Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Similar documents
Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

High Voltage DC Transmission 2

Voltage Source Converter Modelling

The University of Nottingham

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Overview of Actuation Thrust

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

HVDC Solutions for Integration of the Renewable Energy Resources

MMC Design Aspects and Applications. John Strauss Siemens AG.

HVDC High Voltage Direct Current

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018

Overview of Actuation Thrust

VSC Transmission. Presentation Overview. CIGRE B4 HVDC and Power Electronics HVDC Colloquium, Oslo, April LCC HVDC Transmission

The rapid evolution of voltage Source Converters as applied to High Voltage DC power transmission Carl Barker

Modelling of VSC-HVDC for Slow Dynamic Studies. Master s Thesis in Electric Power Engineering OSCAR LENNERHAG VIKTOR TRÄFF

AORC Technical meeting 2014

Control and Operation of Multiterminal

Importance of DC-DC Transformation in Grids of the Future

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

This document is a preview generated by EVS

U I. HVDC Control. LCC Reactive power characteristics

DC Line Protection for Multi-terminal (MT)- HVDC Systems

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Facilitating Bulk Wind Power Integration Using LCC HVDC

Trans Bay Cable A Breakthrough of VSC Multilevel Converters in HVDC Transmission

Grounded HVDC Grid Line Fault Protection Using Rate of Change of Voltage and Hybrid DC Breakers. Jeremy Sneath. The University of Manitoba

Bipole III Transmission Project

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

East-South HVDC Interconnector II, India : in commercial operation since 2003

Impacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults

ATC s Mackinac Back to Back. Summary

New Converter Topologies for High-Voltage Dc Converters. Prof. Ani Gole University of Manitoba, Canada

Reactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors

Fault Current Control Methods for Multi-Terminal DC Systems based on Fault Blocking Converters

ESB National Grid Transmission Planning Criteria

Grid integration of offshore wind farms using HVDC links: HVDC-VSC technology overview

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

IMPORTANCE OF VSC IN HVDC

Sensitivity Analysis of MTDC Control System

Experience with Connecting Offshore Wind Farms to the Grid

Open Access Simulation Toolbox for Wind Power Transmission using High Voltage Direct Current Technology

ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER

Symmetrical Monopole VSC Transmission

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Multi-terminal HVDC operation in a weakly interconnected system: results from Best Paths Demo 3

The Thyristor based Hybrid Multiterminal HVDC System

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Using Fault Current Limiting mode of a Hybrid DC Breaker

MODELLING AND CONTROL OF HYBRID

2-Dimensional Control of VSC-HVDC

ABB Power Systems AB Sweden

DC current interruption tests with HV mechanical DC circuit breaker

Grid West Project HVDC Technology Review

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

Digital Object Identifier: /PESMG URL:

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Round Power Mode

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

Deliverable 16.1: Definition and Specification of Test Cases

Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Modelling and Control of Multi-Terminal HVDC Networks for Offshore Wind Power Generation

Recent trends in High Voltage Direct Current (HVDC)Transmission Systems Abstract

SPECIAL REPORT FOR SC B4 (DC and Power Electronics) C. Bartzsch M. Mohaddes Special Reporters

EH2741 Communication and Control in Electric Power Systems Lecture 2

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Transient system behaviour under DC fault conditions in meshed HVDC system

Topics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control

Review of Worldwide Experience of Voltage Source Convertor (VSC) High Voltage Direct Current Technology (HVDC) Installations

USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID

HVDC AND POWER ELECTRONICS INTERNATIONAL COLLOQUIUM

THE first use of direct current for electrical power transmission

DC current breaking solutions in HVDC applications

Introduction to HVDC VSC HVDC

AEIJST - July Vol 3 - Issue 7 ISSN A Review of Modular Multilevel Converter based STATCOM Topology

SUMMARY. KEYWORDS Advanced Control, Type 4 WTG, Offshore, HVDC, Grid Access, Diode Rectifier Unit. 21, rue d Artois, F PARIS B4-121 CIGRE 2016

Control of multiple VSC-HVDC converters within an offshore AC-hub

Investigation of Hybrid Pseudo Bipolar HVDC Performances Supply Power to Passive AC Network

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012

DC Cable Short Circuit Fault Protection in VSC-MTDC

Protect and survive. Fault protection analysis in low-voltage DC microgrids with photovoltaic generators

Digital Fault Recorder Deployment at HVDC Converter Stations

Integration of Offshore Wind Farms Through High Voltage Direct Current Networks. Luke Livermore School of Engineering Cardiff University

Compact Systems for HVDC Applications Dr. Denis Imamovic

Simulative Study into the Development of a Hybrid HVDC System Through a Comparative Research with HVAC: a Futuristic Approach

Selective Wave-Front Based Protection Algorithm for MTDC Systems

HVDC Transmission and AC hubs for Offshore Wind Generation

Fixed Series Compensation

Impact of VSC Converter Topology on Fault Characteristics in HVDC Transmission Systems

The Effect of an Embedded VSC-HVDC link on the Transient stability of the Dutch and German Transmission Systems

Preprint.

THE ALTERNATE ARM CONVERTER: A NEW HYBRID MULTILEVEL CONVERTER WITH DC- FAULT BLOCKING CAPABILITY

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

Transcription:

1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560 Copyright Wiley 2016 Chapter 10 MMC-HVDC Transmission Technology and MTDC Networks

Outline (1) Introduction 10.2 LCC-HVDC Transmission Technology 10.3 Two-Level VSC-HVDC Transmission Technology 10.3.1 Comparison of VSC-HVDC vs. LCC-HVDC Technology 10.4 Modular Multilevel HVDC Transmission Technology 10.4.1 Monopolar Asymmetric MMC-HVDC Scheme Configuration 10.4.2 Symmetrical Monopole MMC-HVDC Scheme Configuration 10.4.3 Bipolar HVDC Scheme Configuration 10.4.4 Homopolar HVDC Scheme Configuration 10.4.5 Back-to-Back HVDC Scheme Configuration 10.5.1 The North Sea Countries Offshore Grid Initiative (NSCOGI) 10.5.2 Large Integration of Offshore Wind Farms and Creation of the Offshore DC Grid 10.6 Multi-Terminal HVDC Configurations 10.6.1 Series-Connected MTDC Network 2

Outline (2) 10.6.2 Parallel-Connected MTDC Network 346 10.6.3 Meshed MTDC Networks 347 10.7 DC Load Flow Control in MTDC Networks 348 10.8 DC Grid Control Strategies 10.8.1 Dynamic Voltage Control and Power Balancing in MTDC Networks 10.8.2 Power and Voltage Droop Control Strategy 10.8.3 Voltage Margin Control Method 10.8.4 Dead-Band Droop Control 10.8.5 Centralized and Distributed Voltage Control Strategies 10.9 DC Fault Detection and Protection in MTDC Networks 10.10 10.11 DC Circuit Breaker Technologies 10.12 Fault-Current Limiters 10.12.3 10.13 The Influence of Grounding Strategy on Fault Currents 10.14 DC Supergrids of the Future

Introduction LCC HVDC transmission technology is widely recognized as being advantageous for bulk power transmission over long distances, asynchronous interconnections of AC power systems and interconnectors with long submarine cable. In addition the LCC-HVDC technology is utilized as firewall in back-to-back configurations. New Modular Multilevel converter designs have broadened the potential range of HVDC transmission to include application of HVDC schemes in weak AC networks e.g. integration of remote offshore wind power plants to the onshore AC networks. MMC-HVDC technology is foreseen as the most suitable technology for development of Multi Terminal DC (MTDC) networks. 4

Short History of HVDC technology 1957- First commercial installation in Sweden 100kV,DC, 20 MW- Mercury value 1970- First installation with Thyristor values 1997- First VSC HVDC installation (Gotland) 2004- First offshore VSC-HVDC installation Troll oil and gas platform (Norway) 2014- First MMC-HVDC offshore installation for export of wind energy to shore, BorWin2

LCC HVDC transmission technology The converter typically consists of two six-pulse Thyristor bridges, called Graetz bridges, which are series connected on the DC side, and parallel connected on the AC side. By using a YY converter transformer for one bridge and a YD converter transformer for the other bridge, the 6-pulse harmonics are theoretically cancelled, both on the AC and the DC side, which reduces the filtering requirements. AC filters are required to limit the impact of the remaining low order harmonics on the AC network and on the DC side. LCC HVDC systems require connection to a strong AC network in order to ensure the commutation and to avoid operation instability of the converters.

VSC-HVDC transmission technology Voltage Source Converter consisting of IGBTs and large DC capacitors; Converter reactors; DC smoothing reactor; AC filters; Interface transformer; VSC control and protection systems; Auxiliary systems (e.g. cooling systems, auxiliary power, fire protection system, etc.)

Comparison of VSC-HVDC vs. LCC-HVDC technology VSC-HVDC transmission technology has 40 60% smaller footprint compared with the LCC-HVDC technology. 2-level VSC-HVDC has higher converter loses and costs compared with the LCC technology. XLPE cables with polyethylene cross-linked insulation can be utilized to link the VSC-HVDC terminals as power reversal does not require voltage polarity reversal.

Monopolar MMC-HVDC scheme configurations (a) Symetrical Monopole (b) Symetrical Monopole With metalic return (c) Symetrical Monopole With ground electrode return

Bipolar HVDC scheme configuration 2Idc 2Idc With Metaic retun With ground return

Homopolar HVDC scheme configuration 2Idc 2Idc With Metaic retun With ground return

Typical configuration of offshore wind farm with HVDC export link to shore Substation Offshore Wind Farm 1 To WTGs To WTGs AC collector hub With export cable to shore Substation Offshore Wind Farm 2 To WTGs Substation Offshore Wind Farm 3 Offshore AC collector hubplatform AC subsea cable Onshore substation AC Grid Onshore To WTGs OFFSHORE ONSHORE Substation Offshore Wind Farm 4

Multi-terminal HVDC configurations Meshed MTDC networks AC DC Offshore wind generation AC DC Solar PV generation DC DC AC DC AC Offshore Oil&Gas Consumer DC AC AC DC Hydro generation DC AC AC DC DC AC AC DC DC AC Onshore grid HVDC Terminal Parallel connected MTDC network Series connected MTDC network

Load flow control in a DC grid

MTDC grid control system hierarchy

Dynamic voltage control and power balancing in MTDC networks A multi-terminal HVDC system has to operate with unplanned contingencies, such as power exchange variations, loss of a transmission link or a terminal trip. Therefore converter stations injecting active power into the DC grid should limit the possible overvoltage by reducing power import and terminals exporting power should limit the under-voltage by reducing its power export. The chosen control strategy must be able to keep the interconnected system at a stable operating point e.g. stay within the predefined voltage limits. Because of long distances between substations and the risk of communication failure, local control method seems to be a better solution for such a primary control as it is the case with primary control in AC systems.

Power and voltage droop control strategy Current-Voltage control: The current-voltage (I-V) relationship characteristic is used to control the DC voltage in a current-based control strategy. The main advantage of a current-voltage control characteristic is that it reflects the linear control behaviour in the sense that a voltage deviation will result in an equivalent current deviation. As the voltage is linked with charging or discharging the capacitors in the DC system, the control is linear and it is the same for all voltage deviations from any reference value. Voltage power control: In the power based control strategy the DC voltage control is expressed in terms of active power. The power-voltage (P-V) relation is assumed to be linear. The voltage droop control strategy for MTDC networks is similar to the voltage droop control traditionally implemented in AC power system.

Droop control voltage and current characteristics Voltage-Current relation for current droop Voltage-Power relation for current droop Voltage 0.85 0.9 0.95 1 1.05 Voltage 0.85 0.9 0.95 1 1.05 Current -1-0.5 0 0.5 1 Power -1-0.5 0 0.5 1

Voltage margin control method 1.4 Rectifier Inverter 1.4 Rectifier Inverter 1.2 1.2 1.0 1.0 Voltage Udc (p.u.) 0.8 Voltage Udc (p.u.) 0.8 0.6 0.6 0.4 0.4-2 -1 0 1 2-2 -1 0 1 2 Current Idc (p.u.) Power Pdc (p.u.) Refernce point I-droop P-droop

Centralized and decentralized voltage control strategies In a centralized control strategy one converter controls the DC voltage to a constant value of the converter s DC bus voltage, and acts as a DC slack bus. While the other converters control their current/power. In a decentralized voltage control strategy, not all converters take part in the control of the DC voltage similar to AC grids, where some power stations take part in the primary frequency control while others do not. In a distributed control strategy for large multi-terminal DC networks, each DC-voltage-controlling HVDC terminal is assigned to a specific direct voltage set-point control. In distributed control strategy, no single converter is left alone with the responsibility of balancing the power inside the DC network, i.e. the control of the DC system voltage is distributed between several nodes inside the MTDC network.

DC fault detection and protection in MTDC networks (1) Selectivity: The protection system should only operate after a fault (not during normal operation), and only if the fault is in its protection zone. Speed: The protection system should be fast enough to interrupt faults before they reach the unacceptable high values which may cause permanent damage to the DC grid components. Reliability: A good protection system is reliable and has a backup system in case the primary protection system fails. Robustness: The protection system should have the ability to detect faults in normal mode as in degraded mode, and to discriminate faults from any other operation occurring (e.g. setpoint changes, normal switching operations,) Seamless: After the fault clearance, the remaining part of the system should continue operating in a secure state

DC fault detection and protection in MTDC networks (2) Once the fault is detected the location of the fault must be identified and the fault current must be interrupted, and finally the faulty equipment or line must be isolated. In a DC system this can be achieved in three distinct ways: Utilizing DC Circuit Breakers (DCB), interrupting the DC fault current and isolating the faulty section. Fast converter control action (e.g. converters with inherent fault blocking capabilities). Activating the AC breakers of all HVDC converters and isolating the DC grid from the connecting AC networks.

DC current Idc [ka] DC fault current It is essential to detect, limit or interrupt the fault current before reaching critical values in few ms. 20 15 10 5 0-5 0.35 0.4 0.45 0.5 0.55 0.6 0.65 time [s] Halfbridge module Fullbridge module Technologies to limit the DC fault current e.g. fault current limiters and utilize AC breakers MMC topologies with inherent fault blocking capability e.g. Full-bridge topology Interrupt the fault current with DC breakers.

DC fault current development under pole-topole short circuit condition

DC fault detection methods in MTDC Fault detection and location methods Direct based measurement methods Signal Processing based methods Differential protection Distance protection Overcurrent protection Neural network based protection Wavelets based protection Travelling wave based protection Derivative based protection

Example: Mesh HVDC configuration and the dc fault current In a meshed grid the fault currents in the branches are much higher due to summation of individual contributions.

DC breaker technologies Different HVDC breaker technologies: Solid state breaker (fast but expensive and high losses) Hybrid breaker (combination power electronics and fast disconnector switch) Mechanical breaker (making use of auxiliary resonance circuit, slow, not applicable in DC grids)

DC Breaker The direct current in the grid can only be extinguished by inserting a counter-emf that exceeds the driving source U drive, which is typically the DC system voltage. Example: DC grid voltage = 500kV Fault current 10kA The counter emf of 1.5 times nominal voltage, which is 750kV must be inserted to extinguish the DC fault current.

DC breaker

Hybrid DC breaker 1. The power electronic switch in the lowimpedance branch is turned off so that the current must flow through the (low-voltage) varistor; 2. The first thyristor switch in the auxiliary branch is triggered and the current in the low-impedance branch commutates into the uncharged capacitor, thereby eliminating the current through the ultrafast disconnector. The mechanical switch opens and establishes the required voltage withstand capability; 3. The current is commutated through a number of similar branches with varistors with increasing voltage. When a new branch is turned on, the preceding one turns off as the current initially commutates into the uncharged newly inserted capacitor; 4. The last capacitor in the auxiliary branch conducts the current until the voltage reaches the level when the metal-oxide extinguishing branch starts to conduct;,and 5. The metal-oxide varistor inserts a counter-voltage that makes the current drop to zero. The thyristor turns off when the voltage across the varistor drops.

DC Circuit Breaker requirement A DC circuit breaker has to fulfil the following requirements: The DC breaker must function and interrupt the fault current in a few milliseconds. It must create an artificial current zero The breaker must be able to absorb and dissipate large amounts of energy stored in the DC system

DC breaker technologies Resonant DC breakers with serial or parallel resonance circuits Solid state DC breakers Hybrid DC breakers DC breaker energy absorbers inserted in series or in in shunt.

DC breaker operation stages 1. The power electronic switch in the low-impedance branch is turned off so that the current must flow through the (low-voltage) varistor; 2. The first thyristor switch in the auxiliary branch is triggered and the current in the low-impedance branch commutates into the uncharged capacitor, thereby eliminating the current through the ultra-fast disconnector. The mechanical switch opens and establishes the required voltage withstand capability; 3. The current is commutated through a number of similar branches with varistors with increasing voltage. When a new branch is turned on, the preceding one turns off as the current initially commutates into the uncharged newly inserted capacitor; 4. The last capacitor in the auxiliary branch conducts the current until the voltage reaches the level when the metal-oxide extinguishing branch starts to conduct; 5. The metal-oxide varistor inserts a counter-voltage that makes the current drop to zero. The thyristor turns off when the voltage across the varistor drops.

Hybrid dc breakers with MOVs in series Aux DC breaker Low impedance brach Ultra fast diconnector Ultra fast diconnector Auxilary branch Main switch Extinction branch

DC breaker with MOV in parallel + The counter- emf can alternatively be inserted in shun

Influence grounding strategy on fault currents

Influence of grounding strategy on fault currents HVDC schemes and converters can be designed with solid grounding, resistive grounding, or high- or low-impedance grounding. The scheme configuration and the grounding strategy influence the dc fault dynamics and behavior. High impedance grounding results in significant voltage stresses during ac and dc fault conditions. In the event of low impedance grounding, the system will experience significant current stresses. During earth faults in a high-impedance-grounded HVDC scheme, the fault currents are effectively limited. However, the converters will be subjected to large over-voltages, up to twice the normal operating voltage. For a symmetrical bi-pole configuration with an isolated grounding, very high short-circuit currents will flow through the system during a solid pole-to-pole fault. In the event of a single pole-to-ground fault, the system will experience lower shortcircuit currents determined by the grounding impedance. symmetrical MMC-HVDC configurations are designed with high-resistive-grounding configurations. The single pole-to-ground faults will result in a dc voltage imbalance between the poles, and cause the un-faulted pole to be charged by up to 2 p.u. of the normal operating voltage.