol. 18 (3), 2003. [10] K. Thiyagarajah, V.T Ranganathan, B.S.R Iyengar, A high switching frequency IGBT PWM rectifier/inverter system for AC motor drives operating from single phase supply, IEEE Transactions on Power Electronics, vol. 6, No. 4, 1991. Fig. 17. CH1(Yellow,200V/div): Grid voltage; CH2(Blue,10A/div): Inverter current; CH3(Pink,10V/div): Enable signal; CH4(Green,5V/div): Reference current signal changed from 10% to 90%