Type CA Percentage Differential Relay for Transformer Protection (50 and 60 Hertz)

Similar documents
3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

! CAUTION D TABLE 1

Type CVX and CVX-1 Synchro-Verifier Relays

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping R. Table 1:

A. Photo #9664A14. Figure 1. Type KS-3 Out-of-Step Blocking Relay Without Case

Type KLF Generator Field Protection-Loss of Field Relay

www. ElectricalPartManuals. com Westinghouse HRU Instantaneous Overcurrent Relay with Harmonic Restraint Descriptive Bulletin Page 1

www. ElectricalPartManuals. com Type CGR Ratio Ground Relay Descriptive Bulletin Page 1

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway. Malvern, PA TRANSFORMER DIFFERENTIAL RELAY

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

EASUN REYROLLE LIMITED

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GE K-45307K TRANSFORMER DIFFERENTIAL RELAYS WITH

Power System Protection Manual

GENERALS ELECTRIC INSTRUCTIONS POWER SYSTEMS MANAGEMENT DEPARTMENT PHILADELPHIA, PA. GEK Insert Booklet GEK RESTRAINT CIRCUITS

which is used to shift the phase angle between the two sets of coils to produce torque.

Two variable ac current, variable phase-angle sources Variable dc voltage/current source and latch timer Variable harmonic current source

UNIT II MEASUREMENT OF POWER & ENERGY

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

INTELLIMETER REGISTER

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

Type VDG 13 Undervoltage Relay

POWER SYSTEM II LAB MANUAL

INSTRUCTIONS TYPE SBF STATIC BREAKER FAILURE RELAY

Back to the Basics Current Transformer (CT) Testing

Busbars and lines are important elements

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

which is used to shift the phase angle between the two sets of coils to produce torque.

CATALOG & INSTRUCTION MANUAL. Type LJ High Speed Auxiliary Relays

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Transformer Protection

R-F Skewed Hybrids. Type H1SB and H1SB-R. & R-F Balanced Hybrids Type H1R, H3X and Type H1RB, H3XB and Type H1RB-40. System Manual CH44 VER03

INSTRUCTION MANUAL FOR VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G

TRANSFORMERS INTRODUCTION

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA

GEK-45405G INSTRUCTIONS DIFFERENTIAL VOLTAGE RELAYS TYPE S PVD21A PVD21B PVD21C PVD2ID GENERAL ELECTRIC

GENERAL ELECTRIC INSTRUCTIONS In3ert Booklet GEK GEK-4530/ TRANSFORMER DIFFERENTIAL RELAY WITH PERCENTAGE AND HARMONIC RESTRAINT STD28C TYPE

Synchronism Check Equipment

DANFYSIK A/S - DK-4040 JYLLINGE - DENMARK

Transformer Protection

Protective Relays Digitrip 3000

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

LBI-4938C. Mobile Communications MASTR II POWER AMPLIFIER MODELS 4EF4A1,2,3. Printed in U.S.A. Maintenance Manual

Generator Advanced Concepts

GENERALS ELECTRIC I NSTRUCT IONS GEK-45312A. Insert Booklet GEK TRANSFORMER DIFFERENTIAL RELAY WITH PERCENTAGE AND HARMONIC RESTRAINT

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC.

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

ASX SERIES PACIFIC OPERATION MANUAL AC POWER SOURCE POWER SOURCE

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

Unit Protection Differential Relays

A Practical Guide to Free Energy Devices

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Review 6. unlike poles cause the magnets to attract. like poles cause the magnets to repel.

GEI-98328J. INSTRUCTiONS DIRECTIONAL DISTANCE (REACTANCE RELAY) TYPES. GCX51A Forms 11 and up. GCXS1B Forms 11 and up GENERAL ELECTRIC

Power systems Protection course

Testing Numerical Transformer Differential Relays

Inductance, capacitance and resistance

U, W, and Y -- MULTIPLE LEG STARBARS, SILICON CARBIDE HEATING ELEMENTS

TECHNICAL BULLETIN 004a Ferroresonance

Size 5A, 400 Amp, Single Pole DC Contactor, Normally Closed Type MGAO3, Series A Class Table 2 Operating Coil Ratings

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

CHAPTER 5 CONCEPTS OF ALTERNATING CURRENT

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

OVEN INDUSTRIES, INC. Model 5C7-362

Distribution/Substation Transformer

Variable Transformers Product Design & Engineering Data

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

INSPECTION AND CORRECTION OF BELLHOUSING TO CRANKSHAFT ALIGNMENT

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

PROTECTION of electricity distribution networks

www. ElectricalPartManuals. com TypeCW Power Relay Descriptive Bulletin Page 1

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Verifying Transformer Differential Compensation Settings

SECTION PANELBOARDS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Style FR HI Shunt Track Unit

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

SINGLE-PHASE VSV SWITCH

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

Beyond the Knee Point: A Practical Guide to CT Saturation

g GE POWER MANAGEMENT

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

Basic Electrical Training

Transformer Protection Principles

HPS Universal BUCK-BOOST TRANSFORMERS

A1000 ALPHA and A1200 ALPHA Meter Installation Instructions. General. Installation. For A1000 ALPHA Type R, A1000 ALPHA Type C, and A1200 ALPHA Meters

WATT TRANSDUCER. Instruction Manual

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Load-Trainer Transformer Simulator

High Frequency Sinewave Guardian TM Filter

Crane Control Class 7001

Transcription:

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-332.2F Effective: May 1992 Supersedes I.L.41-332.2E, Dated February 1984 ( ) Denotes Change Since Previous Issue. ype CA Percentage Differential Relay for ransformer Protection (50 and 60 Hertz)! CAUION Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment, make sure that all moving parts operate freely, inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings and electrical connections. 1.0 APPLICAION he type CA percentage differential relay for transformer protection is designed for the protection of power transformer. his relay can be applied where the magnetizing inrush current to the transformer is not severe. Current transformer ratio error should not exceed 10% with maximum symmetrical external fault current flowing. he sensitivity of type CA relay for transformer protection is 50%. It satisfactorily handles up to 35% of mismatch (transformer tap-changing under load plus ct mismatch) 2.0 CONSRUCION he type CA relay consists of a percentage differential unit and an indicating contactor switch. he principle component parts of the relay and their locations are shown in Figures 1 through 3. 2.1 PERCENAGE DIFFERENIAL UNI his unit is an induction disc unit with an electro-magnet that has poles above and below the disc as shown in Figure 2. wo restraint coils are placed on the lower left-hand pole (front view) and an operating coil is wound on the lower right-hand pole. A transformer winding is supplied on both the left and right hand poles and these are connected in parallel to supply current to the upper pole windings. he upper pole current generates a flux which is in quadrature with the lower pole resultant flux, and the two fluxes react to produce a torque on the disc. If the operating winding is energized, this torque is in the contact closing direction, if current flows through the two restraining windings in the same direction a contact opening torque is produced. 2.2 INDICAING CONACOR SWICH UNI (ICS) he dc indicating contactor switch is a small clapper type device. A magnetic armature, to which leafspring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts completing the trip circuit. Also during this operation two fingers on the armature deflect a spring located on the front of the switch which allows the operation indicator target to drop. he target is reset from the outside of the case by a push rod located at the bottom of the cover. he front spring, in addition to holding the target, provides restraint for the armature and thus controls the pick-up value of the switch. All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power &D Company Inc. representative should be contacted. Printed in U.S.A.

Figure 1. ype CA ransformer Relay (Front View). Figure 2. ype CA ransformer Relay (Rear View). Figure 3. Internal Schematic of the ype CA ransformer Relay in he ype F-21 Case. Sub 2 Sub 1 57D4554 182A885 Figure 4. Schematic Diagrams of the Percentage Differential Relays: (A) Fault Current Distribution for an External Fault. (B) Distribution for an Internal Fault. 2

3.0 OPERAION With the relay connected as in the schematic diagram, Figure 4.(A), a through fault causes currents to flow through two restraint windings in the same direction. If the current transformers operate properly, these restraining currents are equal, or effectively equal if appropriate auto balance taps are used to compensate for mismatch in current transformer ratios and no effective current flows in the operating coil winding and hence only contact opening torque is produced. If the currents in the two restraining windings are effectively unequal, the effective difference must flow in the operating coil. he operating coil current required to overcome the restraining torque and close the relay contacts is a function of restraining current. In the case of heavy internal fault, when an external source feeds current into the fault, the restraining currents are in opposite directions and restraining torque tends to cancel out as illustrated in Figure 4.(B). When the currents fed from the two sides are equal or effectively equal because of the taps used, the restraint is totally cancelled. When effectively unequal currents flow in from the two sides, the restraint is equivalent to the difference in the two effective currents, divided by two, but since the more sensitive operating coil is energized by the sum of the two currents, the restraint in this case is inconsequential, and a large amount of contact closing torque is produced. 4.0 CHARACERISICS he operating characteristics of the relay for normal through load current and through fault current are shown in Figures 5 and 6. When the currents flowing into and out of the relay are plotted on these curves, if the point falls outside of the inoperative area, the relay will close its contacts. In Figures 5 and 6, the two curves going with the 5-5 tap are tied together with a bracket to indicate that these two curves go together. Similarly, the two curves for the 5-10 tap are also tied together with a bracket. he center lines between pairs of curves are shown for all taps. he paired curves, bounding the inoperative areas, are not shown for taps 5-5.5 through 5-9. hese curves may be determined approximately by means of the following formulas: For the upper curve: I 9 = I 7 * K 1 / + 1.8 (1) For the lower curve: I 7 = I 9 * K2 * + C 2 (2) he relations between, K 1, K 2, and C 2 are given in the following table: K 1 K 2 C 2 5 7.28.276 2.5 5.5 7.32.274 2.65 6 7.36.272 2.8 6.6 7.41.27 2.98 7.3 7.46.268 3.19 8 7.52.265 3.4 9 7.6.262 3.7 10 7.67.258 4 In these formulas, is the larger number of the tap pair. For example, if the relay is used on the 5 7.3 tap, then = 7.3. As an example of the degree of accuracy of the formula consider the point I 7 = 43.5, and I 9 = 30, read from the lower curve for the 5 5 tap, Figure 4. Applying the formula, Equation (2) the calculated value of I 7 is found to be 45 amperes, which is fairly close to the curve value, I 7 = 43.5. he derivations of Equations (1) and (2) are given in Figure 7, which has been included to illustrate the meaning of these equations. ypical time-of-operation curves are shown in Figure 9. Figure 8 shows the operating curves for the relay with the restraining currents 180 out-of-phase. hese curves also apply where current flows in only one restraining winding and the operating coil. 4.1 RIP CIRCUI he main contacts will safely close 30 amperes at 250 dc and the seal-in contacts of the indicating contactor switch will safely carry this current long enough to trip a circuit breaker. he indicating contactor switch has two taps that provide a pick-up setting of 0.2 or 2 amperes. o change taps require connecting the lead located in front of the 3

Sub 2 Sub 2 183A161 183A162 Figure 5. ypical Operating Curves for Low Values of Current. tap block to the desired setting by means of a screw connection. 4.2 RIP CIRCUI CONSAN Indicating Contactor Switch (ICS) 0.2 Ampere ap 6.5 Ohms dc Resistance 2.0 Ampere ap 0.15 Ohms dc Resistance 4.3 ENERGY REQUIREMENS he 60 Hz burdens of the type CA relay are best given in curve formulas illustrated and given by the curves, Figures 10,11, and 12. he burden data of the 50 Hz relay can be approximately estimated by using the following equations. θ 2 = arc an 5 6 -- an θ 1 V 2 I 2 = V 1 I 1 cos 2 θ 25 1 + ----- sin 2 θ1 36 Where the V 1 I 1 & θ 1 and V 2 I 2 & θ 2 are the VA and angles for the 60 and 50 Hz relays respectively. Figure 10, gives the 60 Hz VA burdens only. he 50 Hz equivalent curves can be obtained by using the 60 Hz curve times a factor of 0.88. he restraining windings of the relay have a continuous rating of 10 amperes. he operating coil has a continuous rating of 5 amperes. However, it is best not to allow more than 5 amperes in the untapped restraining winding in order to keep from over-loading a portion of the operating winding. For example, currents of 10 and 6.85 amperes would be in the proper Figure 6. ypical Operating Curves for High Values of Current. ratio of the 5-7.3 taps, but when these taps are used, 6.85 amperes would flow in a portion of the 5 ampere operating coil. 5.0 SEINGS! CAUION Since the tap block screw carries operating current, be sure that the screws are turned tight. In order to avoid opening current transformer circuits when changing taps under load, the relay must be first removed from the case. Chassis operating shorting switches on the case will short the secondary of the current transformer. he taps should then be changed with the relay outside of the case and then reinserted into the case. 5.1 PERCENAGE DIFFERENIAL UNI he transformer relay is detailed in Figure 4. When the relay is correctly set, one screw must be in the lower row of holes at the correct tap value and the other must be in the hole directly above. o determine the correct tap setting, calculate the currents delivered to the relay at full load on the transformer bank, taking into consideration not only the current transformer ratios, but also any delta connections which may be used. hese currents will be in a certain ratio and the taps on the relay should be chosen to match that ratio as closely as possible. For example, assume that the currents are 7.8 and 4.6 amperes, with the relay properly connected so that the higher current, 7.8 amperes, flows in the tapped 4

Case I 5 I 7 > I 9 Figure 7. I 7 Fundamental Relationships in the ype CA Electromagnet. restraining winding. he ratio 4.6/7.8 is equal to 5/ 8.48. he nearest tap ratio on the relay is 5/8, and this pair of taps should be used. he time dial should be set on the number 1 position. 5.2 INDICAING CONACOR SWICH For the ICS unit, the selection of the 0.2 or 2.0 amp tap setting must be made by connecting the lead located in front of the tap block to the desired setting by means of the connecting screw. When the relay energizes a 125 or 250 volt dc type WL relay switch, or equivalent, use the 0.2 ampere tap; for 48 Vdc applications set relay in 2 ampere and use WL relay coil S#304C209G01 or equivalent. For direct tripping of a circuit breaker use the 2 ampere tap. 6.0 INSALLAION OPERAING COIL RESRAINING COILS I (EFFECIVE) = 5 I D 7 I 9 SINCE HE RELAY IS A 50% RELAY 5 I 7 - I 9 = 0.5 I 9 FOR MINIMUM OPERAING CURREN FROM WHICH I 7 =.3 I 9 CASE II I 9 > 5 I 7 I 7 5A 6.1 MOUNING he relays should be mounted on switchboard panels or their equivalent in a location free from dirt, I D I D I 9 I 9 OPERAING COIL RESRAINING COILS I (EFFECIVE) = I D 9-5 I 7 SMALLER RESRAIN CURREN (EFFECIVE) = I = 5 I 7 9 I = 0.5 I FOR MINIMUM OPERAING CURREN D 7 FROM WHICH I 9-5 I 7 = 0.5 (5 I 7 ) AND I 9 = 7.5 I 7 5B dtp I 7 AMPERES IN APPED RESRAINING COIL 6 5 4 3 2 1 0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Figure 8. ypical Sensitivity Characteristics of the ype CA ransformer Relay. moisture, excessive vibration, and heat. Mount the relay vertically by means of the four mounting holes on the flange for semi-flush mounting or by means of the rear mounting stud or studs for projection mounting. Either a mounting stud or the mounting screws may be utilized for grounding the relay. he electrical connections may be made directly to the terminals by means of screws for steel panel mounting or to the studs furnished with the relay for thick panel mounting. he terminal studs may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench. For detailed F Case information refer to I.L. 41-076. 6.2 CONNECION Figure 14 shows the connections for a delta-wye transformer with the delta on the high voltage side. he current transformer connections must be different from this when the delta is on the low voltage side because the phase relationships between high and low currents is different. 7.0 ADJUSMENS AND MAINENANCE he proper adjustments to insure correct operation of this relay have been made at the factory and should not be disturbed after receipt by the customer. 7.1 PERFORMANCE ESS 5-10 5-7.3 Ampere Ratio aps 5-5 I 9 AMPERES IN UNAPPED RESRAINING COIL he following check is recommended to verify that the relay is in proper working order. dtp 5

Sub 1 187A778 Figure 9. ypical ime Curves for the ype CA transformer Relay. 282267 Figure 10. ypical 60 Hertz Saturation Curves for the ype CA ransformer Relay. 7.1.1 Contact he index mark on the movement frame will coincide with the O mark on the time dial when the stationary contact has moved through approximately one-half of its normal deflection. herefore, with the stationary contact resting against the backstop, the index mark is offset to the right of the O mark by approximately.020 inch. he placement of the one time dial position in line with the index will give operating times as shown on the respective time-current curves. For double trip relays, the follow on the stationary contacts should be approximately 1/32 inch. 7.1.2 Minimum rip Current With the relay set on the 5-5 tap, the contacts should close within the following limits with current applied to the specified terminals: erminal 9 and 5... 2.7 to 2.8 amperes erminal 7 and 5... 2.9 to 3.2 amperes 7.1.3 Differential Characteristics Connect the relay per the test circuit of Figure 13 (normal connection). Set the relay on the 5-5 tap and apply 20 amperes to terminal 9. he relay should just operate when the current from terminal 7 is between the limits of 28.5 to 31.5 amperes. he above points should be taken with the relay cool. Care should be taken not to overheat the relay. Reverse the connection to terminal 7 and 9 and apply 20 amperes to terminal 7. he relay should just operate when the current from terminal 9 is between the limits of 29 to 33 amperes. 7.1.4 ime Curve With the time dial on the number 1 position, apply 20 amperes to terminals 5 and 9. he relay should operate between.080 and.10 seconds with a tap setting of 5-5. 7.1.5 Indicating Contactor Switch (ICS) Close the main relay contacts and pass sufficient dc current through the trip circuit to close the contacts of the ICS. his value of current should not be greater than the particular ICS tap setting being used. he indicator target should drop freely. For proper contact adjustment, insert a.030" feeler gauge between the core pin and the armature. Hold the armature closed against the core pin and gauge and adjust the stationary contacts such that they just make with the moving contact. Both stationary contacts should make at approximately the same time. he contact follow will be approximately 1/64 to 3/64. 6

282372 282373 Figure 11. ypical 60 Hertz Burden Curves for the ype CA ransformer Relay on the 5-5 ap (I 5 =0). Figure 12. ypical 60 Hertz Burden Curves for the ype CA ransformer Relay on the 5-10 ap (I 5 =0). 7.2 CALIBRAION Use the following procedure for calibrating the relay if the relay has been taken apart for repairs or the adjustments disturbed. his procedure should not be used until it is apparent that the relay is not in proper working order (see Section 7.1, Performance est). 7.2.1 Contact he index mark on the movement frame will coincide with the O mark on the time dial when the stationary contact has moved through approximately onehalf of its normal deflection. herefore, with the stationary contact resting against the backstop, the index mark is offset to the right of the O mark by approximately.020". he placement of the one time dial position in line with the index mark will give operating times as shown on the respective time-current curves. For double trip relays, the follow on the stationary contacts should be approximately 1/32. 7.2.2 Minimum rip Current he adjustments of the spring tension in setting the minimum trip current value of the relay is most conveniently made with he damping magnet removed. With a tap setting of 5-5, apply current to terminals 9 and 5 of the relay and adjust the control spring tension so that the moving contacts just closes between limits of 2.7 to 2.8 amperes. Apply current to terminals 7 and 5 of the relay. he contacts should just close between the limits of 2.9 to 3.1 Ampere. 7.2.3 Percentage Slope Characteristics Points on the percentage slope curve can be checked by use of the test circuit of Figure 13. he operating current required to operate the relay 7

should be within ±7% of the curve value. Care should be taken not to overheat the relay during these tests. 7.2.4 ime Curve Place the permanent magnet of the relay and set the time dial at the number 1 position. Adjust the permanent magnet keeper until the contacts close between the limit of.085 to.095 seconds. With 20 amperes applied to terminals 5 and 9. 7.2.5 Indicating Contactor Switch (ICS) Sub 5 182A810 Figure 13. Diagram of est Connections for the ype CA ransformer Relay in the ype F-21 Case Close the main relay contacts and pass sufficient dc current through the trip circuit to close the contacts of the ICS. his value of current should be not greater than the particular ICS tap setting being used. he operation indicator target should drop freely. Sub 3 182A808 Figure 14. External Schematic Diagram of the ype CA ransformer Relay in the ype F-21 Case for Protection of a Wye-Delta. ransformer Bank For proper contact adjustment, insert a.030" feeler gauge between the core pin and the armature. Hold the armature closed against the core pin and gauge and adjust the stationary contacts such that they just make with the moving contact. Both stationary contacts should make at approximately the same time. he contact follow will be approximately 1/64 to 3/64. 7.3 ROUINE MAINENANCE All relays should be checked at such time intervals as may be dictated by experience to be suitable to the particular application. All contacts should be periodically cleaned. A contact burnisher S#182A836H01 is recommended for this purpose. he use of abrasive material for cleaning contacts is not recommended, because of the danger of embedding small particles in the face of the soft silver and thus impairing the contact. 8.0 RENEWAL PARS Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be furnished to the customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data. 8

his Page Reserved for Notes 9

Sub 3 182A807 Figure 15. External Schematic Diagram of the ype CA ransformer Relay in the ype F-21 Case for Protection of a Delta-Delta ransformer Bank. 10

Sub 3 185A530 Figure 16. Relay ype CA Percentage with I.I.. For ransformer Protection in ype F-21 Case. Sub 2 183A658 Figure 17. Relay ype CA Percentage Differential for ransformer Protection - Double rip in ype F-21 Case. 11

Figure 18. Outline and Drilling Plan for the ype CA ransformer Relay in ype F-21 Case * Denotes Change * Sub 16 57D7901 Printed in U.S.A. visit our website at www.abbus.com/papd ABB Automation Inc. 4300 Coral Ridge Drive Coral Springs Florida 33065 EL: 954-752-6700 FAX: 954-345-5329 12